Plan Review Details - Permit 16060576
Plan Review Stops For Permit 16060576
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-10 Cont ID  
Sent By cthroop Date 2016-08-10 Time 15:41 Rev Time 0.00
Received By cthroop Date 2016-08-10 Time 15:41 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-13 Cont ID  
Sent By cthroop Date 2016-07-13 Time 11:42 Rev Time 0.00
Received By cthroop Date 2016-07-13 Time 11:42 Sent To E
Notes
2016-07-13 11:55:25BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 ACTION: DENIED
 DATE: 7/13/16
  
 1. PLAN TO REFERENCE CURRENT GOVERNING CODES.
 2. PLAN TO BE REVIEWED, SIGNED AND SEALED BY DESIGN
 PROFESSIONAL.
 3. SUBMITTAL TO BE IN DUPLICATE.
 4. REF. PLAN PG. 2 OF 10. INSTALLATION DETAIL REQUIRES
 HILTI WEDGE ANCHORS. PROVIDE DETAIL OF EXISTING WALL
 TYPE WITH FASTENER SIZE AND LENGTH FOR WALL TYPE.
 5. REF. PLAN PG. 3 OF 10. INSTALLATION COMMENTS REQUIRE
 "STUD MOUNT FLUSH TO FACIA". NO DETAIL PROVIDED.
 PROVIDE DETAIL OF EXISTING WALL TYPE WITH FASTENER SIZE
 AND LENGTH FOR WALL TYPE.
 6. REF. PLAN PG. 4 OF 10. INSTALLATION COMMENTS REQUIRE
 "MECHANICALLY FASTEN WITH APPROPRIATE HARDWARE". NO
 DETAIL PROVIDED. PROVIDE DETAIL OF EXISTING WALL TYPE
 WITH FASTENER SIZE AND LENGTH FOR WALL TYPE.
 7. REF. PLAN PG. 5 OF 10. INSTALLATION COMMENTS REQUIRE
 "MECHANICALLY FASTEN WITH APPROPRIATE HARDWARE". NO
 DETAIL PROVIDED. PROVIDE DETAIL OF EXISTING WALL TYPE
 WITH FASTENER SIZE AND LENGTH FOR WALL TYPE.
 8. PROVIDE WIND LOAD DESIGN PER ASCE 7-10 FOR EACH
 LETTER TYPE. PROVIDE FASTENER SCHEDULE FOR EACH LETTER
 TYPE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-06-28 Cont ID  
Sent By cthroop Date 2016-06-28 Time 08:51 Rev Time 0.00
Received By cthroop Date 2016-06-28 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-08-10 Cont ID  
Sent By mvaldes Date 2016-08-10 Time 13:38 Rev Time 0.00
Received By mvaldes Date 2016-08-10 Time 13:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-13 Cont ID  
Sent By mvaldes Date 2016-07-13 Time 18:17 Rev Time 0.00
Received By mvaldes Date 2016-07-13 Time 18:13 Sent To Z
Notes
2016-07-13 18:26:34REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - WEST PALM BEACH REQUIRES 2 SET OF COPIES PER
 APPLICATION SUBMITTAL SHOP DRAWINGS.
  
