Plan Review Details - Permit 16051235
Plan Review Stops For Permit 16051235
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-03-03 Cont ID  
Sent By jwitmer Date 2017-03-03 Time 15:06 Rev Time 0.00
Received By jwitmer Date 2017-03-03 Time 13:26 Sent To  
Notes
2017-03-03 15:06:58BUILDING PROVISO:
 ROOF PRODUCT APPROVAL REQUIRED.
 SUBMITTED THE COVERSHEET FOR FL. 6623 HYDRO STOP LIQUID
 APPLIED ROOF SYSTEMS NO TECHNICAL SHEET OR SYSTEMS.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-09-22 Cont ID  
Sent By jwitmer Date 2016-09-22 Time 09:56 Rev Time 0.00
Received By jwitmer Date 2016-09-22 Time 09:54 Sent To  
Notes
2016-09-22 09:56:35BUILDING PLAN REVIEW
 W. P. B. PERMIT:16051235
 ADD: 880 VALLEY FORGE RD.
 CONT: FLORIDA DESIGN DRILLING CORP.
 TEL: 561-844-2966
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. SEPT. 22/2016
 ACTION: DENIED
  
 NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH RESPECT
 TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 RESPONSE INDICATES AES PRECAST WILL APPLY FOR STATE
 APPROVAL FOR PREMANUFACTURED BUILDING PROGRAM. UNTIL
 THE PLANS ARE APPROVED THROUGH THE STATE. THIS PERMIT
 AND THE OTHER SIMILAR PERMITS CANNOT BE APPROVED. THERE
 ARE NO INSPECTIONS CALLED IN TO VERIFY THE REBAR IN THE
 CONCRETE POUR OF THE FLOOR, WALLS AND OR ROOF SYSTEM.
  
  
 1) PLEASE NOTE SHEET S-2 INDICATES UNDER NOTE # 1 THIS
 IS A PRE-MANUFACTURERED BUILDING. PRE-MANUFACTURED
 BUILDINGS ARE BUILT AT A PLANT TOTALLY COMPLETE. FOR
 MANUFACTURERED BUILDINGS (MODULAR)AT A PLANT AND
 TRANSPORTED COMPLETE TO THE JOBSITE, THEY HAVE TO BE
 PART OF THE STATE MANUFACTURED BUILDING PROGRAM IN
 COMPLIANCE WITH :
 FLORIDA STATUTE 428.3 INSPECTIONS. INSPECTION OF
 INSTALLATION OF MANUFACTURED BUILDINGS AND CONSTRUCTION
 ACTIVITIES CONDUCTED AT THE SITE OF THE INSTALLATION
 SHALL BY CONDUCTED PURSUANT TO CHAPTER 1 HEREOF.
 INSPECTIONS DURING THE MANUFACTURING PROCESS SHALL BE
 CONDUCTED BY THOSE THIRD-PARTY AGENCIES
  
 THIS BUILDING IS SITE BUILT W/ OFF SITE
 PRE-MANUFACTURED PANELS. PLEASE CORRECT THE
 TERMINOLOGY. THE ISSUE WE HAVE WITH THIS BUILDING IS ON
 SHEET S-1 NOTES INDICATE FABRICATION AND ERECTION
 DRAWINGS WILL BE PREPARED BY A DELEGATE ENGINEER.
  
 WHAT WE ARE NOT GETTING IS THE INSPECTION OF THE STEEL
 (REBAR) AND EMBEDS IN THE STRUCTURAL WALL AND ROOF
 PANEL OR PANELS. THIS NEEDS TO BE COMPLETED BY A STATE
 CERTIFIED BUILDING INSPECTOR WHO HOLDS A BN LICENSE.
 THIS IS NOT A MODULAR BUILDING UNDER THE STATE PROGRAM.
 FLORIDA STATUTE 428.3 INSPECTIONS. INSPECTION OF
 INSTALLATION OF MANUFACTURED BUILDINGS AND CONSTRUCTION
 ACTIVITIES CONDUCTED AT THE SITE OF THE INSTALLATION
 SHALL BY CONDUCTED PURSUANT TO CHAPTER 1 HEREOF.
 INSPECTIONS DURING THE MANUFACTURING PROCESS SHALL BE
 CONDUCTED BY THOSE THIRD-PARTY AGENCIES FLORIDA ADMIN.
 CODE CHAPTER 61-41 MANUFACTURERED BUILDINGS.
  
