Plan Review Details - Permit 16051254
Plan Review Stops For Permit 16051254
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-05 Cont ID  
Sent By jwitmer Date 2016-07-05 Time 16:04 Rev Time 0.00
Received By jwitmer Date 2016-07-05 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-08 Cont ID  
Sent By jwitmer Date 2016-06-08 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2016-06-08 Time 07:41 Sent To  
Notes
2016-06-08 09:03:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16051254
 ADD: 401 S. DIXIE HWY. SUITE # 1
 CONT: IBIS BUILDING CORP.
 TEL: 561-318-8408
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 08/ 2016
 ACTION: DENIED
 LAST PERMITTED ACTIVITY: 13081030.
  
 1) SHEET LS-1 THE LIFE SAFETY PLAN SHOWS 2 EXIT DOORS
 TO THE EXTERIOR AND A EXIT ACCESS DOOR TO A FIRE RATED
 CORRIDOR TO THE REAR OF THE TENANT SPACE.
 THE REAR EXIT ACCESS DOOR SHOWS A CEILING EXIT
 DIRECTIONAL LIGHT. THE ARE 2 OTHER EXITS TOWARD THE
 FRONT OF THE TENANT SPACE, ONE IS A EXIT DISCHARGE DOOR
 DIRECTLY TO THE SIDEWALK ON DIXIE HWY. THE OTHER DOOR
 THAT HAS THE CEILING MOUNTED EXIT LIGHT TAKING YOU TO
 THE SIDE DOOR THAT LEADS TO A FENCED IN AND GATED
 COURTYARD. IS THE GATE UNLOCKED AND MEET THE
 REQUIREMENTS FOR AN EGRESS COURT THAT LEADS TO THE
 PUBLIC WAY? 2014 FBC-B 1027.4.2 & 1027.5.
  
 2) SHEET A2 SHOWS A NEW BREAKROOM WITH SINK. THERE ARE
 NO DETAILS SHOWING COMPLIANCE WITH: 2014
 FBC-ACCESSIBLITY CODE 606.1-5.
  
 3) JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-28 Cont ID  
Sent By vperez Date 2016-06-28 Time 09:05 Rev Time 0.00
Received By vperez Date 2016-06-28 Time 08:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-31 Cont ID  
Sent By cpuell Date 2016-06-23 Time 09:42 Rev Time 0.00
Received By vperez Date 2016-05-31 Time 14:45 Sent To  
Notes
2016-05-31 17:12:43BLDG MISC 2
2016-05-31 14:45:47INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY IF THIS PERMIT IS THE DEMO ONLY OF
 SCOPE SHOWN. IF NOT PLEASE PROVIDE REQUIRED INFORMATION
 ON PLANS REGARDING NEW SCOPE. SHOW LIGHTING CIRCUITS
 DESIGNATIONS, EXISTING OR NEW. PANEL SCHEDULE
 REFLECTING NEW INSTALL OF FIXTURES. PROVIDE ALSO THE
 MINIMUM LIGHTING DENSITIES FOR THE AREA AND LIGHTING
 CONTROLS AS PER FBC ENERGY CONSERVATION C405. ALSO
 CLARIFY EMERGENCY LIGHTING FOR THE AREA SHOWN. FBC
 107.3.5 MINIMUM CRITERIA PLAN REVIEW.
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-27 Cont ID  
Sent By scaldero Date 2016-06-27 Time 11:12 Rev Time 0.00
Received By scaldero Date 2016-06-27 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By scaldero Date 2016-06-06 Time 12:07 Rev Time 0.00
Received By scaldero Date 2016-06-06 Time 11:57 Sent To  
Notes
2016-06-06 12:07:16PERMIT # 16051254
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 3) PERMIT APPLICATION INDICATES "SELECTIVE INTERIOR
 DEMOLITION", HOWEVER ALL WALLS ARE MARKED AS
 "EXISTING". A DEMOLITION SHEET / PLAN HAS NOT BEEN
 PROVIDED.
  
 4) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWERS' COMMENTS
 HAVE BEEN SATISFIED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-06 Cont ID  
Sent By tklarge Date 2016-07-06 Time 15:26 Rev Time 0.00
Received By tklarge Date 2016-06-22 Time 09:45 Sent To  
Notes
2016-06-23 09:45:57B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-23 Cont ID  
Sent By cpuell Date 2016-06-13 Time 09:42 Rev Time 0.00
Received By cpuell Date 2016-05-27 Time 09:24 Sent To E
Notes
2016-06-03 10:17:51B12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-30 Cont ID  
Sent By ccole Date 2016-06-30 Time 09:28 Rev Time 0.00
Received By ccole Date 2016-06-30 Time 09:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By ccole Date 2016-06-06 Time 14:58 Rev Time 0.00
Received By ccole Date 2016-06-06 Time 14:58 Sent To  
Notes
2016-06-06 15:17:321ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16051254
 6/6/16
  
 1) TRANSFER DUCTS MUST BE SIZED 1.5 TIMES THE
 CROSS-SECTIONAL AREA OF THE SUPPLY DUCTS ENTERING EACH
 ROOM- SEE SECTION 601.5 AND PROVIDE THE TRANSFER AND
 SUPPLY DUCT SIZES FOR EACH ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-06 Cont ID  
Sent By tklarge Date 2016-07-06 Time 15:26 Rev Time 0.00
Received By tklarge Date 2016-07-06 Time 15:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-13 Cont ID  
Sent By gearl Date 2016-06-13 Time   Rev Time 0.00
Received By gearl Date 2016-06-13 Time   Sent To  
Notes
2016-06-13 14:34:05NEED DRAWING TO SHOW SANITARY AND WATER PIPING FOR
 SEWER CONNECTION AND FIXTURES- SINK AND W/H