Plan Review Details - Permit 16061174
Plan Review Stops For Permit 16061174
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-02-01 Cont ID  
Sent By jgomez Date 2017-02-01 Time 09:19 Rev Time 0.00
Received By jgomez Date 2017-02-01 Time 08:41 Sent To Z
Notes
2017-02-01 09:20:10 
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 INSTALLATION OF BRICK VENEER, INCLUDING VENEER SUPPORTS
 AT OPENINGS. ALSO, SPECIFY WEEP-HOLES, ETC.
 NOTE: PROVIDE COMPLETE DETAILS/ SPECIFICATIONS. DON'T
 CITE CODE SECTIONS.
  
 2- ENERGY CALCULATIONS WERE REVISED FOR FULL HOUSE
 COMPLIANCE INSTEAD OF ADDITION ALONE:
 A) REVISE CEILING INSULATION ITEM #10 TO MATCH PLANS.
 VENTED AND UNVENTED ROOFS.
 B) REVISE ROOF MATERIAL SHOWN ON PAGE 2 OF 5 TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED.
 C) REVISE CONCRETE BLOCK INSULATION ITEM #9 DOESN'T
 MATCH PLANS. SEE DETAIL #2 ON SHEET A-10.
 D) REVISE R-VALUE SHOWN ON THE CEILING INSULATION ON
 PAGE 3 OF 5 TO MATCH PLANS AND INFORMATION SHOWN ON
 ITEM #10.
 E) REVISE DOOR TYPE SPECIFIED ON PAGE 3 OF 5 TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. THERE ARE NO
 INSULATED DOORS. DOORS WITH GLASS NEED TO BE INCLUDED
 IN THE WINDOWS AREA.
 F) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS.
 G) REVISE NUMBER OF OCCUPANTS ON PAGE 2 OF 5. WHY 20
 PEOPLE IN A SINGLE FAMILY RESIDENCE.
 H) REVISE FLOOR TYPES ON PAGE 2 OF 5. 2ND FLOOR IS NOT
 ON SLAB ON GRADE.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOORS THAT MEETS ALL THE DESIGN LOADS SHOWN
 ON SHEET S-6 (POSITIVE AND NEGATIVE).
 B) DOUBLE EXTERIOR DOORS THAT MEET THE DESIGN PRESSURES
 SPECIFIED ON SHEET S-6 FOR FAMILY ROOM AREA.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-01-05 Cont ID  
Sent By jgomez Date 2017-01-03 Time 13:31 Rev Time 0.00
Received By jgomez Date 2016-12-30 Time 16:49 Sent To M
Notes
2016-12-30 16:53:20 
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 INSTALLATION OF BRICK VENEER, INCLUDING VENEER SUPPORTS
 AT OPENINGS. ALSO, SPECIFY WEEP-HOLES, ETC.
 NOTE: PROVIDE COMPLETE DETAILS/ SPECIFICATIONS. DON'T
 CITE CODE SECTIONS.
  
 2- ENERGY CALCULATIONS WERE REVISED FOR FULL HOUSE
 COMPLIANCE INSTEAD OF ADDITION ALONE:
 A) REVISE CEILING INSULATION ITEM #10 TO MATCH PLANS.
 VENTED AND UNVENTED ROOFS.
 B) REVISE ROOF MATERIAL SHOWN ON PAGE 2 OF 5 TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED.
 C) REVISE CONCRETE BLOCK INSULATION ITEM #9 DOESN'T
 MATCH PLANS. SEE DETAIL #2 ON SHEET A-10.
 D) REVISE R-VALUE SHOWN ON THE CEILING INSULATION ON
 PAGE 3 OF 5 TO MATCH PLANS AND INFORMATION SHOWN ON
 ITEM #10.
 E) REVISE DOOR TYPE SPECIFIED ON PAGE 3 OF 5 TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. THERE ARE NO
 INSULATED DOORS. DOORS WITH GLASS NEED TO BE INCLUDED
 IN THE WINDOWS AREA.
 F) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS.
 G) REVISE NUMBER OF OCCUPANTS ON PAGE 2 OF 5. WHY 20
 PEOPLE IN A SINGLE FAMILY RESIDENCE.
 H) REVISE FLOOR TYPES ON PAGE 2 OF 5. 2ND FLOOR IS NOT
 ON SLAB ON GRADE.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOORS THAT MEETS ALL THE DESIGN LOADS SHOWN
 ON SHEET S-6 (POSITIVE AND NEGATIVE).
 B) DOUBLE EXTERIOR DOORS THAT MEET THE DESIGN PRESSURES
 SPECIFIED ON SHEET S-6 FOR FAMILY ROOM AREA.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-31 Cont ID  
Sent By jgomez Date 2016-10-31 Time 18:01 Rev Time 0.00
Received By jgomez Date 2016-10-27 Time 11:06 Sent To  
Notes
2016-10-27 11:25:22RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING PLAN REVIEW MAY BE PASSED WITH PROVISO.
 CONTRACTOR (OWNER/BUILDER) MAY SUBMIT THE REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTIONS TO AVOID CONFLICTS/DELAYS. CONTRACTOR
 (OWNER/BUILDER) TO ADVICE IF PROVISO OPTION IS
 PREFERRED AT THIS TIME.
 REVISION FEES MAY APPLY.
  
  
 1- DETAIL 3/S-1 IS INCOMPLETE: PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS FOR THE INSTALLATION OF BRICK VENEER
 SHOWING COMPLIANCE WITH SEC. R703.7 FBC-RESIDENTIAL.
 SPECIFY BRICK VENEER SUPPORT AT BOTTOM AND AT OPENINGS.
 ALSO, SPECIFY WEEP-HOLES, ETC.
  
 2- PROVIDE SOIL TEST REPORTS WITH ORIGINAL SEAL &
 SIGNATURES (NO COPIES) AS REQUIRED BY CHAPTER 471 F.S.
  
 3- PLANS TO SPECIFY THE FINISH ELEVATION OF THE
 MECHANICAL AND UTILITY EQUIPMENT SERVICING THE
 BUILDING. NEED AT LEAST 7'-6" ELEVATION. SEC. 94- 546
 CITY CODE.
  
 4- ENERGY CALCULATIONS SUBMITTED:
 A) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). REPEAT COMMENT. NOTE: OWNER IS APPLYING FOR THE
 PERMIT AS THE CONTRACTOR. OWNER/BUILDER HAS THE SAME
 RESPONSIBILITIES AS A CONTRACTOR.
  
 B) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION
 CHECKLIST ON TABLE 402.4.1.1 SUBMITTED. SEC. R405.4.3
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). REPEAT
 COMMENT. NOTE: OWNER IS APPLYING FOR THE PERMIT AS THE
 CONTRACTOR. OWNER/BUILDER HAS THE SAME RESPONSIBILITIES
 AS A CONTRACTOR.
  
 C) CEILING INSULATION ITEM #10 DOESN'T MATCH PLANS.
 COORDINATE CEILING INSULATION INSULATION WITH
 ARCHITECTURAL PLANS. SEE WALL SECTION 8-8 ON SHEET A-9.
 SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 NOTE: CLARIFY IF THE 1901 S.F. AREA SHOWN ON ITEM #6 OF
 THE ENERGY CALCULATIONS SUBMITTED IS FOR THE ADDITION
 OF THE FIRST FLOOR ON THE NORTH SIDE AND THE TWO STORY
 ADDITION ON THE EAST SIDE. THE CEILING VENTING AND
 INSULATION VARIES ON BOTH AREAS OF THE HOUSE. SEE
 PLANS. ENERGY CALCULATIONS TO MATCH PLANS. REVISE AS
 REQUIRED.
  
 D) ROOF MATERIAL SHOWN ON PAGE 2 OF 4 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SEC. R103.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT. NOT ADDRESSED).
  
 E) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME, PERMIT OFFICE, JURISDICTION
 NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). REPEAT COMMENT. NOTE: OWNER IS APPLYING
 FOR THE PERMIT AS THE CONTRACTOR. OWNER/BUILDER HAS THE
 SAME RESPONSIBILITIES AS A CONTRACTOR.
  
 NEW COMMENTS:
 F) CONCRETE BLOCK INSULATION ITEM #9 DOESN'T MATCH
 PLANS. SEE DETAIL #2 ON SHEET A-10 AND REVISE AS
 REQUIRED. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 G) R-VALUE SHOWN ON THE CEILING INSULATION ON PAGE 3 OF
 4 DOESN'T MATCH PLANS. SEE WALL SECTION 8-8 ON SHEET
 A-9 AND REVISE AS REQUIRED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 H) CLEARLY IDENTIFY WHERE ARE THE INSULATED DOORS
 SPECIFIED ON PAGE 3 OF 4?. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 I) WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH
 PLANS. REVISE AS REQUIRED.SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 5- SPECIFY THE ROOF PITCH FOR EXISTING PORCH LOCATED
 BETWEEN THE GARAGE AND MAIN HOUSE TO VERIFY COMPLIANCE
 WITH THE PROPOSED SHINGLES. ROOF SLOPE MAY BE TOO LOW.
 REPEAT COMMENT. THE ROOF SLOPE WAS NOT SPECIFIED.
 ARCHITECT'S RESPONSE LETTER AND DRAWING A-4 SPECIFIES
 "EXISTING ROOF TO BE REPAIRED AS NEEDED". THIS
 STATEMENT IS TOO GENERAL. WHAT KIND OF REPAIRS ARE
 REQUIRED. REPLACEMENT OF ROOFING?. PROPOSED SHINGLES
 DON'T MATCH EXISTING. IF MORE THAN 25% OF THE SHINGLES
 OF THIS ROOF AREA NEED TO BE REPLACED, THEN ENTIRE ROOF
 SECTION NEEDS TO BE REPLACED. PROPOSED ROOF PRODUCT
 APPROVAL MAY NO BE ALLOWED TO BE INSTALLED BASED ON THE
 ROOF SLOPE. CLEARLY SPECIFY TYPE OF REPAIRS. TOTAL
 SQUARE FOOTAGE, ROOF PITCH, ETC. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOORS AS SHOWN ON PLANS. DESIGN PRESSURES
 SHOWN ON FLORIDA PRODUCT APPROVAL FL16546-R6 SUBMITTED
 DON'T MEET THE DESIGN PRESSURES SHOWN ON PLANS ON SHEET
 S-6.
  
 B) EXTERIOR OUTSWING DOORS AS SHOWN ON PLANS. FLORIDA
 PRODUCT APPROVAL FL10196-R3 SUBMITTED DOESN'T MEET THE
 CALCULATED DESIGN PRESSURE ON SHEET S-6 FOR THE DOUBLE
 DOORS.
  
 7- A) ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) THE FLOOD VENT FLORIDA
 PRODUCT APPROVAL FL17588 SUBMITTED. AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 8- PLANS TO INDICATE THE FINISH FLOOR ELEVATION OF THE
 MAIN HOUSE, GARAGE AND ALL THE EQUIPMENT SERVING THE
 BUILDING. SECTION 107.2.1 CITY AMENDMENTS.
  
 IMPORTANT:
 FLOOD ZONE A5: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON"T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-05 Cont ID  
Sent By jgomez Date 2016-08-04 Time 18:49 Rev Time 0.00
Received By jgomez Date 2016-08-04 Time 17:40 Sent To M
Notes
2016-08-04 19:00:04RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 ***NOTE: THERE IS A RED TAG FOR INTERIOR DEMOLITION
 WITHOUT PERMIT. PLEASE SPECIFY HOW MUCH MONEY WAS USED
 FOR DEMOLITION TO PROPERLY ASSESS THE FEES.
  
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THE NEW ENTRY DOOR NEEDS TO PROVIDE COMPLIANCE WITH
 THE EGRESS MINIMUM WIDTH REQUIREMENT OF SEC. R311.2
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED.
  
 3- SHEET A-2:
 A) MASTER BEDROOM EGRESS WINDOWS IDENTIFIED AS "E" ON
 PLANS ARE FOR CASEMENT FIXED WINDOWS. FIXED WINDOWS
 DON'T PROVIDE EGRESS. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
 NOTE: SAME APPLIES TO WINDOWS "D" ON BEDROOM #2. REVISE
 AS REQUIRED.
  
 B) SIZE OF WINDOWS SHOWN ON THE WINDOW AND DOORS
 SCHEDULES ARE NOT LEGIBLE. THE NUMBERS ARE TOO SMALL.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. NOTE:
 THIS APPLIES TO SHEET A-3 ALSO.
  
 4- A) SPECIFY ROOF VENTILATION FOR THE ADDITIONS (OR
 SPECIFY IF DESIGNING UNVENTTED ATTICS) SHOWING
 COMPLIANCE WITH SEC. R806 FBC-RESIDENTIAL. PROVIDE
 COMPLETE SPECIFICATIONS. NOTE: COORDINATE WITH THE
 ENERGY CALCULATIONS SUBMITTED. THEY SHOW VENTED ATTIC.
 ALSO, THEY SHOW BLOWN INSULATION. INFORMATION ON PLANS
 AND ENERGY CALCULATIONS NEED TO MATCH). NOTE: SHINGLES
 PRODUCT APPROVAL SUBMITTED REQUIRES VENTILATION.
  
 B) PROVIDE COPY OF ICC EVALUATION REPORT IF FOAM
 INSULATION IS SPECIFIED ON PLANS SEC. R316
 FBC-RESIDENTIAL. NOTE: DESIGNER OF RECORD TO APPROVE
 FOAM INSULATION REPORT PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 5- SPECIFY ATTIC ACCESS SIZE AND LOCATION FOR NEW
 FAMILY ROOM WING AREA AND NEW LIVING ROOM WING AREA.
 NOTE: ATTIC ACCESS NEEDS TO BE IN HALLWAY OR READILY
 ACCESSIBLE LOCATION (NOT INSIDE CLOSET. SEE SHEET A-7).
 SEC. R807 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE STAIRWAY, RISERS, TREADS, HANDRAILS
 AND GUARDRAILS SHOWING COMPLIANCE WITH TABLE R301.5,
 R311.7 AND SEC. R312.1 OF FBC-RESIDENTIAL. (HANDRAIL
 AND GUARDRAIL SHOP DRAWINGS APPROVED BY THE DESIGNER OF
 RECORD TO BE SUBMITTED LATER PRIOR TO CONSTRUCTION).
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF BRICK VENEER SHOWING COMPLIANCE WITH
 SEC. R703.7 FBC-RESIDENTIAL.
  
 8- STRUCTURAL DRAWINGS TO SPECIFY ALL DEAD AND LIVE
 LOADS FOR EACH FLOOR, ROOF AND THE ATTIC LIVE LOADS AS
 REQUIRED BY SEC. R301.1 AND TABLE R301.5
 FBC-RESIDENTIAL. NOTE: SEE FOOTNOTES "B" AND "G" ON
 TABLE R301.5.
  
 9- SHEET S-6:
 A) DESIGN PRESSURES FOR COMPONENTS AND CLADDING SHOWN
 ON FLOOR PLANS FOR EDGE AND INTERIOR WALLS DON'T MATCH
 DESIGN PRESSURES SHOWN ON THE ALLOWABLE WIND LOAD TABLE
 SHOWN ON THE SAME PAGE. REVISE AS REQUIRED. NOTE:
 ACCORDING TO FOOTNOTE ON FIGURE R301.2(7)
 FBC-RESIDENTIAL THE WALL EDGE "A" IS 4'-0" MIN. IN ALL
 CASES. TAKE THIS IN CONSIDERATION WHEN PROVIDING THE
 DESIGN PRESSURES FOR OPENINGS LOCATED IN THE END ZONES.
  
 B) PROVIDE THE DESIGN PRESSURES FOR THE OVERHEAD GARAGE
 DOORS TO VERIFY COMPLIANCE WITH PRODUCT APPROVAL
 SUBMITTED. SEC. R301 FBC-RESIDENTIAL.
  
 C) REVISE THE DESIGN PRESSURES SHOWN ON THE ALLOWABLE
 AND ULTIMATE WIND LOAD INFORMATION TABLES. THE DESIGN
 PRESSURES FOR PERIMETER AND CORNER AREAS ARE TOO LOW
 BASED ON THE BUILDING HEIGHT AND EXPOSURE SHOWN ON
 PLANS. ALSO, CLARIFY WHY THE DESIGN PRESSURES FOR THE
 PERIMETER AND CORNER AREAS ARE EQUAL. DESIGN PRESSURES
 FOR PERIMETER AND CORNER AREAS ARE NOT EQUAL FOR THE
 TYPE OF ROOF SHOWN ON PLANS. REVISE AS REQUIRED. SEC.
 R301. 2.1 FBC-RESIDENTIAL.
  
 10- SEC. R803.2.3.1 REQUIRES 8D RING-SHANK NAILS MIN.
 STRUCTURAL PLANS, SPECIFICATIONS AND DETAILS SPECIFY
 ROOF SHEATHING ATTACHMENT WITH 10D NAILS. PROVIDE
 CALCULATIONS SHOWING THAT 10D NAILS PROVIDE EQUAL OR
 MORE UPLIFT RESISTANCE OR REVISE ALL DETAILS AND
 SPECIFICATIONS SHOWING THE 8D RING SHANK NAILS. SEC.
 107.2.1.3 CITY AMENDMENTS. NOTE: SHINGLES NOA
 12-0514.12 SUBMITTED REQUIRES 8D RING-SHANK NAILS ALSO.
 SEE DECK ATTACHMENT.
  
 11- PROVIDE SOIL TEST REPORT (2 COPIES WITH ORIGINAL
 SEAL/SIGNATURE) AS REQUIRED BY CHAPTER 471 F.S.
  
 12- ACCORDING TO COPY OF ELEVATION CERTIFICATE
 SUBMITTED, THE EQUIPMENT IS LOCATED BELOW THE REQUIRED
 7'-6' FINISH ELEVATION. ALL EQUIPMENT NEEDS TO BE
 RAISED AT 7'-6" MIN. SEC. 94-546 CITY CODE.
  
 13- ENERGY CALCULATIONS SUBMITTED:
 A) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION
 CHECKLIST ON TABLE 402.4.1.1 SUBMITTED. SEC. R405.4.3
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) COORDINATE ATTIC INSULATION TYPE AND VENTING WITH
 FLOOR PLANS SUBMITTED (PLANS DON'T SHOW BLOWN
 INSULATION). ALSO, COORDINATE ROOF MATERIAL WITH PLANS
 AND PRODUCT APPROVAL SUBMITTED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME, PERMIT OFFICE, JURISDICTION
 NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 E) REVISE THE ROOF MATERIAL SHOWN ON PAGE 2 OF 4 TO
 MATCH PLANS AND PRODUCT APPROVAL SUBMITTED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 14- SPECIFY THE ROOF PITCH FOR EXISTING PORCH LOCATED
 BETWEEN THE GARAGE AND MAIN HOUSE TO VERIFY COMPLIANCE
 WITH THE PROPOSED SHINGLES. ROOF PITCH SEEMS TO BE TOO
 LOW. AND SHINGLES MAY NO BE ALLOWED. LOW SLOPE ROOFS
 REQUIRE A DIFFERENT PRODUCT APPROVAL. SEC. R905.1
 FBC-RESIDENTIAL.
  
 15- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOORS. DESIGN PRESSURES ON FLORIDA PRODUCT
 APPROVAL FL15279-R4 SUBMITTED ARE TOO LOW. NEED DOORS
 THAT MEET THE CALCULATED DESIGN PRESSURES. COORDINATE
 WITH THE DESIGN PRESSURES REQUIRED ON ITEM #9(B) ABOVE.
  
 B) SHINGLES THAT MEET THE REVISED DESIGN PRESSURES
 CALCULATED ON SHEET. S-6. NOTE: THE DESIGN PRESSURES
 SHOWN ON NOA 12-0514.12 SUBMITTED MAY NOT RESIST THE
 REVISED DESIGN PRESSURES. VERIFY AND RE-SUBMIT.
  
 C) LOW SLOPE ROOF IF REQUIRED BY ITEM #14 ABOVE.
 IDENTIFY SELECTED ASSEMBLY. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE CALCULATED DESIGN PRESSURES.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS: (1) THE
 APPLICATION STATUS FOR FL14133-R5 SAYS "APPLIED FOR".
 NEED PRODUCT APPROVAL THAT IS ALREADY APPROVED. OR
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 (2)PROVIDE DRAWINGS THAT CORRESPOND TO FLORIDA PRODUCT
 APPROVAL FL14133-R5 SUBMITTED. AND, (3)CLEARLY SPECIFY
 SIZE AND LOCATION OF WINDOW MULLIONS TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 E) FIXED WINDOWS AS SHOWN ON PLANS : (1) THE
 APPLICATION STATUS FOR FL10188-R7 SAYS "APPLIED FOR".
 NEED PRODUCT APPROVAL THAT IS ALREADY APPROVED. OR
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL. (2)
 MAKE SURE SELECTED WINDOWS MEET THE REVISED DESIGN
 PRESSURES FOR ALL WINDOWS. (3)PROVIDE DRAWINGS THAT
 CORRESPOND TO FLORIDA PRODUCT APPROVAL FL10188-R7
 SUBMITTED.
  
 F) CASEMENT WINDOWS AS SHOWN ON PLANS : (1) THE
 APPLICATION STATUS FOR FL10197-R4 SAYS "APPLIED FOR".
 NEED PRODUCT APPROVAL THAT IS ALREADY APPROVED. OR
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL. (2)
 MAKE SURE SELECTED WINDOWS MEET THE REVISED DESIGN
 PRESSURES FOR ALL WINDOWS. (3)PROVIDE DRAWINGS THAT
 CORRESPOND TO FLORIDA PRODUCT APPROVAL FL10197-R-4
 SUBMITTED.
  
 G) EXTERIOR OUTSWING DOORS AS SHOWN ON PLANS. (1)
 PROVIDE DRAWINGS THAT CORRESPOND TO FLORIDA PRODUCT
 APPROVAL FL10196-R3 SUBMITTED. 2) MAKE SURE SELECTED
 DOORS MEET THE REVISED DESIGN PRESSURES FOR ALL DOORS
 SHOWN ON PLANS.
  
 H) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, SECTIONS AND DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL NUMBER AND PAGE SHOWING THE SPECIFIED
 CONNECTOR. OR LIST THE FLORIDA PRODUCT APPROVAL NUMBER
 NEXT TO EACH SPECIFIED CONNECTOR.
  
 16- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 IMPORTANT:
 FLOOD ZONE A5: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON"T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-19 Cont ID  
Sent By vperez Date 2016-10-19 Time 14:55 Rev Time 0.00
Received By vperez Date 2016-10-19 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-14 Cont ID  
Sent By vperez Date 2016-07-14 Time 10:08 Rev Time 0.00
Received By vperez Date 2016-07-14 Time 07:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-11-08 Cont ID  
Sent By gjohnson Date 2016-11-08 Time 13:12 Rev Time 0.00
Received By gjohnson Date 2016-11-08 Time 13:12 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-07-25 Cont ID  
Sent By tklarge Date 2016-07-25 Time 14:00 Rev Time 0.00
Received By tklarge Date 2016-07-25 Time 13:55 Sent To  
Notes
2016-07-25 14:00:171) SHT. P-2 SHOWS THE RANGE AS 122,000 BTU'S BUT SHT.
 P-4 SHOWS THE RANGE AS 65,000 BTU'S. CLARIFY.
 2) SHT.P-4 SHOWS THE TOTAL BTU LOAD AS 321,000 BUT ONLY
 264,000 BTU'S ARE SHOWN ON THE RISER. CLARIFY.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 EQUIPMENT. ALL GAS EQUIPMENT SHALL BE LISTED AND
 LABELED PER 2014 FBCR SEC.G2404.3.
 4) GAS SHALL BE SUBMITTED AS A SEPARATE PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-02-07 Cont ID  
Sent By cpuell Date 2017-02-07 Time 11:01 Rev Time 0.00
Received By cpuell Date 2017-01-31 Time 16:05 Sent To  
Notes
2017-01-31 16:05:10IMPACT FEES ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-05 Cont ID  
Sent By jgomez Date 2017-01-05 Time 14:59 Rev Time 0.00
Received By jgomez Date 2016-12-06 Time 08:55 Sent To  
Notes
2016-12-07 08:58:08R28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-07 Cont ID  
Sent By lmarchan Date 2016-12-07 Time 08:55 Rev Time 0.00
Received By lmarchan Date 2016-10-17 Time 16:17 Sent To  
Notes
2016-10-17 16:18:49R28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-09 Cont ID  
Sent By hmoser Date 2016-08-09 Time 15:40 Rev Time 0.00
Received By hmoser Date 2016-06-21 Time 09:34 Sent To  
Notes
2016-06-23 13:23:27R28
2016-06-22 09:34:56LIBRARY

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2017-02-01 Cont ID  
Sent By jgomez Date 2017-02-01 Time 09:33 Rev Time 0.00
Received By jgomez Date 2017-02-01 Time 09:28 Sent To  
Notes
2017-02-01 09:34:31$21.91 PAID. MU-2017-2275.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-01-03 Cont ID  
Sent By jgomez Date 2017-01-03 Time 12:57 Rev Time 0.00
Received By jgomez Date 2017-01-03 Time 12:57 Sent To  
Notes
2017-01-03 12:57:241- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEE ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-10-27 Cont ID  
Sent By jgomez Date 2016-10-27 Time 15:06 Rev Time 0.00
Received By jgomez Date 2016-10-27 Time 15:06 Sent To  
Notes
2016-10-27 15:06:531- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEE ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-08-05 Cont ID  
Sent By jgomez Date 2016-08-05 Time 07:34 Rev Time 0.00
Received By jgomez Date 2016-08-05 Time 07:03 Sent To  
Notes
2016-08-05 07:34:471- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-01-05 Cont ID  
Sent By jgomez Date 2017-01-05 Time 14:58 Rev Time 0.00
Received By hmoser Date 2017-01-05 Time 11:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-11-08 Cont ID  
Sent By jvalido Date 2016-11-08 Time 16:21 Rev Time 0.00
Received By jvalido Date 2016-11-08 Time 14:59 Sent To  
Notes
2016-11-08 16:04:34CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 REFER TO SECTION M1602.4 BALANCE RETURN AIR EXCEPTION
 #3 MASTER SUITE. 2014 FBC RESIDENTIAL CODE.
  
 (1) MASTER BEDROOM HAS 525 CFM OF SUPPLY AIR. RETURN
 AIR FROM MASTER BEDROOM ON PLANS IS NOT TO CODE (AS PER
 M1602.4 EXCEPTION #3).
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By hmoser Date 2016-08-09 Time 15:39 Rev Time 0.00
Received By hmoser Date 2016-08-09 Time 11:13 Sent To  
Notes
2016-08-09 15:39:44PLAN DENIED
 1) SHOW ACCESS TO NEW A C # 4 AIR HANDLER REFER TO
 SECTION 403.2.4 AIR HANDLING UNITS 2014 FLORIDA ENERGY
 CODE.
 2) PROVIDE THE MANUFACTURER'S INSTALLATION INSTRUCTIONS
 ON THE KITCHEN HOOD.REFER TO SECTION M1503.4 MAKE
 UP AIR REQUIRED 2014 RESIDENTIAL CODE.
 3) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 EXCEPTION # 3 MASTER SUITE. 2014 FBC RESIDENTIAL
 CODE.
 4) PROVIDE DUCT SIZE ON ALL DUCT SOME NOT LEGIBLE.
 SECTION 107 FBC
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-85-6676

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2020-08-15 Cont ID  
Sent By pvalenti Date 2020-08-15 Time 14:06 Rev Time 0.00
Received By pvalenti Date 2020-08-15 Time 14:06 Sent To  
Notes
2020-08-15 14:08:27PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 NFIP APPROVED WITH ELEVATION CERTIFICATE COMPLETED. SEE
 ELEVATION CERTIFICATE FOR RESIDENCE AND DETACHED
 GARAGE, PERMIT # 19080006.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-12-09 Cont ID  
Sent By jgomez Date 2019-12-09 Time 10:23 Rev Time 0.00
Received By jgomez Date 2019-12-09 Time 09:09 Sent To  
Notes
2019-12-09 10:23:531- PROPERTY IS LOCATED IN SPECIAL FLOOD ZONE AREA.
 ELEVATION CERTIFICATES ARE REQUIRED BASED ON
 CONSTRUCTION DRAWINGS, BUILDING UNDER CONSTRUCTION AND
 FINISHED CONSTRUCTION. PROVIDE THE REQUIRED ELEVATION
 CERTIFICATES.

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-08 Cont ID  
Sent By gjohnson Date 2016-11-08 Time 13:08 Rev Time 0.00
Received By gjohnson Date 2016-11-08 Time 13:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-25 Cont ID  
Sent By tklarge Date 2016-07-25 Time 13:55 Rev Time 0.00
Received By tklarge Date 2016-07-25 Time 10:55 Sent To  
Notes
2016-07-25 13:19:401) THE WATER SUPPLY VALVES FOR THE GROUND FLOOR
 WASHER/DRYER UNIT SHALL BE ACCESSIBLE PER 2014 FBCR
 SEC. P2903.9.3.
 2) THE WASHING MACHINE & SINK ON THE 2ND FLOOR ARE NOT
 SHOWN ON THE SANITARY RISER. IT APPEARS THEY MAY BE
 LABELED AS LAVATORIES. AS DRAWN, THEY RISER IS NOT CODE
 COMPLIANT FOR THESE TWO FIXTURES.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2017-01-03 Cont ID  
Sent By jgomez Date 2017-01-03 Time 12:49 Rev Time 0.00
Received By jgomez Date 2017-01-03 Time 12:45 Sent To  
Notes
2017-01-03 11:48:12APPROVED ROOFING PRODUCT APPROVAL: ENVIROSHAKE NOA
 12-0706.06.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-11-01 Cont ID  
Sent By jgomez Date 2016-11-01 Time 12:39 Rev Time 0.00
Received By jgomez Date 2016-11-01 Time 12:26 Sent To  
Notes
2016-11-01 12:42:321- SPECIFY THE ROOF PITCH FOR EXISTING PORCH LOCATED
 BETWEEN THE GARAGE AND MAIN HOUSE TO VERIFY COMPLIANCE
 WITH THE PROPOSED SHINGLES. ROOF SLOPE MAY BE TOO LOW.
 REPEAT COMMENT. THE ROOF SLOPE WAS NOT SPECIFIED.
 ARCHITECT'S RESPONSE LETTER AND DRAWING A-4 SPECIFIES
 "EXISTING ROOF TO BE REPAIRED AS NEEDED". THIS
 STATEMENT IS TOO GENERAL. WHAT KIND OF REPAIRS ARE
 REQUIRED. REPLACEMENT OF ROOFING?. PROPOSED SHINGLES
 DON'T MATCH EXISTING. IF MORE THAN 25% OF THE SHINGLES
 OF THIS ROOF AREA NEED TO BE REPLACED, THEN ENTIRE ROOF
 SECTION NEEDS TO BE REPLACED. PROPOSED ROOF PRODUCT
 APPROVAL MAY NO BE ALLOWED TO BE INSTALLED BASED ON THE
 ROOF SLOPE. CLEARLY SPECIFY TYPE OF REPAIRS. TOTAL
 SQUARE FOOTAGE, ROOF PITCH, ETC. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  
 APPROVED ROOFING PRODUCT APPROVAL: ENVIROSHAKE NOA
 12-0706.06.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-08-08 Cont ID  
Sent By jgomez Date 2016-08-08 Time 14:34 Rev Time 0.00
Received By jgomez Date 2016-08-08 Time 14:33 Sent To  
Notes
2016-08-08 14:41:561- SPECIFY THE ROOF PITCH FOR EXISTING PORCH LOCATED
 BETWEEN THE GARAGE AND MAIN HOUSE TO VERIFY COMPLIANCE
 WITH THE PROPOSED SHINGLES. ROOF PITCH SEEMS TO BE TOO
 LOW. AND SHINGLES MAY NO BE INSTALLED. LOW SLOPE ROOFS
 REQUIRE A DIFFERENT PRODUCT APPROVAL. SEC. R905.1
 FBC-RESIDENTIAL.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SHINGLES THAT MEET THE REVISED DESIGN PRESSURES
 CALCULATED ON SHEET. S-6. NOTE: THE DESIGN PRESSURES
 SHOWN ON NOA 12-0514.12 SUBMITTED MAY NOT RESIST THE
 REVISED DESIGN PRESSURES. VERIFY AND RE-SUBMIT.
  
