Plan Review Details - Permit 16060963
Plan Review Stops For Permit 16060963
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-08-17 Cont ID  
Sent By cthroop Date 2016-08-17 Time 14:40 Rev Time 0.00
Received By cthroop Date 2016-08-17 Time 14:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-08-02 Cont ID  
Sent By cthroop Date 2016-08-02 Time 12:14 Rev Time 0.00
Received By cthroop Date 2016-08-02 Time 12:14 Sent To  
Notes
2016-08-02 12:16:06BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 ACTION: DENIED
 DATE: 8/2/16
  
 1. COMMENTS FROM 2ND REVIEW HAVE NOT BEEN ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-25 Cont ID  
Sent By cthroop Date 2016-07-25 Time 09:22 Rev Time 0.00
Received By cthroop Date 2016-07-25 Time 09:22 Sent To P
Notes
2016-07-25 09:29:39BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 ACTION: DENIED
 DATE: 7/25/16
  
 1. EXISTING WINDOW TO BE REPLACED PER PROPOSED PLANS.
 2. PROVIDE FRAMING DETAIL W/DEMENSIONS.
 3. PROVIDE PRODUCT APPROVALS FOR NEW WINDOW.
 4. PROVIDE DESIGN WIND LOADS FOR OPENING.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW
 SUBMITTALS.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By cthroop Date 2016-06-27 Time 15:21 Rev Time 0.00
Received By cthroop Date 2016-06-27 Time 15:21 Sent To  
Notes
2016-06-27 15:25:43BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 DATE: 6/27/16
 ACTION: DENIED
  
 1. THE PLANS SUBMITTED, WHICH ARE REQUIRED TO BE SIGNED
 BY THE DESIGNER, EXCEEDS THE SCOPE OF WORK INDICATED ON
 THE APPLICATION.
 2. PROVIDE A SCOPE OF WORK INDICATING ALL WORK TO BE
 PERFORMED.
 3. PROVIDE FLOOR PLAN WITH DEMENSIONS.
 4. PLUMBING PERMIT MAY BE REQUIRED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-07-27 Cont ID  
Sent By mvaldes Date 2016-07-27 Time 16:28 Rev Time 0.00
Received By mvaldes Date 2016-07-27 Time 16:16 Sent To P
Notes
2016-07-27 16:57:36ROUTED TO GEORGE JOHNSON ( PLUMBING ).

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-20 Cont ID  
Sent By mvaldes Date 2016-07-20 Time 14:30 Rev Time 0.00
Received By mvaldes Date 2016-07-20 Time 13:35 Sent To B
Notes
2016-07-20 14:32:11REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 SAME COMMENTS AS PREVIOUSLY ASKED FOR : ( COPY & PASTE
 )
  
 - FBC 107.2.1 PLEASE CLEARLY IDENTIFY THE SCOPE OF
 WORK. THE APPLICATION SHOWS "KITCHEN REMODEL", HOWEVER
 WORK IS BEING DONE IN THE BATHROOMS AS WELL ? HAVE THE
 PLANS SIGNED AND DATED BY THE DESIGNER RESPONSIBLE FOR
 THE DRAWING.
  
 - IF THE KITCHEN AND BATHROOMS ARE BEING REMODELED AN
 ELECTRICAL SUB PERMIT WILL BE REQUIRED. THE PLANS SHALL
 INCLUDE FBC R SECTIONS E3901.4 KITCHEN COUNTERTOP SPACE
 REQUIREMENTS & E3901.6 BATHROOM RECEPTACLE OUTLETS.
  
 - SHOW LOCATIONS OF OUTLETS ON THE FLOOR PLAN INCLUDE
 GFCI PROTECTION FOR E3902.1 BATHROOMS, E3902.6
 KITCHENS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By mvaldes Date 2016-06-27 Time 09:46 Rev Time 0.00
Received By mvaldes Date 2016-06-27 Time 09:29 Sent To B
Notes
2016-06-27 09:45:46REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - FBC 107.2.1 PLEASE CLEARLY IDENTIFY THE SCOPE OF
 WORK. THE APPLICATION SHOWS "KITCHEN REMODEL", HOWEVER
 WORK IS BEING DONE IN THE BATHROOMS AS WELL ? HAVE THE
 PLANS SIGNED AND DATED BY THE DESIGNER RESPONSIBLE FOR
 THE DRAWING.
  
 - IF THE KITCHEN AND BATHROOMS ARE BEING REMODELED AN
 ELECTRICAL SUB PERMIT WILL BE REQUIRED. THE PLANS SHALL
 INCLUDE FBC R SECTIONS E3901.4 KITCHEN COUNTERTOP SPACE
 REQUIREMENTS & E3901.6 BATHROOM RECEPTACLE OUTLETS.
  
 - SHOW LOCATIONS OF OUTLETS ON THE FLOOR PLAN INCLUDE
 GFCI PROTECTION FOR E3902.1 BATHROOMS, E3902.6
 KITCHENS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-17 Cont ID  
Sent By cthroop Date 2016-08-17 Time 14:40 Rev Time 0.00
Received By cthroop Date 2016-08-17 Time 12:45 Sent To  
Notes
2016-08-17 12:45:31CTHROOP'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-02 Cont ID  
Sent By cthroop Date 2016-08-02 Time 12:13 Rev Time 0.00
Received By cthroop Date 2016-07-27 Time 14:39 Sent To  
Notes
2016-07-27 14:39:57RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-25 Cont ID  
Sent By gjohnson Date 2016-07-25 Time 14:27 Rev Time 0.00
Received By gjohnson Date 2016-07-25 Time 14:26 Sent To  
Notes
2016-07-19 09:29:36RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-27 Cont ID  
Sent By cthroop Date 2016-06-27 Time 15:21 Rev Time 0.00
Received By cthroop Date 2016-06-15 Time 14:34 Sent To  
Notes
2016-06-16 14:34:36BLDG MISC 1
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-08-01 Cont ID  
Sent By gjohnson Date 2016-08-01 Time 14:12 Rev Time 0.00
Received By gjohnson Date 2016-08-01 Time 14:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-25 Cont ID  
Sent By gjohnson Date 2016-07-25 Time 14:26 Rev Time 0.00
Received By gjohnson Date 2016-07-25 Time 14:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-24 Cont ID  
Sent By skennedy Date 2016-06-24 Time 16:40 Rev Time 0.00
Received By skennedy Date 2016-06-24 Time 16:40 Sent To E
Notes
2016-06-24 16:45:301ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 DENIED. I CANNOT DETERMINE THE SCOPE OF WORK FROM
 EITHER THE PLAN OR THE DESCRIPTION. PLEASE PROVIDE MORE
 DETAIL AND PLACE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN ON THE DRAWINGS.. CLARIFY IF
 YOU ARE DOING PLUMBING WORK BEYOND REPLACING FIXTURES
 AND TILE. ARE YOU INSTALLING OR REPLACING A SHOWER PAN?
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  