Plan Review Details - Permit 16060160
Plan Review Stops For Permit 16060160
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-05-25 Cont ID  
Sent By dharvey Date 2018-05-25 Time 12:40 Rev Time 0.00
Received By dharvey Date 2018-05-25 Time 12:40 Sent To  
Notes
2018-05-25 12:42:31SPOKE WITH CHIEF LEDUC AND EXPLAINED DEVICES ARE BEING
 REMOVED AND REPLACED WITH THE SAME DEVICE IN THE SAME
 LOCATION AND ONLY AN ELECTRICAL PERMIT SHOULD BE
 REQUIRED WITH NO PLANS. HE IS IN AGREEMENT AND
 AUTHORIZED THE NOTE TO BE ADDED AND PERMIT ISSUED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-25 Cont ID  
Sent By shill Date 2018-05-25 Time 10:42 Rev Time 0.00
Received By shill Date 2018-05-25 Time 10:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-08 Cont ID  
Sent By mvaldes Date 2016-06-08 Time 18:14 Rev Time 0.00
Received By mvaldes Date 2016-06-08 Time 18:14 Sent To  
Notes
2016-06-08 18:17:03REVIEW 2014 5TH BC ED. NECK 2011
 MARIO VALDEZ
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - NO PLANS SUBMITTED WITH APPLICATION FBC107 MINIMUM
 PLAN CRITEREA.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2018-05-25 Cont ID  
Sent By dharvey Date 2018-05-25 Time 12:42 Rev Time 0.00
Received By dharvey Date 2018-05-25 Time 12:42 Sent To  
Notes
2018-05-25 12:43:13SEE NOTES ON ELECTRICAL REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2018-05-25 Cont ID  
Sent By shill Date 2018-05-25 Time 10:41 Rev Time 0.00
Received By shill Date 2018-05-25 Time 10:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By scaldero Date 2016-06-06 Time 11:40 Rev Time 0.00
Received By scaldero Date 2016-06-06 Time 11:36 Sent To E
Notes
2016-06-06 11:40:53PERMIT # 16060160
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) NO PLANS SUBMITTED WITH THE APPLICATION. A SITE PLAN
 AND SHOP DRAWINGS ARE NEEDED, AS WELL AS SPECIFICATION
 SHEETS FOR THE DEVICES.
 2) PERMIT APPLICATION INDICATES THAT DEVICES BEING
 REPLACED ARE "SPEAKER ONLY UNITS". SITE PLAN SHOULD
 INDICATE LOCATION OF VISIBLE DEVICES TO ENSURE
 COMPLIANCE WITH NFPA STANDARDS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-08 Cont ID  
Sent By mvaldes Date 2016-06-08 Time 18:17 Rev Time 0.00
Received By mvaldes Date 2016-06-03 Time 13:48 Sent To  
Notes
2016-06-03 13:48:59ROUTED TO FIRE