Plan Review Details - Permit 16060799
Plan Review Stops For Permit 16060799
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-30 Cont ID  
Sent By jwitmer Date 2016-06-30 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2016-06-30 Time 07:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By jwitmer Date 2016-06-27 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2016-06-27 Time 07:01 Sent To  
Notes
2016-06-27 07:28:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060799
 ADD: 120 S. OLIVE (NORTH SIDE OF BUILDING)
 CONT: DWYER CONSTRUCTION & DEV.
 TEL: 561-870-6484
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 27/ 2016
 ACTION: DENIED
  
 1) ALPINE FIRESTORM/ WIND STORM RESISTANT INSULATED
 DOORSUNDER THE HEADING OF NOTES FIRE STORM / BUILDING
 NOTE # 6. REACTION FORCES PRINCIPLE ENGINEER IS
 REQUIRED TO CERIFY THAT THE BUILDING STRUCTURE CAN
 SUPPORT THE BELOW LISTED FORCES:
 MAXIMUM HORIZONTAL FORCES PX (LBS/FT) 2151
 MAXIMUM VERTICAL FORCES PY (LBS/ FT) 241
  
 2) ALPINE FIRESTORM/ WIND STORM RESISTANT INSULATED
 DOORSUNDER THE HEADING OF NOTES FIRE STORM / BUILDING
 NOTE # 5. WIND LOAD: DOORS ARE DESIGNED FOR A MAXIMUM
 PRESSURES OF 60 PSF.
  
 PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THESE
 OPENINGS. IT APPEARS ONE OPENING MAY BE IN OR PARTIALLY
 IN WALL ZONE 5?
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-06-14 Cont ID  
Sent By destabro Date 2016-06-14 Time 16:30 Rev Time 0.00
Received By destabro Date 2016-06-14 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-30 Cont ID  
Sent By jwitmer Date 2016-06-30 Time 08:55 Rev Time 0.00
Received By jwitmer Date 2016-06-29 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-27 Cont ID  
Sent By   Date 2016-06-27 Time   Rev Time 0.00
Received By lmarchan Date 2016-06-13 Time 15:56 Sent To  
Notes
2016-06-25 14:48:536/25 TO JW DESK
  
  
2016-06-13 15:56:49ROUTED TO HISTORIC VIA ZONING INBOX