Plan Review Details - Permit 16060158
Plan Review Stops For Permit 16060158
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-07-06 Cont ID  
Sent By jwitmer Date 2016-07-06 Time 15:24 Rev Time 0.00
Received By jwitmer Date 2016-07-06 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-22 Cont ID  
Sent By jwitmer Date 2016-06-22 Time   Rev Time 0.00
Received By jwitmer Date 2016-06-22 Time   Sent To  
Notes
2016-06-22 15:53:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060158
 ADD: 651 OKEECHOBEE BLVD.
 CONT: CAREY CONSTRUCTION
 TEL: 561-746-1440
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 22/2016
 ACTION: DENIED
  
 1) COMPLIED. ADDRESS: 651 OKEECHOBEE BLVD
  
 2) THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD
 BUILDING FL S. S. 553.71(7) ?THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES
 OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A)COMPLIED. THRESHOLD INSPECTION PLAN.
  
 2B) SEMI-COMPLIED. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
 2ND REQUEST. THE SPECIAL INSPECTOR FORMS SUBMITTED TO
 THE BUILDING DEPARTMENT ARE NOT COMPLETE, MISSING THE
 NOTARIZED SIGNATURES OF OWNER & CONTRACTOR.
  
 2C) MISSING PLANS. MISSING STATEMENT. THRESHOLD BLDG.,
 REQUIRED STATEMENT: W.P.B. AMENDMENT 110.3.7.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE ARCHITECT OR ENGINEER OF RECORD
 CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
  
 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F)(1) 2ND REQUEST. NOT COMPLETED. NOTE FOR PAPER PLANS
 3 SETS OF DOCUMENTS ARE REQUIRED. ONLY 2 SETS OF SIGNED
 & SEALED CONCRETE RESTORATION & REHABILITATION PROJECT
 MANUEL WERE SUBMITTED.
  
 2F)(2) OF THE (2) SIGNED & SEALED CONCRETE RESTORATION
 & REHABILITATION PROJECT MANUALS THE TABLE OF CONTENTS
 IS NOT SIGNED AND SEALED. SHOW COMPLIANCE WITH FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002(2) FL. ADMIN. CODE. A
 COVER SHEET OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
  
 2G) 2ND REQUEST. 110.3.7.4.1 THE SPECIAL INSPECTOR,
 UPON COMPLETION OF THE BUILDING AND PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY, FILE A SIGNED
 AND SEALED STATEMENT WITH THE ENFORCEMENT AGENCY IN
 SUBSTANTIALLY THE FOLLOWING FORM: ?TO THE BEST OF MY
 KNOWLEDGE AND BELIEF, THE ABOVE DESCRIBED CONSTRUCTION
 OF ALL STRUCTURAL LOAD-BEARING COMPONENTS COMPLIES WITH
 THE PERMITTED DOCUMENTS, AND THE SHORING AND RESHORING
 CONFORMS TO THE SHORING AND RESHORING PLANS SUBMITTED
 TO THE ENFORCEMENT AGENCY.?
  
 2H) 2ND REQUEST. 110.3.7.4.2 ANY PROPOSAL TO INSTALL AN
 ALTERNATE STRUCTURAL PRODUCT OR SYSTEM TO WHICH
 BUILDING CODES APPLY SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR REVIEW FOR COMPLIANCE WITH THE
 CODES AND MADE PART OF THE ENFORCEMENT AGENCY?S
 RECORDED SET OF PERMIT DOCUMENTS. 110.3.7.4.3 ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION
 SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN
 COMPLIANCE WITH THE SHORING DOCUMENTS BY THE
 CONTRACTOR.
  
 2I) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3)2ND REQUEST. PLEASE PROVIDE A SITE PLAN SHOWING THE
 PROPERTY LINES, CONSTRUCTION AREAS, STAGING AREAS, HOW
 THE OCCUPANTS OF THE BUILDING WILL BE SAFE GUARDED
 DURING THEIR ENTRY AND EXIT OF THE BUILDING. SHOW
 COMPLIANCE WITH 2014 FBC-B 3306.7 COVERED WALKWAYS
 INCLUDING LIGHTING FOR THE EXIT DISCHARGE.
 2014 FBC-B 3310.2 MAINTENANCE OF MEANS OF EGRESS.
 REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR
 ALTERATIONS AND ADDITIONS TO ANY BUILDING.
  
 4A)2ND REQUEST. IF SCAFFOLDING EXTENDS BEYOND THE
 PRIVATE PROPERTY AND ONTO CITY RIGHT OF WAY ENGINEERING
 WILL REQUIRE RIGHT OF WAY PERMITS. PLEASE CONTACT MANNY
 GONZALEZ AT THE ENGINEERING DEPARTMENT 494-1085.
  
