2016-08-25 19:18:20 | 2ND ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: |
| JOB ADDRESS: 3240 NORTH FLAGLER DR. |
| DESCRIPTION: RENOVATION |
| MASTER PERMIT: 16061191 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| PER THE NEC AND THE FBC-R YOU SHALL PROVIDE THE |
| FOLLOWING FOR A SUCCESSFUL ELECTRICAL PLAN REVIEW: |
| |
| 1. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM |
| SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS |
| SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR |
| SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE |
| SITE SPECIFIC. ALONG WITH THE LOCATION OF THE ELECTRIC |
| METER AND THE MDP, YOU SHALL MARK ON THE FLOOR PLAN THE |
| LOCATION OF EACH ELECTRICAL LOAD CENTER MENTIONED ON |
| THE ABOVE RISER DIAGRAM. |
| 2. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A |
| PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING |
| THE SPECIFIC PURPOSE OF EVERY CIRCUIT. THIS APPLIES TO |
| EACH PANEL IDENTIFIED ABOVE. |
| 3. ITEMS A THRU E BELOW CAN BE ADDRESSED WITH A BLOCK |
| NOTE ON THE PLANS. |
| A) FBC-RE3902.12/NEC 210.12(B) ARC-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION. ALL BRANCH CIRCUITS |
| THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| OUTLETS INSTALLED IN FAMILY ROOMS, DINING ROOMS, LIVING |
| ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS AND SIMILAR ROOMS |
| OR AREAS SHALL BE PROTECTED BY A COMBINATION TYPE |
| ARC-FAULT CIRCUIT INTERRUPTER INSTALLED TO PROVIDE |
| PROTECTION OF THE BRANCH CIRCUIT. |
| B) FBC-RE4002.9 NEC 406.9(B) RECEPTACLES IN WET |
| LOCATIONS. 15 AND 20 AMPERE, 125 AND 250 VOLT |
| RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN |
| ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE |
| ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE, |
| 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED |
| WEATHER-RESISTANT TYPE ?WR?. |
| C) FBC-R4002.14 NEC 406.12 TAMPER-RESISTANT RECEPTACLES |
| IN DWELLING UNITS. IN ALL AREAS SPECIFIED IN 210.52, |
| ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES SHALL BE |
| LISTED TAMPER RESISTANT RECEPTACLES. |
| D) FBC-ER404.1 LIGHTING EQUIPMENT (MANDATORY). A |
| MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| EFFICACY LAMPS. |
| E) BOTH, THE OUTLETS BELOW TUB AND THE TUB MOTOR SHALL |
| BE ACCESSIBLE. |
| 4. FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. DURING THIS |
| REVIEW I NOTICED MISSING SMOKE DETECTORS AT THE BOTTOM |
| OF STAIR 113, HALL 201, AND SUITE LIVING ROOM 218. |
| 5. FBC-R315.1 CARBON MONOXIDE PROTECTION. EVERY |
| SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 |
| MM) OF EACH ROOM USED FOR SLEEPING PURPOSES |
| 6. FBC-RE3901.7 NEC 210.52(E)(3) BALCONIES. BALCONIES, |
| DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM INSIDE THE |
| DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| INSTALLED WITHIN THE PERIMETER OF THE BALCONY, DECK, OR |
| PORCH. THE RECEPTACLE SHALL NOT BE LOCATED MORE THAN |
| 2.0 M (61?2 FT.) ABOVE THE BALCONY, DECK, OR PORCH |
| SURFACE. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |