Plan Review Details - Permit 16061164
Plan Review Stops For Permit 16061164
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-23 Cont ID  
Sent By mvaldes Date 2016-06-23 Time 18:33 Rev Time 0.00
Received By mvaldes Date 2016-06-23 Time 18:29 Sent To M
Notes
2016-06-23 18:34:35ROUTED TO JORGE VALIDO

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-06-21 Cont ID  
Sent By pleduc Date 2016-06-21 Time   Rev Time 0.00
Received By pleduc Date 2016-06-21 Time 13:31 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-28 Cont ID  
Sent By cpuell Date 2016-06-28 Time 10:31 Rev Time 0.00
Received By cpuell Date 2016-06-21 Time 10:15 Sent To  
Notes
2016-06-21 10:15:57ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-08 Cont ID  
Sent By hmoser Date 2016-07-08 Time 09:02 Rev Time 0.00
Received By hmoser Date 2016-07-08 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By jvalido Date 2016-06-27 Time 17:02 Rev Time 0.00
Received By jvalido Date 2016-06-27 Time 16:51 Sent To  
Notes
2016-06-27 17:02:04FLORIDA BUILDING CODE 5TH EDITION (2014) MECHANICAL
  
 606.2.1 RETURN AIR SYSTEMS.
 SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR
 SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM
 (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF
 ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR
 CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND
 APPLIANCES.
  
 606.2.2 COMMON SUPPLY AND RETURN AIR SYSTEMS.
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S), THE RETURN
 AIR SYSTEM SHALL BE PROVIDED WITH SMOKE DETECTORS IN
 ACCORDANCE WITH SECTION 606.2.1.
  
 606.2.3 RETURN AIR RISERS.
 WHERE RETURN AIR RISERS SERVE TWO OR MORE STORIES AND
 SERVE ANY PORTION OF A RETURN AIR SYSTEM HAVING A
 DESIGN CAPACITY GREATER THAN 15,000 CFM (7.1 M3/S),
 SMOKE DETECTORS SHALL BE INSTALLED AT EACH STORY. SUCH
 SMOKE DETECTORS SHALL BE LOCATED UPSTREAM OF THE
 CONNECTION BETWEEN THE RETURN AIR RISER AND ANY AIR
 DUCTS OR PLENUMS.
  
 PROVIDE EQUIPMENT SCHEDULE FOR ALL (4) RTU.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER