Notes |
2016-07-11 11:05:52 | REVISED SHEETS A1.2, A1.3, S1 AND S2 HAVE BEEN | | APPROVED. | | | | REVISED SHEET A4.0 HAS BEEN DENIED FOR THE FOLLOWING | | REASONS. | | (1) THE TYPICAL BALCONY DETAIL IS MISSING THE | | LENGTH/EMBED DEPTH OF THE 5/8" DIAMETER LAG BOLT AND | | THE 5/8" DIAMETER CONCRETE BOLT. | | (2) ON THE BALCONY DETAIL, THERE IS A NOTE FOR A 5/8" | | STRUCTURAL STEEL L-SHAPED WALL ANGLE BRACKET FOR (2) 2 | | X 8 WD LEDGER SUPPORT WITH FOUR 5/8" DIA. S.S. THRU | | BOLTS WITH 1-1/2" S.S. WASHERS. THE ARROWS ARE POINTING | | TO THE INSULATION AND THE L-SHAPED ANGLE BRACKET AND | | THRU BOLTS ARE NOT SHOWN. PROVIDE DETAILS OF THE L | | BRACKET WITH THE THICKNESS AND DIMENSIONS. FBC 301.1 | | (3) THERE IS A SMALL PORTION OF TEXT ON A4.0 BETWEEN | | DETAIL 2 AND DETAIL 4. IF NOT REQUIRED PLEASE REMOVE. | | FBC 107.2.1 |
|
|