Plan Review Details - Permit 16060591
Plan Review Stops For Permit 16060591
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-05 Cont ID  
Sent By jwitmer Date 2016-08-05 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2016-08-05 Time 06:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-17 Cont ID  
Sent By jwitmer Date 2016-06-17 Time 15:33 Rev Time 0.00
Received By jwitmer Date 2016-06-17 Time 14:29 Sent To  
Notes
2016-06-17 15:33:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060591
 ADD: 524 DATURA ST.
 CONT: MOSS & ASSOCIATES, LLC
 TEL: 561-228-6420
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 17/2016
 ACTION: DENIED
  
 1) SHEET A-1.01 SHOWS THE USE OF 2 FT. 8 IN. DOORS IN
 3'-0" OPENINGS. PERMIT # 14120850 INDICATED ALL DOOR
 OPENINGS (WRAPPED OPENINGS AT 36 INCHES FINISH
 DIMENSION) THE 2014 FBC-B SECTION 1008.1.1. SIZE OF
 DOORS, REQUIRES A MINIMUM CLEAR OPENING OF 32 INCHES.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 2) A-1.01 NOR THE ELECTRICAL SHEET SHOW HOW COMPLIANCE
 WITH 2014 FBC-B SECTION 1006.3(2) WILL BE ACHIEVED.
 1006.3 EMERGENCY POWER FOR ILLUMINATION.
 THE POWER SUPPLY FOR MEANS OF EGRESS ILLUMINATION SHALL
 NORMALLY BE PROVIDED BY THE PREMISES? ELECTRICAL
 SUPPLY.
 IN THE EVENT OF POWER SUPPLY FAILURE, AN EMERGENCY
 ELECTRICAL SYSTEM SHALL AUTOMATICALLY ILLUMINATE ALL OF
 THE FOLLOWING AREAS:
 1. AISLES AND UNENCLOSED EGRESS STAIRWAYS IN ROOMS AND
 SPACES THAT REQUIRE TWO OR MORE MEANS OF EGRESS.
  
 2. CORRIDORS, INTERIOR EXIT STAIRWAYS AND RAMPS AND
 EXIT PASSAGEWAYS IN BUILDINGS REQUIRED TO HAVE TWO OR
 MORE EXITS.
  
 3. EXTERIOR EGRESS COMPONENTS AT OTHER THAN THEIR
 LEVELS OF EXIT DISCHARGE UNTIL EXIT DISCHARGE IS
 ACCOMPLISHED FOR BUILDINGS REQUIRED TO HAVE TWO OR MORE
 EXITS.
  
 3) SHEET A-1.01 DOES NOT SHOW THE LOCATION WHERE FIRE
 EXTINGUISHERS ARE TO BE LOCATED. FBC-B 906.1(5) WHERE
 REQUIRED BY THE FIRE PREVENTION CODE.
  
