2016-06-27 07:28:13 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16060799 |
| ADD: 120 S. OLIVE (NORTH SIDE OF BUILDING) |
| CONT: DWYER CONSTRUCTION & DEV. |
| TEL: 561-870-6484 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JUNE 27/ 2016 |
| ACTION: DENIED |
| |
| 1) ALPINE FIRESTORM/ WIND STORM RESISTANT INSULATED |
| DOORSUNDER THE HEADING OF NOTES FIRE STORM / BUILDING |
| NOTE # 6. REACTION FORCES PRINCIPLE ENGINEER IS |
| REQUIRED TO CERIFY THAT THE BUILDING STRUCTURE CAN |
| SUPPORT THE BELOW LISTED FORCES: |
| MAXIMUM HORIZONTAL FORCES PX (LBS/FT) 2151 |
| MAXIMUM VERTICAL FORCES PY (LBS/ FT) 241 |
| |
| 2) ALPINE FIRESTORM/ WIND STORM RESISTANT INSULATED |
| DOORSUNDER THE HEADING OF NOTES FIRE STORM / BUILDING |
| NOTE # 5. WIND LOAD: DOORS ARE DESIGNED FOR A MAXIMUM |
| PRESSURES OF 60 PSF. |
| |
| PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THESE |
| OPENINGS. IT APPEARS ONE OPENING MAY BE IN OR PARTIALLY |
| IN WALL ZONE 5? |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 2.2. RISK CATEGORY. |
| |
| 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |