Plan Review Details - Permit 16061084
Plan Review Stops For Permit 16061084
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-10-11 Cont ID  
Sent By shill Date 2016-10-11 Time 10:46 Rev Time 0.00
Received By shill Date 2016-10-11 Time 10:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-08-08 Cont ID  
Sent By shill Date 2016-08-08 Time 11:30 Rev Time 0.00
Received By shill Date 2016-08-08 Time 11:25 Sent To  
Notes
2016-08-08 11:30:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A SIGNED AND SEALED LETTER FROM THE ENGINEER
 OF RECORD WHICH ACKNOWLEDGES THE CHANGE IN DESIGN
 (CABLE GROUPINGS ELIMINATED AT LEVELS 8, 9, 10) AND THE
 STATEMENT MADE REGARDING SUFFICIENT CAPACITY (REFER TO
 SHOP REVIEW BY CORDELL VAN NOSTRAND), FAC61G15.
  
 2. CONTRACTOR IS RESPONSIBLE FOR PROVIDING THREE
 COLLATED COMPLETE SETS. THE FIRST SUBMITTAL WAS FOR
 POST TENSION DELEGATED ENGINEERING, FLOORS 8-20, AND
 INCLUDED CALCULATIONS. THE SECOND SUBMITTAL INCLUDES
 REVISED DRAWINGS MARKED 8-20, BUT ALSO INCLUDES A
 LETTER WHICH STATES THAT THREE CABLE GROUPINGS
 (109-111) WERE MISSED ON FLOORS 8-10. THE PREVIOUS
 SUBMITTAL WAS MARKED "VOID" AND THE CURRENT SUBMITTAL
 TITLE BLOCK STATES THAT THIS IS FOR FLOORS 8-20, AND
 CALCS FOR 109-11 INCLUDED.
  
 IT APPEARS THAT THE POST TENSION ENGINEERING AND CALCS
 SHOULD BE REVISED; ONE DRAWING AND CALCS FOR FLOORS
 8-10, AND ANOTHER SEPARATE SUBMITTAL WHICH INCLUDES
 DRAWINGS AND CALCS FOR FLOORS 11-20. PLEASE REVISE
 ACCORDINGLY OR CONTACT ME TO DISCUSS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By shill Date 2016-07-11 Time 14:25 Rev Time 0.00
Received By shill Date 2016-07-11 Time 14:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-23 Cont ID  
Sent By shill Date 2016-06-23 Time 13:23 Rev Time 0.00
Received By shill Date 2016-06-23 Time 13:23 Sent To  
Notes
2016-06-23 13:25:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE ENGINEER'S REVIEW LETTER FOR THE DELEGATED
 ENGINEERING WAS ALTERED. PLEASE HAVE THE ENGINEER
 PREPARE A NEW LETTER AS THE CURRENT LETTER IS FOR THE
 8TH FLOOR BUT THE ENGINEERING PROVIDED IS FOR 8TH
 THROUGH 20TH FLOORS.
  
 THE REVIEW LETTER FOR DELEGATED ENGINEERING IS TO BE
 CONSISTENT WITH THE DELEGATED ENGINEERING TO SHOW
 COMPLIANCE WITH FAC61G15-31.004.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-10-11 Cont ID  
Sent By shill Date 2016-10-11 Time 10:47 Rev Time 0.00
Received By shill Date 2016-09-21 Time 09:56 Sent To  
Notes
2016-09-22 09:56:12RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-08 Cont ID  
Sent By shill Date 2016-08-08 Time 12:26 Rev Time 0.00
Received By shill Date 2016-08-04 Time 11:18 Sent To  
Notes
2016-08-05 11:18:17SUBMITTAL ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-11 Cont ID  
Sent By shill Date 2016-07-11 Time 14:25 Rev Time 0.00
Received By shill Date 2016-07-05 Time 08:40 Sent To  
Notes
2016-07-06 08:40:15RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-23 Cont ID  
Sent By shill Date 2016-06-23 Time 13:25 Rev Time 0.00
Received By shill Date 2016-06-20 Time 08:46 Sent To  
Notes
2016-06-21 08:46:48SUBMITTAL ROUTED TO SHILL