 4) PLEASE NOTE THE COVER SHEET INDICATES THIS IS A
 FULLY FIRE SPRINKLERED BUILDING. PART OF THE SCOPE OF
 WORK UNDER THIS PERMIT IS THE INSTALATION OF ACOUSTICAL
 CEILINGS. THERE WAS NO FIRE SPRINKLER PLANS SUBMITTED
 FOR THE DROPPING OF THE FIRE SPRINKLERS TO THE NEW
 ACOUSTICAL CEILING HEIGHT. 2014 FBC-B 903.3.1.1 NFPA 13
 SPRINKLER SYSTEMS. WHERE THE PROVISIONS OF THIS CODE
 REQUIRE THAT A BUILDING OR PORTION THEREOF BE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH THIS SECTION, SPRINKLERS SHALL BE
 INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13 EXCEPT
 AS PROVIDED IN SECTION 903.3.1.1.1.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-19 Cont ID  
Sent By vperez Date 2016-07-19 Time 09:05 Rev Time 0.00
Received By vperez Date 2016-07-19 Time 09:05 Sent To  
Notes
2016-07-19 09:05:152ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 PROVISO COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS. A NOTE WILL SUFFICE.
 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC C405.7-
 AUTOMATIC MEANS OF LIGHTING CONTROLS
 3. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION.
 4. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By vperez Date 2016-06-27 Time 11:17 Rev Time 0.00
Received By vperez Date 2016-06-25 Time 15:06 Sent To  
Notes
2016-06-27 11:17:33INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. ADDRESS BUILDING, FIRE AND MECHANICAL COMMENTS FOR A
 COMPLETE ELECTRICAL APPROVAL.
 2. SHOW MEANS OF AUTOMATIC LIGHTING CONTROLS FOR ENTIRE
 AREA. FBC EC C405
 3. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERN.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-20 Cont ID  
Sent By pleduc Date 2016-07-20 Time   Rev Time 0.00
Received By pleduc Date 2016-07-20 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-21 Cont ID  
Sent By pleduc Date 2016-06-21 Time   Rev Time 0.00
Received By pleduc Date 2016-06-21 Time 10:27 Sent To  
Notes
2016-06-21 11:28:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 1.01 - NO DOOR SCHEDULE IS INDICATED. THREE
 (3) DOORS ARE NOT SPECIFICALLY INDICATED; THE WAREHOUSE
 STORAGE / CORRIFOR DOOR, THE OPEN OFFICE / CORRIDOR
 DOOR AND THE COMMON LOBBY / CORRIDOR DOOR.
  
 PLEASE PROVIDE APPLICABLE DOOR SCHEDULE INFORMATION,
 INCLUDING HARDWARE, AND DIMENSIONS.
  
  
 2) SHEET A.1.01 - THERE IS AN INDICATION OF AN EMEGENCY
 LIGHT IN OFFICE # 3. IT IS RECOMMENDED TO MOVE THAT
 EMEGENCY LIGHT INTO THE EXIT CORRIDOR.
  
  
 3) SHEET A 1.00 - THERE IS AN INDICATION THAT THE
 BUILDING IS FULLY SPRINKLERED.
  
 PLEASE PROVIDE A NOTE THAT ANY AND ALL WORK ON THE FIRE
 SPRINKLER SYSTEM SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 4) SHEET E 1.01 - THERE ARE NO INDICATIONS OF ANY FIRE
 ALARM DEVICES.
  
 PLEASE VERIFY AND PROVIDE A NOTE SAYING NO FIRE A,ARM
 DEVICES; HOWEVER, IF THEY ARE EXISTING PROVIDE
 LOCATIONS.
  
 ADDITIONALLY, PLEASE PROVIDE A NOTE THAT ANY AND ALL
 WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 5) SHEET M 1.01 - THERE IS NO INDICATION OF THE SIXE OF
 THE A/C SYSTEM.
  
 DUCT DETECTORS
 PER NFPA 90 A , CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2016-07-15 Time 14:03 Sent To  
Notes
2016-07-15 16:32:43B37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-27 Cont ID  
Sent By vperez Date 2016-06-27 Time 11:17 Rev Time 0.00
Received By vperez Date 2016-06-27 Time 11:17 Sent To  
Notes
2016-06-09 13:10:45B04

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-22 Cont ID  
Sent By ccole Date 2016-07-22 Time 10:54 Rev Time 0.00
Received By ccole Date 2016-07-22 Time 10:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By ccole Date 2016-06-15 Time 16:28 Rev Time 0.00
Received By ccole Date 2016-06-15 Time 16:28 Sent To  
Notes
2016-06-15 16:44:061ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16060591
 6/15/16
  
 1) SHEET M-1.01: PLEASE CLARIFY IF THE SEPARATION WALL
 IN DETAIL A IS FIRE-RATED- FIRE DAMPERS ARE REQUIRED
 FOR THE RETURN AIR PLENUM GRILL AND SUPPLY DUCT IF THE
 WALL IS RATED.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2016-06-15 Cont ID  
Sent By kmartin Date 2016-06-15 Time   Rev Time 0.00
Received By kmartin Date 2016-06-15 Time 14:20 Sent To  
Notes
***NONE***