Plan Review Details - Permit 16060212
Plan Review Stops For Permit 16060212
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-09 Cont ID  
Sent By jwitmer Date 2016-06-09 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2016-06-09 Time 07:30 Sent To  
Notes
2016-06-09 07:39:33BUILDING PLAN REVIEW
 REVISION: 16060212
 PERMIT: 14090028
 ADD: 525 S FLAGLER DR, COMMON FLOOR AREA
 CONT: URBAN DESIGN CONCEPTS
 TEL: (561)301-9506
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 09/2016
 ACTION: DENIED
  
 1) THE WIND DESIGN UNDER THE 2010 FBC-B HAS NOT BEEN
 PROVIDEDPLEASE NOTE THE EXPOSURE IS A EXPOSURE D.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 1.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 2) THE S-SHEETS DOES NOT INCLUDE THE DESIGN CRITERIA
 UNDER SECTION 3105 OF THE FBC-B FOR RIGID FRAME
 STRUCTURES.
  
 3) THE PLANS DO NOT INCLUDE CODE LANGUAGE FOR
 COMPLIANCE WITH: 2010 FBC-B 3105.3.1. FABRIC USED FOR
 AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE FLAME
 PROPAGATION PERFORMANCE CRITERIA OF NFPA 701.
  
 4) SHEET S-3 INDICATES A NEW 6 FT. TALL FRAMELESS GLASS
 GUARD RAIL. THE PLANS HAVE CROSS SECTION DETAILS THAT
 ARE NOT CLEAR AS TO HOW COMPLIANCE WITH SECTIONS LISTED
 BELOW ARE GOING TO BE MET:
  
 2010FBC-B:
 1607.7.1 HANDRAILS AND GUARDS. HANDRAILS AND GUARDS
 SHALL BE DESIGNED TO RESIST A LOAD OF 50 POUNDS PER
 LINEAR FOOT (PLF) (0.73 KN/M) APPLIED IN ANY DIRECTION
 AT THE TOP AND TO TRANSFER THIS LOAD THROUGH THE
 SUPPORTS TO THE STRUCTURE. GLASS HANDRAIL ASSEMBLIES
 AND GUARDS SHALL ALSO COMPLY WITH SECTION 2407.
  
 1607.1.1CONCENTRATED LOADS. HANDRAILS AND GUARDS SHALL
 BE ABLE TO RESIST A SINGLE CONCENTRATED LOAD OF 200
 POUNDS (0.89 KN), APPLIED IN ANY DIRECTION AT ANY POINT
 ALONG THE TOP, AND TO TRANSFER THIS LOAD THROUGH THE
 SUPPORTS TO THE STRUCTURE. THIS LOAD NEED NOT BE
 ASSUMED TO ACT CONCURRENTLY WITH THE LOADS SPECIFIED IN
 SECTION 1607.7.1.
 1607.7.1.2 COMPONENTS.
  
 1607.7.1.2 COMPONENTS. INTERMEDIATE RAILS (ALL THOSE
 EXCEPT THE HANDRAIL), BALUSTERS AND PANEL FILLERS SHALL
 BE DESIGNED TO WITHSTAND A HORIZONTALLY APPLIED NORMAL
 LOAD OF 50 POUNDS (0.22 KN) ON AN AREA EQUAL TO 1
 SQUARE FOOT (0.0929 M2), INCLUDING OPENINGS AND SPACE
 BETWEEN RAILS. REACTIONS DUE TO THIS LOADING ARE NOT
 REQUIRED TO BE SUPERIMPOSED WITH THOSE OF SECTION
 1607.7.1 OR 1607.7.1.1.
  
 2407.1.1 LOADS. THE PANELS AND THEIR SUPPORT SYSTEM
 SHALL BE DESIGNED TO WITHSTAND THE LOADS SPECIFIED IN
 SECTION 1607.7. A SAFETY FACTOR OF FOUR SHALL BE USED.
  
