Plan Review Details - Permit 16060579
Plan Review Stops For Permit 16060579
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2016-06-16 Cont ID  
Sent By pleduc Date 2016-06-16 Time   Rev Time  
Received By pleduc Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-09-21 Cont ID  
Sent By pleduc Date 2016-09-21 Time   Rev Time 0.00
Received By pleduc Date 2016-09-21 Time 11:24 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-09-19 Cont ID  
Sent By pleduc Date 2016-09-19 Time   Rev Time 0.00
Received By pleduc Date 2016-09-19 Time 09:25 Sent To PC
Notes
2016-09-19 11:43:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 2ND REVIEW:
  
 1) THE ADDRESS ON THE APPLICATION, 501 EVERNIA ST, DOES
 NOT MATCH THE ADDRESS ON THE TITLE BLOCK, 520 DATURA
 ST,
  
 PLEASE CLARIFY/CORRECT.
  
 SECOND REVIEW : CORRECTED.
  
  
  
 2) DESIGN AREA 2 INDICATES AN AREA OF SPRINKLER
 OPERATION DENSITY OF 900. THE ENGINEER OF RECORD PER
 THE MASTER PERMIT # 15110807 INDICATES 1500 SQ FT.
  
 THE SUBMITTAL DOES NOT APPEAR TO HAVE AN APPROVAL FROM
 THE ENGINEER OF RECORD PER MASTER PERMIT # 15110807 FOR
 THIS CHANGE.
  
 SECOND REVIEW : CORRECTED.
  
  
  
 3) THE SUBMITTED PLANS ARE NOT BOUND/ORGANIZED.
  
 PLEASE BIND ALL SHEETS SO THEY CAN NOT BECOME LOST,
 REMOVED OR DISORGANIZED.
  
  
 SECOND REVIEW : PLANS REMAIN UNBOUND/LOOSE/UNSTAPLED.
 PLEASE SECURE ALL PAGES TO EACH OTHER.
  
  
  
 4) FIRE SPRINKLER SPECIFICATION SHEETS ARE NOT INCLUDED
 WITH THE SUMITTAL.
  
 PLEASE PROVIDE SPEC SHEETS FOR THE TYPE OF EQUIPMENT
 BEING INSTALLED.
  
 SECOND REVIEW : CORRECTED.
  
  
  
 5) THE DESIGN AREAS ARE NOT CLEARLY INDICATED ON THE
 INDICATING SHEETS. THERE APPEARS TO BE DASHED LINES BUT
 ALSO CLOUDED AREAS ON THE SAME SHEET.
  
 PLEASE PROVIDE DEFINITIVE LINES FOR EACH DESIGN AREA
 AND REMOVE ANY UNNECESSARY INDICATORS.
  
 SECOND REVIEW : CORRECTED.
  
  
  
 6) NO DIMENSIONS ARE PROVIDED FOR THE DESIGN AREAS.
  
 PLEASE PROVIDE DIMENSIONS OF EACH DESIGN AREA FOR
 VERIFICATION PRUPOSES.
  
 SECOND REVIEW : CORRECTED.
  
  
  
 7) THE AREAS OF THE OPEN STAIRWAYS DO NOT INDICATE FIRE
 SPRINKLER PROTECTION PER NFPA 8.15.4
  
 8.15.4.1* GENERAL. UNLESS THE REQUIREMENTS OF 8.15.4.4
 ARE
 MET, WHERE MOVING STAIRWAYS, STAIRCASES, OR SIMILAR
 FLOOR OPENINGS
 ARE UNENCLOSED AND WHERE SPRINKLER PROTECTION IS
 SERVING
 AS THE ALTERNATIVE TO ENCLOSURE OF THE VERTICAL
 OPENING, THE
 FLOOR OPENINGS INVOLVED SHALL BE PROTECTED BY CLOSELY
 SPACED
 SPRINKLERS IN COMBINATION WITH DRAFT STOPS IN
 ACCORDANCE WITH
 8.15.4.2 AND 8.15.4.3.
  
 PLEASE PROVIDE FOR COMPLAINCE OR PROVIDE A DETAILED
 NARRATIVE OF EXPLANATION OF WHY IT MAY NOT BE REQUIRED.
  
 SECOND REVIEW : TWO OF THE THREE ESCALATORS SHOW
 CLOSELY SPACED SPRINKLERS BUT THE WEST/MAIN ESCALTOR
 DOES NOT. PLEASE CLARIFY AND OR CORRECT WHY THIS ONE
 DOES NOT.
  
  
  
  
 8) ONLY ONE SET OF HYDRALIC CALCULATION ARE PROVIDED.
  
 PLEASE PROVIDE ANOTHER SET OF HYDRALIC CALCULATIONS,
 ONE PER EACH PLAN SET.
  
 SECOND REVIEW : CORRECTED.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 SECOND REVIEW :
  
 9A) PLANS REMAIN UNBOUND/LOOSE/UNSTAPLED.
  
 PLEASE SECURE ALL PAGES TO EACH OTHER.
  
  
  
 9B) THERE ARE 5 SHEETS NOTED ON THIS SUBMITTAL. THE
 FIRST SHEET IS INDICATED AS 1 OF 4.
  
 PLEASE CORRECT.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By pleduc Date 2016-06-16 Time 13:36 Rev Time 0.00
Received By pleduc Date 2016-06-16 Time 10:12 Sent To PC
Notes
2016-06-16 13:32:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE ADDRESS ON THE APPLICATION, 501 EVERNIA ST, DOES
 NOT MATCH THE ADDRESS ON THE TITLE BLOCK, 520 DATURA
 ST,
  
 PLEASE CLARIFY/CORRECT.
  
 2) DESIGN AREA 2 INDICATES AN AREA OF SPRINKLER
 OPERATION DENSITY OF 900. THE ENGINEER OF RECORD PER
 THE MASTER PERMIT # 15110807 INDICATES 1500 SQ FT.
  
 THE SUBMITTAL DOES NOT APPEAR TO HAVE AN APPROVAL FROM
 THE ENGINEER OF RECORD PER MASTER PERMIT # 15110807 FOR
 THIS CHANGE.
  
 3) THE SUBMITTED PLANS ARE NOT BOUND/ORGANIZED.
  
 PLEASE BIND ALL SHEETS SO THEY CAN NOT BECOME LOST,
 REMOVED OR DISORGANIZED.
  
 4) FIRE SPRINKLER SPECIFICATION SHEETS ARE NOT INCLUDED
 WITH THE SUMITTAL.
  
 PLEASE PROVIDE SPEC SHEETS FOR THE TYPE OF EQUIPMENT
 BEING INSTALLED.
  
 5) THE DESIGN AREAS ARE NOT CLEARLY INDICATED ON THE
 INDICATING SHEETS. THERE APPEARS TO BE DASHED LINES BUT
 ALSO CLOUDED AREAS ON THE SAME SHEET.
  
 PLEASE PROVIDE DEFINITIVE LINES FOR EACH DESIGN AREA
 AND REMOVE ANY UNNECESSARY INDICATORS.
  
 6) NO DIMENSIONS ARE PROVIDED FOR THE DESIGN AREAS.
  
 PLEASE PROVIDE DIMENSIONS OF EACH DESIGN AREA FOR
 VERIFICATION PRUPOSES.
  
 7) THE AREAS OF THE OPEN STAIRWAYS DO NOT INDICATE FIRE
 SPRINKLER PROTECTION PER NFPA 8.15.4
  
 8.15.4.1* GENERAL. UNLESS THE REQUIREMENTS OF 8.15.4.4
 ARE
 MET, WHERE MOVING STAIRWAYS, STAIRCASES, OR SIMILAR
 FLOOR OPENINGS
 ARE UNENCLOSED AND WHERE SPRINKLER PROTECTION IS
 SERVING
 AS THE ALTERNATIVE TO ENCLOSURE OF THE VERTICAL
 OPENING, THE
 FLOOR OPENINGS INVOLVED SHALL BE PROTECTED BY CLOSELY
 SPACED
 SPRINKLERS IN COMBINATION WITH DRAFT STOPS IN
 ACCORDANCE WITH
 8.15.4.2 AND 8.15.4.3.
  
 PLEASE PROVIDE FOR COMPLAINCE OR PROVIDE A DETAILED
 NARRATIVE OF EXPLANATION OF WHY IT MAY NOT BE REQUIRED.
  
 8) ONLY ONE SET OF HYDRALIC CALCULATION ARE PROVIDED.
  
 PLEASE PROVIDE ANOTHER SET OF HYDRALIC CALCULATIONS,
 ONE PER EACH PLAN SET.
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-21 Cont ID  
Sent By pleduc Date 2016-09-21 Time   Rev Time 0.00
Received By pleduc Date 2016-09-19 Time 11:47 Sent To  
Notes
2016-09-20 11:47:35RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-20 Cont ID  
Sent By lmarchan Date 2016-09-20 Time 11:46 Rev Time 0.00
Received By lmarchan Date 2016-09-15 Time 12:59 Sent To  
Notes
2016-09-15 13:00:03RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-16 Cont ID  
Sent By pleduc Date 2016-06-16 Time   Rev Time 0.00
Received By pleduc Date 2016-06-08 Time 10:12 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-06-16 Cont ID  
Sent By pleduc Date 2016-06-16 Time   Rev Time  
Received By pleduc Date   Time   Sent To  
Notes
***NONE***