2016-07-25 11:07:38 | SUBMITTED TABLE WAS NOT USED. DESIGN PRESSURES TAKEN | | FROM THE FBC 2014. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-06-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2016-06-16 |
Time |
18:29 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2016-06-16 |
Time |
17:55 |
Sent To |
|
|
Notes |
2016-06-16 18:49:58 | RESIDENTIAL (R3) ENTRY DOOR REPLACEMENT, BUILDING | | REVIEW COMMENTS. | | CODE: FBC 5TH EDITION(2014) | | | | 1- ACCORDING TO SEC. R301.2.1.4 OF FBC-RESIDENTIAL, 5TH | | EDITION (2014) THIS BUILDING IS LOCATED IN EXPOSURE "C" | | NOT EXPOSURE "B" AS SHOWN ON WIND-LOADS TABLE | | SUBMITTED. THE DOOR PRODUCT APPROVAL FL17184-R3 | | SUBMITTED DOESN'T MEET THE DESIGN PRESSURES SHOWN ON | | THE WIND- LOAD TABLE SUBMITTED. PROVIDE PRODUCT | | APPROVAL THAT MEETS THE CALCULATED DESIGN PRESSURES. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-06-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2016-06-16 |
Time |
17:56 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2016-06-14 |
Time |
10:18 |
Sent To |
|
|
Notes |
2016-06-15 10:19:05 | BLDG <5K |
|
|
|