Plan Review Details - Permit 16060811
Plan Review Stops For Permit 16060811
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-20 Cont ID  
Sent By mvaldes Date 2016-07-20 Time 10:53 Rev Time 0.00
Received By mvaldes Date 2016-07-20 Time 10:09 Sent To M
Notes
2016-07-20 10:53:27ROUTED TO JORGE VALIDO

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 14:59 Rev Time 0.00
Received By mvaldes Date 2016-06-15 Time 14:59 Sent To M
Notes
2016-06-15 15:04:20REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PLEASE SITE THE NEC 2011 AS THHE APPLICABLE CODE IN
 THE ELECTRICAL NOTES.
  
 - CHILLER PUMPS SCHEDULE ON SHEET M4.1 SHOWS THE MOTOR
 VOLTAGE AS 460 V 3 PHASE AND THE CHILLER PANEL REFLECTS
 120/208 V 3 PHASE ? CORRECT AND MATCH.
  
 - ELECTRICAL SUB PERMIT REQUIRED
  
 - PROVIDE ARC-FLASH HAZRD WARNING LABEL IN ACCORDANCE
 WITH NEC 110.16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-21 Cont ID  
Sent By cpuell Date 2016-07-21 Time 10:37 Rev Time 0.00
Received By cpuell Date 2016-07-18 Time 09:52 Sent To  
Notes
2016-07-19 09:52:51RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-17 Cont ID  
Sent By cpuell Date 2016-06-17 Time 09:06 Rev Time 0.00
Received By cpuell Date 2016-06-13 Time 09:30 Sent To  
Notes
2016-06-14 09:30:36ROUTED TO ELECTRICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-21 Cont ID  
Sent By jvalido Date 2016-07-21 Time 09:29 Rev Time 0.00
Received By jvalido Date 2016-07-21 Time 09:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-06-16 Cont ID  
Sent By jvalido Date 2016-06-16 Time 18:35 Rev Time 0.00
Received By jvalido Date 2016-06-16 Time 17:49 Sent To  
Notes
***NONE***