Plan Review Details - Permit 16051302
Plan Review Stops For Permit 16051302
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-06-02 Cont ID  
Sent By tklarge Date 2016-06-02 Time 08:26 Rev Time 0.00
Received By tklarge Date 2016-06-02 Time 06:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-06-01 Cont ID  
Sent By tklarge Date 2016-06-01 Time 05:03 Rev Time 0.00
Received By tklarge Date 2016-06-01 Time 04:44 Sent To  
Notes
2016-06-01 04:57:041) INDICATE THE TYPE OF PIPE, THE PIPE SIZE, AND THE
 LENGTH OF PIPE FROM THE STEP DOWN REGULATOR TO THE
 APPLIANCE FOR THE TANKLESS WATER HEATER, THE DRYER AND
 THE FUTURE POOL HEATER. FBC 107.2.1.
 2) SUBMIT TWO COPIES OF THE APPLICABLE PIPE SIZING
 TABLE FOR THESE APPLIANCES. FBC 107.2.1.
 3) ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2014
 FGC SEC. 301.3. MANUF. INSTALLATION MANUALS FOR ALL
 APPLIANCES SHALL BE ONSITE FOR INSPECTOR.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-02 Cont ID  
Sent By tklarge Date 2016-06-02 Time 08:26 Rev Time 0.00
Received By tklarge Date 2016-06-01 Time 14:10 Sent To  
Notes
2016-06-01 14:10:53RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-01 Cont ID  
Sent By tklarge Date 2016-06-01 Time 05:04 Rev Time 0.00
Received By tklarge Date 2016-05-31 Time 13:35 Sent To  
Notes
2016-05-31 13:35:44PLUMB -$5000