 - WHETHER THE CONTRACTOR OR LANDLORD INSTALLS THE SIGN
 EXTERIOR LIGHTING CONTROL PER FBC E C405.2.4 IS NOT
 RELEVANT. PLEASE ADD A NOTE ON THE PLANS WITH THIS
 MANDATORY REQUIREMENT. IF WORK IS TO BE DONE BY OTHERS
 KEEP IN MIND ALL ELECTRICAL WORK SHALL BE DONE A
 LICENSED PROFFESIONAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By mvaldes Date 2016-06-27 Time 08:51 Rev Time 0.00
Received By mvaldes Date 2016-06-27 Time 08:47 Sent To B
Notes
2016-06-27 08:53:11REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - FBC E SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. (ADD TO ELECTRICAL
 GENERAL NOTES)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-19 Cont ID  
Sent By cpuell Date 2016-08-19 Time 10:06 Rev Time 0.00
Received By cpuell Date 2016-08-04 Time 14:56 Sent To  
Notes
2016-08-04 14:57:01RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-22 Cont ID  
Sent By eschneid Date 2016-07-22 Time 14:24 Rev Time 0.00
Received By eschneid Date 2016-07-06 Time 14:31 Sent To  
Notes
2016-07-06 14:31:24RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-28 Cont ID  
Sent By cthroop Date 2016-06-28 Time 08:51 Rev Time 0.00
Received By cthroop Date 2016-06-08 Time 10:15 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-08-18 Cont ID  
Sent By eschneid Date 2016-08-18 Time 10:28 Rev Time 0.25
Received By eschneid Date 2016-08-18 Time 08:49 Sent To PC
Notes
2016-08-18 10:29:31SIGNAGE PERMITTED: 24 SF
 PROPOSED SIGN: 16.6 SF
  
  
2016-08-05 08:32:22ROUTED TO ERIC SCHNEIDER

Review Stop Z ZONING
Rev No 2 Status F Date 2016-07-22 Cont ID  
Sent By eschneid Date 2016-07-22 Time 14:22 Rev Time 0.25
Received By eschneid Date 2016-07-22 Time 13:34 Sent To  
Notes
2016-07-22 14:24:19FAILED
  
 PROVIDE WRITTEN RESPONSE.
  
 1) REPEAT COMMENT: ZONING STAFF IS NOT CLEAR AS TO WHAT
 THE PERMIT IS SUPPOSED TO COVER. THE PERMIT STATES IT
 IS FOR ILLUMINATED CHANNEL LETTERS, WHICH ARE ONLY
 PERMITTED ON THE EXTERIOR FA?ADE OF THE BUILDING. THERE
 IS ALSO A SHEET FOR A NON-ILLUMINATED SIGN THAT APPEARS
 TO BE INSIDE THE ARCADE. IF THE PERMIT DOES NOT INCLUDE
 THE INTERIOR SIGN, THEN THIS SHEET SHALL BE REMOVED
 FROM THE PERMIT PACKAGE. IF IT IS INCLUDED, THE PERMIT
 VALUE SHALL BE INCREASED ACCORDINGLY.
  
 2) SIGN IS LOCATED ON THE EXTERIOR OF THE ARCADE MEETS
 CITYPLACE SIGN CODE.
  
 SIGNAGE PERMITTED: 24 SF
 PROPOSED SIGN: 16.6 SF
  
 3) SIGN LOCATED ON THE INTERIOR OF THE ARCADE MEETS
 CITYPLACE SIGN CODE.
  
 SIGNAGE PERMITTED: 24 SF
 PROPOSED SIGN: 7.4 SF
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2016-07-14 08:09:12ROUTED TO ERIC SCHNEIDER

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-22 Cont ID  
Sent By cthroop Date 2016-06-28 Time 08:51 Rev Time 0.25
Received By eschneid Date 2016-06-17 Time 17:07 Sent To E
Notes
2016-06-22 19:44:15FAILED
  
 PROVIDE WRITTEN RESPONSE.
  
 1) STAFF IS NOT CLEAR AS TO WHERE THIS SIGN IS TO BE
 LOCATED. THE PACKET PROVIDED BY SECURITY SIGNS SHOWS
 THE SIGN LOCATED ABOVE THE ENTRANCE TO THE STORE, WHICH
 MAKES IT AN INTERIOR ARCADE SIGN. THESE SIGNS MAY NOT
 BE ILLUMINATED. BARON SIGN PLANS SHOW THE SIGN AS
 LOCATED ON THE EXTERIOR OF THE ARCADE. THESE SIGNS MAY
 BE ILLUMINATED.
  
 2) IF THE SIGN IS LOCATED ON THE EXTERIOR OF THE
 ARCADE, IT IS PERMITTED.
  
 SIGNAGE PERMITTED: 24 SF
 PROPOSED SIGN: 16.6 SF
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.