Plan Review Details - Permit 16060878
Plan Review Stops For Permit 16060878
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-25 Cont ID  
Sent By jgomez Date 2016-07-25 Time 10:53 Rev Time 0.00
Received By jgomez Date 2016-07-25 Time 10:43 Sent To  
Notes
2016-07-25 11:07:38SUBMITTED TABLE WAS NOT USED. DESIGN PRESSURES TAKEN
 FROM THE FBC 2014.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By jgomez Date 2016-06-16 Time 18:29 Rev Time 0.00
Received By jgomez Date 2016-06-16 Time 17:55 Sent To  
Notes
2016-06-16 18:49:58RESIDENTIAL (R3) ENTRY DOOR REPLACEMENT, BUILDING
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION(2014)
  
 1- ACCORDING TO SEC. R301.2.1.4 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014) THIS BUILDING IS LOCATED IN EXPOSURE "C"
 NOT EXPOSURE "B" AS SHOWN ON WIND-LOADS TABLE
 SUBMITTED. THE DOOR PRODUCT APPROVAL FL17184-R3
 SUBMITTED DOESN'T MEET THE DESIGN PRESSURES SHOWN ON
 THE WIND- LOAD TABLE SUBMITTED. PROVIDE PRODUCT
 APPROVAL THAT MEETS THE CALCULATED DESIGN PRESSURES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-16 Cont ID  
Sent By jgomez Date 2016-06-16 Time 17:56 Rev Time 0.00
Received By jgomez Date 2016-06-14 Time 10:18 Sent To  
Notes
2016-06-15 10:19:05BLDG <5K