Plan Review Details - Permit 16060927
Plan Review Stops For Permit 16060927
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By vperez Date 2016-07-11 Time 14:14 Rev Time 0.00
Received By vperez Date 2016-07-11 Time 14:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-22 Cont ID  
Sent By vperez Date 2016-06-22 Time 07:56 Rev Time 0.00
Received By vperez Date 2016-06-22 Time 07:50 Sent To  
Notes
2016-06-22 07:56:45INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CORRELATE CIRCUIT DESIGNATION SHOWN ON PANEL
 SCHEDULE, AS CIRCUIT 14 IS ASSIGNED TO THE NEW RTU UNIT
 AND FLOOR PLAN SHOWS A SPECIAL OUTLET WITH CIRCUIT 14
 ALSO. FBC 107.3.5
 2. PLEASE ADDRESS MECHANICAL COMMENTS REGARDING EXHAUST
 FANS SPECS . FBC 107.3.5
 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-14 Cont ID  
Sent By ccole Date 2016-07-14 Time 09:09 Rev Time 0.00
Received By ccole Date 2016-07-11 Time 11:21 Sent To  
Notes
2016-07-11 11:21:31RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-22 Cont ID  
Sent By vperez Date 2016-06-22 Time 07:56 Rev Time 0.00
Received By vperez Date 2016-06-22 Time 07:56 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-14 Cont ID  
Sent By ccole Date 2016-07-14 Time 09:09 Rev Time 0.00
Received By ccole Date 2016-07-14 Time 09:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-21 Cont ID  
Sent By ccole Date 2016-06-21 Time 09:50 Rev Time 0.00
Received By ccole Date 2016-06-21 Time 09:50 Sent To  
Notes
2016-06-21 10:00:221ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060927
 6/20/17
  
 1) THE AIR SUPPLIED TO THE LAB SUPPIES ROOM HAS A
 RECIRCULATION LIMIT OF 10% PER TABLE 403.3 FBC-14
 FOOTNOTE G. IT APPEARS FROM THE DRAWING THAT AN AMOUNT
 EXCEEDING 10% WILL BE RETURNED AND RECIRCULATED. THE
 PLAN IS ALSO INDICATING THE REQUIRED EXHAUST FAN IN THE
 ROOM HOWEVER THERE ARE NO DETAILS FOR THE FAN, OR
 EXHAUST VENTIATION CALCULATIONS FOR SIZING THE FAN.
  
 2) PLEASE INDICATE THE CONTROLS OPERATION SEQUENCE FOR
 EF-2. WILL THE FAN(S) BE LINKED TO THE AC SYSTEM?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-17 Cont ID  
Sent By vperez Date 2016-06-22 Time 07:56 Rev Time 0.00
Received By tklarge Date 2016-06-17 Time 05:46 Sent To  
Notes
***NONE***