 4B) 2ND REQUEST. IF SCAFFOLDING IS TO BE USED FOR THE
 HEIGHT OF THE BUILDING, PLEASE PROVIDE HOW THE
 SCAFFOLDING WILL BE BUILT AS WELL AS HOW THE
 SCAFFOLDING WILL BE ANCHORED TO RESIST LATERAL WIND
 LOADING. THERE APPEARS SAND BLASTING WILL ALSO BE A
 ELEMENT OF THE OPERATION, HOW WILL THE SANDBLASTING BE
 CONTAINED, WILL THERE BE WIND SCREENS, IF SO PLEASE
 PROVIDE WHAT ELEMENTS WILL BE INTRODUCED TO KEEP THE
 SCAFFOLDING FROM MOVING WITH THE LATERAL EFFECT OF WIND
 ON THE WIND SCREENS. AT WHAT SAFETY FACTOR ARE THESE
 ELEMENTS FACTORED? 107.2.1.3 ADDITIONAL INFORMATION.
 2014 FBC-B 3302.1 & 3306.1.
  
 5) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2014
 FBC-B 3309.1 WHERE REQUIRED. ALL STRUCTURES UNDER
 CONSTRUCTION, ALTERATION OR DEMOLITION SHALL BE
 PROVIDED WITH NO FEWER THAN ONE APPROVED PORTABLE FIRE
 EXTINGUISHER IN ACCORDANCE WITH SECTION 906 AND SIZED
 FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS:
  
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
  
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
  
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 [F] 3309.2 FIRE HAZARDS.
 THE PROVISIONS OF THIS CODE AND THE FLORIDA FIRE
 PREVENTION CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD
 AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION
 OPERATIONS.
  
 6) 2ND REQUEST. DURING THE RESTORATION WORK ON THE
 BALCONIES HOW WILL THE TENANTS BE SAFE GUARDED FROM THE
 WORK AREA AND EGRESS ONTO THE BALCONIES? 3306.1
 PROTECTION REQUIRED.
  
 7) ALL ADD-MIXTURES RHINOPLASTIC CONCRETE ADDITIVES ARE
 TO BE REVIEWED BY THE ENGINEER OF RECORD AS ALL OTHER
 ADDITIVES SHOP DRAWING STAMP OF APPROVAL. 107.3.4
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-09 Cont ID  
Sent By jwitmer Date 2016-06-09 Time 17:27 Rev Time  
Received By jwitmer Date 2016-06-09 Time 15:44 Sent To  
Notes
2016-06-09 17:27:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060158
 ADD: 651 OKEECHOBEE BLVD.
 CONT: CAREY CONSTRUCTION
 TEL: 561-746-1440
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 09/2016
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE WORK UNDER THE
 SCOPE OF THIS PERMIT LIST THE SITE ADDRESS AS 651
 OKEECHOBEE BLVD. WHERE AS ALL OF THE SUPPORTING
 DOCUMENTS, A.T. DESIGN LETTER, THRESHOLD INSPECTION
 PLAN, SPECIAL INSPECTOR AGREEMENT AND CITY PLACE TOWER
 CONCRETE RESTORATION AND REHABILITATION PROJECT MANUAL
 LIST THE PROJECT ADDRESS PAGE 0400-1 AS 525 OKEECHOBEE
 BLVD. PLEASE CORRECT THE DISCREPANCY IN THE ADDRESS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED,
 DISCREPANCY.
  
 2) THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD
 BUILDING FL S. S. 553.71(7) ?THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES
 OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) UPDATE THE THRESHOLD INSPECTION PLAN, TO THE
 CORRECT ADDRESS. 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THE SPECIAL INSPECTOR FORMS SUBMITTED TO THE BUILDING
 DEPARTMENT ARE NOT COMPLETE, MISSING THE NOTARIZED
 SIGNATURES OF OWNER & CONTRACTOR.
  
 2C) MISSING STATEMENT. THRESHOLD BLDG., REQUIRED
 STATEMENT: W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR
 THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED
 BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS
 COMPLY WITH THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) NOT COMPLETED. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
  
 2E) NOT COMPLETED. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOT COMPLETED. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED.
  
 2G) 110.3.7.4.1 THE SPECIAL INSPECTOR, UPON COMPLETION
 OF THE BUILDING AND PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY, FILE A SIGNED AND SEALED
 STATEMENT WITH THE ENFORCEMENT AGENCY IN SUBSTANTIALLY
 THE FOLLOWING FORM: ?TO THE BEST OF MY KNOWLEDGE AND
 BELIEF, THE ABOVE DESCRIBED CONSTRUCTION OF ALL
 STRUCTURAL LOAD-BEARING COMPONENTS COMPLIES WITH THE
 PERMITTED DOCUMENTS, AND THE SHORING AND RESHORING
 CONFORMS TO THE SHORING AND RESHORING PLANS SUBMITTED
 TO THE ENFORCEMENT AGENCY.?
  
 2H) 110.3.7.4.2 ANY PROPOSAL TO INSTALL AN ALTERNATE
 STRUCTURAL PRODUCT OR SYSTEM TO WHICH BUILDING CODES
 APPLY SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 REVIEW FOR COMPLIANCE WITH THE CODES AND MADE PART OF
 THE ENFORCEMENT AGENCY?S RECORDED SET OF PERMIT
 DOCUMENTS. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2I) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3) PLEASE PROVIDE A SITE PLAN SHOWING THE PROPERTY
 LINES, CONSTRUCTION AREAS, STAGING AREAS, HOW THE
 OCCUPANTS OF THE BUILDING WILL BE SAFE GUARDED DURING
 THEIR ENTRY AND EXIT OF THE BUILDING. SHOW COMPLIANCE
 WITH 2014 FBC-B 3306.7 COVERED WALKWAYS INCLUDING
 LIGHTING FO THE EXIT DISCHARGE.
 2014 FBC-B 3310.2 MAINTENANCE OF MEANS OF EGRESS.
 REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR
 ALTERATIONS AND ADDITIONS TO ANY BUILDING.
  
 4A) IF SCAFFOLDING EXTENDS BEYOND THE PRIVATE PROPERTY
 AND ONTO CITY RIGHT OF WAY ENGINEERING WILL REQUIRE
 RIGHT OF WAY PERMITS. PLEASE CONTACT MANNY GONZALEZ AT
 THE ENGINEERING DEPARTMENT 494-1085.
  
 4B) IF SCAFFOLDING IS TO BE USED FOR THE HEIGHT OF THE
 BUILDING, PLEASE PROVIDE HOW THE SCAFFOLDING WILL BE
 BUILT AS WELL AS HOW THE SCAFFOLDING WILL BE ANCHORED
 TO RESIST LATERAL WIND LOADING. THERE APPEARS SAND
 BLASTING WILL ALSO BE A ELLEMENT OF THE OPERATION, HOW
 WILL THE SANDBLASTING BE CONTAINED, WILL THERE BE WIND
 SCREENS, IF SO PLEASE PROVIDE WHAT ELEMENTS WILL BE
 INTRODUCED TO KEEP THE SCAFFOLDING FROM MOVING WITH THE
 LATERAL AFFECT OF WIND ON THE WIND SCREENS. AT WHAT
 SAFETY FACTOR ARE THESE ELEMENTS FACTORED? 107.2.1.3
 ADDITIONAL INFORMATION. 2014 FBC-B 3302.1 & 3306.1.
  
 5) PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B 3309.1
 WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NO FEWER THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD
 AS FOLLOWS:
  
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
  
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
  
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 [F] 3309.2 FIRE HAZARDS.
 THE PROVISIONS OF THIS CODE AND THE FLORIDA FIRE
 PREVENTION CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD
 AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION
 OPERATIONS.
  
 6) DURING THE RESTORATION WORK ON THE BALCONIES HOW
 WILL THE TENANTS BE SAFE GUARDED FROM THE WORK AREA AND
 EGRESS ONTO THE BALCONIES? 3306.1 PROTECTION REQUIRED.
  
 7) ALL ADD-MIXTURES RHINOOPLASTIC CONCRETE ADDITIVES
 ARE TO BE REVIEWED BY THE ENGINEER OF RECORD AS ALL
 OTHER ADDITIVES SHOP DRAWING STAMP OF APPROVAL.
 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-06 Cont ID  
Sent By jwitmer Date 2016-07-06 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2016-06-30 Time 09:13 Sent To  
Notes
2016-07-01 09:13:28RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-22 Cont ID  
Sent By jwitmer Date 2016-06-22 Time 15:54 Rev Time 0.00
Received By jwitmer Date 2016-06-10 Time 09:44 Sent To  
Notes
2016-06-13 09:45:11RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-10 Cont ID  
Sent By jwitmer Date 2016-06-10 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2016-06-03 Time 11:32 Sent To  
Notes
2016-06-06 11:33:08ROUTED TO ZONING

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2016-07-06 Cont ID  
Sent By jwitmer Date 2016-07-06 Time 15:24 Rev Time 0.00
Received By jwitmer Date 2016-07-06 Time 15:24 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2016-06-22 Cont ID  
Sent By   Date 2016-06-22 Time   Rev Time 0.00
Received By   Date 2016-06-22 Time   Sent To  
Notes
2016-06-22 15:55:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060158
 ADD: 651 OKEECHOBEE BLVD.
 CONT: CAREY CONSTRUCTION
 TEL: 561-746-1440
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 22/2016
 ACTION: DENIED
  
 1) COMPLIED. ADDRESS: 651 OKEECHOBEE BLVD.
  