 B) LOW SLOPE ROOF IF REQUIRED BY ITEM #14 ABOVE.
 IDENTIFY SELECTED ASSEMBLY. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE CALCULATED DESIGN PRESSURES.
  

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2017-02-06 Time   Rev Time 0.00
Received By   Date 2017-02-06 Time   Sent To  
Notes
2017-02-06 10:41:29*******ZONING PROVISO*******
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 PLEASE DO NOT APPROVE FINAL WITHOUT CONFIRMING THAT
 LANDSCAPE PERMIT HAS BEEN ISSUED AND INSPECTION OF
 LANDSCAPE INSTALLATION HAS BEEN APPROVED.
  
 PLEASE CONTACT ALANA WOOTEN WITH ANY QUESTIONS YOU MAY
 HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]
  
  
2017-02-01 13:37:38ROUTED TO ALANA WOOTEN

Review Stop Z ZONING
Rev No 3 Status F Date 2016-12-15 Cont ID  
Sent By awooten Date 2016-12-15 Time 15:49 Rev Time 0.00
Received By awooten Date 2016-12-15 Time   Sent To  
Notes
2016-12-15 15:49:34THE TREE ALTERATION PERMIT APPLICATION IS A SEPARATE
 PERMIT THAT IS REQUIRED TO BE SUBMITTED DIRECTLY TO THE
 CITY'S LANDSCAPE ENGINEER, RAY CARANCI (561-822-1462),
 WITH A $15 PAYMENT. PLEASE COME TO THE PLANNING
 DEPARTMENT ON THE 2ND FLOOR OF CITY HALL TO SUBMIT.
 ONCE THE TREE ALTERATION PERMIT APPLICATION HAS BEEN
 SUBMITTED, THE CONDITIONAL APPROVAL CAN BE ISSUED TO
 THIS PERMIT. THIS CONDITIONAL APPROVAL IS CONTINGENT ON
 THE APPLICANT SUBMITTING A LANDSCAPE PLAN TO BE
 APPROVED AND INSPECTION PASSED BEFORE A CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED FOR THE HOME. PLEASE CONTACT ME
 WITH ANY QUESTIONS YOU MAY HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2016-11-07 Cont ID  
Sent By awooten Date 2016-11-07 Time 13:46 Rev Time 0.00
Received By awooten Date 2016-11-03 Time   Sent To  
Notes
2016-11-07 13:45:57PLANNING AND ZONING: **** FAILED ****
  
 PLANS INDICATE THAT TREES WILL BE REMOVED. A TREE
 ALTERATION PERMIT IS REQUIRED. PLEASE CONTACT THE
 PLANNING DIVISION FOR TREE ALTERATION PERMIT
 APPLICATION.
  
 THE VALUE OF THE CONSTRUCTION ($650,000.00) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($535,509.00) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.FOR ADDITIONAL
 INFORMATION, THE ZONING AND LAND DEVELOPMENT
 REGULATIONS MAY BE VIEWED ONLINE AT WWW.MUNICODE.COM OR
 VISIT THE CITY OF WEST PALM BEACH PLANNING DEPARTMENT
 WEBSITE AT WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 ALANA WOOTEN, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1449
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-30 Cont ID  
Sent By awooten Date 2016-06-30 Time 11:33 Rev Time 0.00
Received By awooten Date 2016-06-30 Time 11:33 Sent To  
Notes
2016-06-30 11:36:28PLANNING AND ZONING: **** FAILED ****
  
 PLANS INDICATE THAT TREES WILL BE REMOVED. A TREE
 ALTERATION PERMIT IS REQUIRED. PLEASE CONTACT THE
 PLANNING DIVISION FOR TREE ALTERATION PERMIT
 APPLICATION.
  
 THE VALUE OF THE CONSTRUCTION ($650,000.00) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($535,509.00) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.FOR ADDITIONAL
 INFORMATION, THE ZONING AND LAND DEVELOPMENT
 REGULATIONS MAY BE VIEWED ONLINE AT WWW.MUNICODE.COM OR
 VISIT THE CITY OF WEST PALM BEACH PLANNING DEPARTMENT
 WEBSITE AT WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  