 2407.1.4 GLAZING IN WIND-BORNE DEBRIS REGIONS. GLAZING
 INSTALLED IN IN-FILL PANELS OR BALUSTERS IN WIND-BORNE
 DEBRIS REGIONS SHALL COMPLY WITH THE FOLLOWING:
  
 2407.1.4.1 BALLUSTERS AND IN-FILL PANELS. GLASS
 INSTALLED IN EXTERIOR RAILING IN-FILL PANELS OR
 BALUSTERS SHALL BE LAMINATED GLASS COMPLYING WITH
 CATEGORY II OF CPSC 16 CFR 1201 OR CLASS A OF ANSI
 Z97.1.
  
 2407.1.4.2 GLASS SUPPORTING TOP RAIL. WHEN THE TOP RAIL
 IS SUPPORTED BY GLASS, THE ASSEMBLY SHALL BE TESTED
 ACCORDING TO THE IMPACT REQUIREMENTS OF SECTION
 1609.1.2. THE TOP RAIL SHALL REMAIN IN PLACE AFTER
 IMPACT.
  
 5)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-24 Cont ID  
Sent By vperez Date 2016-06-24 Time 11:02 Rev Time 0.00
Received By vperez Date 2016-06-24 Time 11:02 Sent To  
Notes
2016-06-24 11:03:28INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A REVISED PANEL LOAD CALCULATION PER
 FBC 107.3.5 REFLECTING ADDED LOADS.
 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-09 Cont ID  
Sent By pleduc Date 2016-06-09 Time 11:09 Rev Time 0.00
Received By wjolin Date 2016-06-09 Time 10:37 Sent To  
Notes
2016-06-09 11:06:57525 SOUTH FLAGLER DRIVE - 5TH FLOOR
 PERMIT #14090028
 TRACKING #16060212
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET S-2: PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR
 THE CANOPY MATERIAL.
  
 SHEET S-4: PLAN INDICATES A NEW KITCHEN ISLAND. WHAT
 COOKING APPLIANCES ARE INTENDED TO BE INSTALLED?
  
 SHEET S-7: PLAN INDICATES EXISTING TENT STRUCTURE WITH
 NEW BARBEQUE GRILL. THE COOKING GRILL LOCATED ON THE
 POOL DECK SHALL COMPLY WITH NFPA 96 OR SHALL BE LOCATED
 AT LEAST 10 FEET FROM ANY BUILDING, STRUCTURE, OR
 COMBUSTIBLES PER NFPA 1 SECTION 10.11.6.1. IF THE GRILL
 WILL BE USED UNDER A ROOF STRUCTURE, THE DESIGN SHALL
 COMPLY WITH NFPA 96. LISTED EQUIPMENT PERMANENTLY
 INSTALLED IN ACCORDANCE WITH ITS LISTING, APPLICABLE
 CODES, AND MANUFACTURER?S INSTRUCTIONS SHALL BE
 PERMITTED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-24 Cont ID  
Sent By vperez Date 2016-06-24 Time 11:03 Rev Time 0.00
Received By vperez Date 2016-06-24 Time 11:03 Sent To  
Notes
2016-06-06 14:25:55B16

Review Stop P PLUMBING
Rev No 1 Status F Date   Cont ID  
Sent By tklarge Date 2016-06-20 Time   Rev Time 0.00
Received By gearl Date 2016-06-20 Time 14:32 Sent To  
Notes
2016-06-20 14:32:14NEED ENLARGED SET OF PLUMBING PLANS FOR REVIEW.
 NEED RELIEF LINE LOCATION FOR W/H
 NEED INFO ON STAIRS IF THEY HAVE A 1 HOUR FIRE RATED
 PLEASE CHECK FBC 2014 SECTION 1009.9.4 TO MAKE SURE W/H
 CAN BE PLACED IN THIS LOCATION