Plan Review Details - Permit 16061090
Plan Review Stops For Permit 16061090
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-03 Cont ID  
Sent By rmcdouga Date 2016-08-03 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2016-08-03 Time 16:39 Sent To M
Notes
2016-08-03 18:21:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) UNDER THE EXISTING BUILDING CODE YOU ARE REQUIRED TO
 SPECIFY THE LEVEL OF ALTERATION ON THE PLANS.
  
 2) SPECIFY THE NUMBER OF OCCUPANTS, THE USE AND TYPE OF
 OCCUPANCY FOR THIS PROJECT. THIS PROPERTY IS ZONED
 SINGLE FAMILY AND IT APPEARS THAT YOU INTEND TO CHANGE
 THE OCCUPANCY TYPE FROM R-3 SINGLE FAMILY TO AN R-2 OR
 R-4. SEE FBC 310.
 2014 EXIST. BUILD. CODE 1001.3 CHANGE OF OCCUPANCY
 CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP. PLEASE DECLARE THE END USAGE OF THE STRUCTURE,
 THE OCCUPANT LOAD. AN R-4 CLASSIFICATION SHALL INCLUDE
 BUILDINGS, STRUCTURES OR PORTIONS THEREOF FOR MORE THAN
 FIVE BUT NOT MORE THAN 16 PERSONS, EXCLUDING STAFF, WHO
 RESIDE ON A 24-HOUR BASIS IN A SUPERVISED RESIDENTIAL
 ENVIRONMENT AND RECEIVE CUSTODIAL CARE. THE PERSONS
 RECEIVING CARE ARE CAPABLE OF SELF-PRESERVATION. PLEASE
 NOTE IF THE RECIPIENTS RECEIVING CUSTODIAL CARE ARE NO
 LONGER CAPABLE OF SELF- PRESERVATION THEN THE OCCUPANCY
 CHANGES TO AN I-2 OCCUPANCY. AN R-2 CLASSIFICATION IS
 RESIDENTIAL OCCUPANCIES CONTAINING SLEEPING UNITS OR
 MORE THAN TWO DWELLING UNITS WHERE THE OCCUPANTS ARE
 PRIMARILY PERMANENT IN NATURE, INCLUDING:
 APARTMENT HOUSES, BOARDING HOUSES (NONTRANSIENT) WITH
 MORE THAN 16 OCCUPANTS AND CONGREGATE LIVING FACILITIES
 (NONTRANSIENT) WITH MORE THAN 16 OCCUPANTS.
 NONTRANSIENT MEANS THE OCCUPANTS ARE THERE FOR MORE
 THAN 30 DAYS.
  
 3) SPECIFY THE TYPE OF CONSTRUCTION ON THE PLANS. FBC
 602
  
 4) SLEEPING ROOM WINDOWS DO NOT COMPLY WITH EGRESS.
 R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND
 RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE
 SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE OPENINGS
 SHALL BE REQUIRED IN EACH SLEEPING ROOM. WHERE
 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY
 SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES
 (1118 MM) MEASURED FROMTHE FINISHED FLOOR TO THE BOTTOM
 OF THE CLEAR OPENING. WHERE A DOOR OPENING HAVING A
 THRESHOLD BELOW THE ADJACENT GROUND ELEVATION SERVES AS
 AN EMERGENCY ESCAPE AND RESCUE OPENING AND IS PROVIDED
 WITH A BULKHEAD ENCLOSURE, THE BULKHEAD ENCLOSURE SHALL
 COMPLY WITH SECTION R310.3. THE NET CLEAR OPENING
 DIMENSIONS REQUIRED BY THIS SECTION SHALL BE OBTAINED
 BY THE NORMAL OPERATION OF THE EMERGENCY ESCAPE AND
 RESCUE OPENING FROM THE INSIDE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS WITH A FINISHED SILL HEIGHT BELOW THE
 ADJACENT GROUND ELEVATION SHALL BE PROVIDED WITH A
 WINDOW WELL IN ACCORDANCE WITH SECTION R310.2.
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL OPEN
 DIRECTLY INTO A PUBLIC WAY, OR TO A YARD OR COURT THAT
 OPENS TO A PUBLIC WAY.
 R310.1.1 MINIMUM OPENING AREA.
 ALL EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE A
 MINIMUM NET CLEAR OPENING OF 5.7 SQUARE FEET (0.530
 M2).
  
 EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2).
  
 R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
 (610 MM).
  
 R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES
 (508 MM).
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 WINDOWS AND STRUCTURAL MULLIONS.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW. BASED ON THE ZONING COMMENTS A CHANGE OF
 OCCUPANCY MAY NOT BE ALLOWED. SEE ZONING COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-13 Cont ID  
Sent By vperez Date 2016-07-13 Time 11:00 Rev Time 0.00
Received By vperez Date 2016-07-13 Time 10:59 Sent To  
Notes
2016-07-13 11:01:54INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE SEE ZONING COMMENTS REGARDING RESTRICTION. A
 COMPLETE REVIEW WILL NOT BE PERFORMED AT THIS TIME.
 2. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2016-06-21 Cont ID  
Sent By fmittner Date 2016-06-21 Time 15:17 Rev Time 0.00
Received By fmittner Date 2016-06-21 Time 15:17 Sent To  
Notes
2016-06-21 15:18:22WINDOWS UNDER SEPERATE PERMIT....NO PRODUCT APPROVALS
 HERE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-10 Cont ID  
Sent By cpuell Date 2016-08-10 Time 09:00 Rev Time 0.00
Received By cpuell Date 2016-06-17 Time 10:50 Sent To  
Notes
2016-06-20 10:50:59R18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By jvalido Date 2016-08-09 Time 17:36 Rev Time 0.00
Received By jvalido Date 2016-08-09 Time 17:17 Sent To  
Notes
2016-08-09 17:33:32CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 REVIEW ALL DUCT SIZES AND CFM QUANTITIES.
 CHECK BED ROOM #8.
 6" DUCT @ .1% FRICTION LOST CANNOT PROVIDE 254 CFM.
 CHECK BATHROOM ON 2ND FLOOR. 185 CFM IS TOO MUCH AIR
 PER CFM PER SQFT RATIO (0.817) GIVEN.
  
 CHECK ALL BEDROOMS.
 CFM PER SQFT 0.817 DOES NOT MEET THE PLANS SCALE SQFT
 OF THE BEDROOMS. PROVIDE PROPER SCALE OR MAKE
 CORRECTIONS TO CFM AND DUCT SIZES.
  
 FLORIDA ENERGY CODE FBC 2014
  
 PROVIDE AHRI FOR EQUIPMENT INSTALLED.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-23 Cont ID  
Sent By tklarge Date 2016-07-23 Time 12:52 Rev Time 0.00
Received By tklarge Date 2016-07-23 Time 12:46 Sent To  
Notes
2016-07-23 12:52:021) SCOPE OF WORK ON SHT. 1 STATES TO ADD BATHROOM ON
 2ND FLOOR BUT THE PLANS SHOW 2 PROPOSED BATHROOMS ON
 THE SECOND FLOOR. WHICH ONE IS BEING ADDED AND WHICH
 ONE IS BEING RENOVATED. CLARIFY.
 2) SUBMIT SANITARY RISERS FOR ALL THE CHANGES BEING
 MADE TO THE PLUMBING SYSTEM. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 3) SHOW THE FIXTURE CLEARANCES OF THE FIXTURES PER FPC
 SEC. 405.3.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By   Date 2016-07-11 Time   Rev Time 0.00
Received By kmartin Date 2016-07-11 Time 10:53 Sent To B
Notes
2016-07-11 10:56:56ROOMING-HOUSES, GROUP-HOMES NOT ALLOWED IN THIS
 DISTRICT. PROPERTY SIZE AND ZONING ALLOW UP TO THREE
 SEPARATE UNITS, WE SUGGEST SPEAKING WITH THE COMMUNITY
 REDEVELOPMENT AGENCY TO LEARN ABOUT INCENTIVE PROGRAMS
 TO REHABILITATE STRUCTURE.
  
 FOR ADDITIONAL DETAILS, PLEASE CONTACT KEVIN MARTIN,
 URBAN DESIGN PLANNER (561) 822-1426 [email protected]
  
 ROUTED TO R18