Plan Review Details - Permit 16060161
Plan Review Stops For Permit 16060161
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-07-08 Cont ID  
Sent By shill Date 2016-07-08 Time 15:00 Rev Time 0.00
Received By shill Date 2016-07-08 Time 15:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-23 Cont ID  
Sent By shill Date 2016-06-23 Time 16:47 Rev Time 0.00
Received By shill Date 2016-06-23 Time 16:47 Sent To  
Notes
2016-06-23 16:54:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. CALCULATIONS NOW REFER TO INCORRECT BUILDING CODE,
 PLEASE REVISE.
  
 2. SEE FBC RESIDENTIAL FIGURE 301.2(7); ZONES 2 AND 3
 ARE REQUIRED TO BE A MINIMUM OF 4', BUT THE RAS
 CALCULATIONS SPECIFY 3'. PLEASE REVISE.
  
 3. PROVIDE A 2ND SET OF THE ROOF / SITE PLAN. TWO
 COMPLETE COLLATED SETS OF PERMIT DOCUMENTS ARE REQUIRED
 FOR PERMIT ISSUANCE.
  
 AN EMAIL WAS SENT TO CONTRACTOR; WILL ACCEPT RESUB VIA
 EMAIL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-07 Cont ID  
Sent By shill Date 2016-06-07 Time 15:15 Rev Time 0.00
Received By shill Date 2016-06-07 Time 15:14 Sent To  
Notes
2016-06-07 15:17:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ASSEMBLY PROPOSED IS NOT CLEAR. TWO ASSEMBLIES WERE
 INCLUDED WITH THE NOA. ONE HAS A DP LIMIT OF -52.5 BUT
 REFERS TO GENERAL LIMITATION #9 (NO ENHANCED FASTENING)
 AND IS NOT CONSISTENT WITH THE CALCULATIONS PROVIDED BY
 SANDRA PUERTA, AR.
  
 THE OTHER ASSEMBLY HAS A LIMITATION OF -127.5, SO IS
 ALSO NOT CONSISTENT WITH THE CALCULATIONS.
  
 FBC 5TH ED RESIDENTIAL 301, PROVIDE ASSEMBLY PROPOSED
 AND CALCULATIONS CONSISTENT WITH THE ASSEMBLY.
  
 2. PROVIDE A SITE PLAN AND ROOF PLAN, FBC 107. THE
 APPLICATION INCLUDES TWO ADDRESSES. A SEPARATE PERMIT
 IS REQUIRED FOR EACH STRUCTURE, IF APPLICABLE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-23 Cont ID  
Sent By shill Date 2016-06-23 Time 16:58 Rev Time 0.00
Received By shill Date 2016-06-16 Time 11:50 Sent To  
Notes
2016-06-16 11:50:46RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-07 Cont ID  
Sent By shill Date 2016-06-07 Time 15:18 Rev Time 0.00
Received By shill Date 2016-06-03 Time 10:49 Sent To  
Notes
2016-06-06 10:50:20SHILL