Plan Review Details - Permit 16060583
Plan Review Stops For Permit 16060583
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-22 Cont ID  
Sent By mvaldes Date 2016-06-22 Time 10:24 Rev Time 0.00
Received By mvaldes Date 2016-06-22 Time 10:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-20 Cont ID  
Sent By mvaldes Date 2016-06-20 Time 18:03 Rev Time 0.00
Received By mvaldes Date 2016-06-20 Time 18:03 Sent To  
Notes
2016-06-20 18:21:27REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUIT
 OCPD.
  
 - NEC 300.5(D)(1)(2)(3)(4) PROTECTION FROM PHYSICAL
 DAMAGE OF SERVICE CONDUCTORS, WARNING RIBBON PLACED 12'
 ABOVE UNDERGROUND SERVICE CONDUCTORS.
  
 - IF EQUIPMENT IS SUBJECT TO VEHICULAR TRAFFIC PROPER
 GUARDING MIGHT BE REQUIRED. NEC 110.26 (E)(2) , NEC
 110.27
  
 - PROVIDE A MOUNTING DETAIL OF ELECTRICAL EQUIPMENT
 SHOWING HOW IT WILL BE INSTALLED MECHANICALLY.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-20 Cont ID  
Sent By mvaldes Date 2016-06-20 Time 18:21 Rev Time  
Received By mvaldes Date 2016-06-08 Time 10:11 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-20 Time 18:21 Rev Time 0.00
Received By tklarge Date 2016-06-15 Time 11:57 Sent To E
Notes
***NONE***