Plan Review Stops For Permit 16051254 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2016-07-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-07-05 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-07-05 |
Time |
15:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-06-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-06-08 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-06-08 |
Time |
07:41 |
Sent To |
|
|
Notes |
2016-06-08 09:03:43 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 16051254 | | ADD: 401 S. DIXIE HWY. SUITE # 1 | | CONT: IBIS BUILDING CORP. | | TEL: 561-318-8408 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: WED. JUNE 08/ 2016 | | ACTION: DENIED | | LAST PERMITTED ACTIVITY: 13081030. | | | | 1) SHEET LS-1 THE LIFE SAFETY PLAN SHOWS 2 EXIT DOORS | | TO THE EXTERIOR AND A EXIT ACCESS DOOR TO A FIRE RATED | | CORRIDOR TO THE REAR OF THE TENANT SPACE. | | THE REAR EXIT ACCESS DOOR SHOWS A CEILING EXIT | | DIRECTIONAL LIGHT. THE ARE 2 OTHER EXITS TOWARD THE | | FRONT OF THE TENANT SPACE, ONE IS A EXIT DISCHARGE DOOR | | DIRECTLY TO THE SIDEWALK ON DIXIE HWY. THE OTHER DOOR | | THAT HAS THE CEILING MOUNTED EXIT LIGHT TAKING YOU TO | | THE SIDE DOOR THAT LEADS TO A FENCED IN AND GATED | | COURTYARD. IS THE GATE UNLOCKED AND MEET THE | | REQUIREMENTS FOR AN EGRESS COURT THAT LEADS TO THE | | PUBLIC WAY? 2014 FBC-B 1027.4.2 & 1027.5. | | | | 2) SHEET A2 SHOWS A NEW BREAKROOM WITH SINK. THERE ARE | | NO DETAILS SHOWING COMPLIANCE WITH: 2014 | | FBC-ACCESSIBLITY CODE 606.1-5. | | | | 3) JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | DEVELOPMENT SERVICES DEPARTMENT | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-06-28 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-06-28 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-06-28 |
Time |
08:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-05-31 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2016-06-23 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-05-31 |
Time |
14:45 |
Sent To |
|
|
Notes |
2016-05-31 17:12:43 | BLDG MISC 2 | 2016-05-31 14:45:47 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE CLARIFY IF THIS PERMIT IS THE DEMO ONLY OF | | SCOPE SHOWN. IF NOT PLEASE PROVIDE REQUIRED INFORMATION | | ON PLANS REGARDING NEW SCOPE. SHOW LIGHTING CIRCUITS | | DESIGNATIONS, EXISTING OR NEW. PANEL SCHEDULE | | REFLECTING NEW INSTALL OF FIXTURES. PROVIDE ALSO THE | | MINIMUM LIGHTING DENSITIES FOR THE AREA AND LIGHTING | | CONTROLS AS PER FBC ENERGY CONSERVATION C405. ALSO | | CLARIFY EMERGENCY LIGHTING FOR THE AREA SHOWN. FBC | | 107.3.5 MINIMUM CRITERIA PLAN REVIEW. | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2016-06-27 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2016-06-27 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2016-06-27 |
Time |
11:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2016-06-06 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2016-06-06 |
Time |
12:07 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2016-06-06 |
Time |
11:57 |
Sent To |
|
|
Notes |
2016-06-06 12:07:16 | PERMIT # 16051254 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAIL COMMENTS: | | 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | AMENDMENTS. | | | | 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | 3) PERMIT APPLICATION INDICATES "SELECTIVE INTERIOR | | DEMOLITION", HOWEVER ALL WALLS ARE MARKED AS | | "EXISTING". A DEMOLITION SHEET / PLAN HAS NOT BEEN | | PROVIDED. | | | | 4) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY | | THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWERS' COMMENTS | | HAVE BEEN SATISFIED. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 644-7326 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-07-06 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-07-06 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-06-22 |
Time |
09:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-06-23 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2016-06-13 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2016-05-27 |
Time |
09:24 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2016-06-30 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-06-30 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-06-30 |
Time |
09:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-06-06 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-06-06 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-06-06 |
Time |
14:58 |
Sent To |
|
|
Notes |
2016-06-06 15:17:32 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16051254 | | 6/6/16 | | | | 1) TRANSFER DUCTS MUST BE SIZED 1.5 TIMES THE | | CROSS-SECTIONAL AREA OF THE SUPPLY DUCTS ENTERING EACH | | ROOM- SEE SECTION 601.5 AND PROVIDE THE TRANSFER AND | | SUPPLY DUCT SIZES FOR EACH ROOM. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2016-07-06 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-07-06 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-07-06 |
Time |
15:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-06-13 |
|
|
Cont ID |
|
Sent By |
gearl |
Date |
2016-06-13 |
Time |
|
Rev Time |
0.00 |
Received By |
gearl |
Date |
2016-06-13 |
Time |
|
Sent To |
|
|
Notes |
2016-06-13 14:34:05 | NEED DRAWING TO SHOW SANITARY AND WATER PIPING FOR | | SEWER CONNECTION AND FIXTURES- SINK AND W/H |
|
|