 2) THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD
 BUILDING FL S. S. 553.71(7) ?THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES
 OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A)COMPLIED. THRESHOLD INSPECTION PLAN.
  
 2B) SEMI-COMPLIED. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
 2ND REQUEST. THE SPECIAL INSPECTOR FORMS SUBMITTED TO
 THE BUILDING DEPARTMENT ARE NOT COMPLETE, MISSING THE
 NOTARIZED SIGNATURES OF OWNER & CONTRACTOR.
  
 2C) MISSING PLANS. MISSING STATEMENT. THRESHOLD BLDG.,
 REQUIRED STATEMENT: W.P.B. AMENDMENT 110.3.7.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE ARCHITECT OR ENGINEER OF RECORD
 CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
  
 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F)(1) 2ND REQUEST. NOT COMPLETED. NOTE FOR PAPER PLANS
 3 SETS OF DOCUMENTS ARE REQUIRED. ONLY 2 SETS OF SIGNED
 & SEALED CONCRETE RESTORATION & REHABILITATION PROJECT
 MANUEL WERE SUBMITTED.
  
 2F)(2) OF THE (2) SIGNED & SEALED CONCRETE RESTORATION
 & REHABILITATION PROJECT MANUALS THE TABLE OF CONTENTS
 IS NOT SIGNED AND SEALED. SHOW COMPLIANCE WITH FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002(2) FL. ADMIN. CODE. A
 COVER SHEET OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
  
 2G) 2ND REQUEST. 110.3.7.4.1 THE SPECIAL INSPECTOR,
 UPON COMPLETION OF THE BUILDING AND PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY, FILE A SIGNED
 AND SEALED STATEMENT WITH THE ENFORCEMENT AGENCY IN
 SUBSTANTIALLY THE FOLLOWING FORM: ?TO THE BEST OF MY
 KNOWLEDGE AND BELIEF, THE ABOVE DESCRIBED CONSTRUCTION
 OF ALL STRUCTURAL LOAD-BEARING COMPONENTS COMPLIES WITH
 THE PERMITTED DOCUMENTS, AND THE SHORING AND RESHORING
 CONFORMS TO THE SHORING AND RESHORING PLANS SUBMITTED
 TO THE ENFORCEMENT AGENCY.?
  
 2H) 2ND REQUEST. 110.3.7.4.2 ANY PROPOSAL TO INSTALL AN
 ALTERNATE STRUCTURAL PRODUCT OR SYSTEM TO WHICH
 BUILDING CODES APPLY SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR REVIEW FOR COMPLIANCE WITH THE
 CODES AND MADE PART OF THE ENFORCEMENT AGENCY?S
 RECORDED SET OF PERMIT DOCUMENTS. 110.3.7.4.3 ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION
 SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN
 COMPLIANCE WITH THE SHORING DOCUMENTS BY THE
 CONTRACTOR.
  
 2I) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-06-10 Cont ID  
Sent By jwitmer Date 2016-06-10 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2016-06-09 Time 15:44 Sent To  
Notes
2016-06-10 09:00:35SEE BLDG REVIEW.

Review Stop Z ZONING
Rev No 2 Status N Date 2016-06-20 Cont ID  
Sent By eschneid Date 2016-06-20 Time 12:19 Rev Time 0.25
Received By eschneid Date 2016-06-20 Time 12:19 Sent To B
Notes
2016-06-20 12:21:30NO GROUND LEVEL WORK - NO NEW OR EXPANDED BALCONIES.
  
 STILL NOTED THAT THERE ARE INCONSISTENT ADDRESSES ON
 THE APPLICATION AND SPECIAL INSPECTOR AGREEMENT.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-08 Cont ID  
Sent By eschneid Date 2016-06-08 Time 13:43 Rev Time 0.25
Received By eschneid Date 2016-06-08 Time 13:43 Sent To  
Notes
2016-06-08 13:49:17FAILED
  
 1) THE SPECIAL INSPECTOR AGREEMENT LISTS THE PROJECT
 ADDRESS AS 525 OKEECHOBEE BLVD, YET THE PERMIT
 APPLICATION ADDRESS IS LISTED AS 651 OKEECHOBEE BLVD.
 THESE ARE TWO COMPLETELY DIFFERENT PARCELS. THE CORRECT
 PARCEL NEEDS TO BE ON RECORD.
  
 2) PROVIDE 2 COPIES OF A SURVEY OUTLINING WHERE THE
 WORK WILL OCCUR.
  
 3) MORE COMMENTS MAY BE PROVIDED WHEN THE ABOVE
 INFORMATION IS PROVIDED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.