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW BEFORE BEING SUBMITTED TO
 THE BUILDING DEPARTMENT.
  
 2) TO BE REVIEWED UNDER THE STATE APPROVAL SYSTEM.
 ALL ONSITE WELDING OF EMBEDS TO PANEL SYSTEMS EITHER
 WALL OR ROOF PANELS WILL NEED TO BE COMPLETED BY A
 CERTIFIED WELDER, PLEASE PROVIDE PAPERWORK INDICATING
 THEIR CERTIFICATION.
  
 3) REQUEST DEFERRED SUBMITTALS. PLEASE PROVIDE
 COMPLIANCE WITH: 2014 FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) PANEL WALLS: WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 4) REQUEST DEFERRED SUBMITTALS. FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5-6) PRESSURES ARE IN VULT
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-23 Cont ID  
Sent By jwitmer Date 2016-06-23 Time 13:18 Rev Time 0.00
Received By jwitmer Date 2016-06-22 Time 16:21 Sent To  
Notes
2016-06-23 08:15:39BUILDING PLAN REVIEW
 W. P. B. PERMIT:16051235
 ADD: 880 VALLEY FORGE RD.
 CONT: FLORIDA DESIGN DRILLING CORP.
 TEL: 561-844-2966
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. JUNE 23/2016
 ACTION: DENIED
  
  
 1) PLEASE NOTE SHEET S-2 INDICATES UNDER NOTE # 1 THIS
 IS A PRE-MANUFACTURERED BUILDING. PRE-MANUFACTURED
 BUILDINGS ARE BUILT AT A PLANT TOTALLY COMPLETE. FOR
 MANUFACTURERED BUILDINGS (MODULAR)AT A PLANT AND
 TRANSPORTED COMPLETE TO THE JOBSITE, THEY HAVE TO BE
 PART OF THE STATE MANUFACTURED BUILDING PROGRAM IN
 COMPLIANCE WITH :
 FLORIDA STATUTE 428.3 INSPECTIONS. INSPECTION OF
 INSTALLATION OF MANUFACTURED BUILDINGS AND CONSTRUCTION
 ACTIVITIES CONDUCTED AT THE SITE OF THE INSTALLATION
 SHALL BY CONDUCTED PURSUANT TO CHAPTER 1 HEREOF.
 INSPECTIONS DURING THE MANUFACTURING PROCESS SHALL BE
 CONDUCTED BY THOSE THIRD-PARTY AGENCIES
  
 THIS BUILDING IS SITE BUILT W/ OFF SITE
 PRE-MANUFACTURED PANELS. PLEASE CORRECT THE
 TERMINOLOGY. THE ISSUE WE HAVE WITH THIS BUILDING IS ON
 SHEET S-1 NOTES INDICATE FABRICATION AND ERECTION
 DRAWINGS WILL BE PREPARED BY A DELEGATE ENGINEER.
  
 WHAT WE ARE NOT GETTING IS THE INSPECTION OF THE STEEL
 (REBAR) AND EMBEDS IN THE STRUCTURAL WALL AND ROOF
 PANEL OR PANELS. THIS NEEDS TO BE COMPLETED BY A STATE
 CERTIFIED BUILDING INSPECTOR WHO HOLDS A BN LICENSE.
 THIS IS NOT A MODULAR BUILDING UNDER THE STATE PROGRAM.
 FLORIDA STATUTE 428.3 INSPECTIONS. INSPECTION OF
 INSTALLATION OF MANUFACTURED BUILDINGS AND CONSTRUCTION
 ACTIVITIES CONDUCTED AT THE SITE OF THE INSTALLATION
 SHALL BY CONDUCTED PURSUANT TO CHAPTER 1 HEREOF.
 INSPECTIONS DURING THE MANUFACTURING PROCESS SHALL BE
 CONDUCTED BY THOSE THIRD-PARTY AGENCIES FLORIDA ADMIN.
 CODE CHAPTER 61-41 MANUFACTURERED BUILDINGS.
  
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW BEFORE BEING SUBMITTED TO
 THE BUILDING DEPARTMENT.
  
 2) ALL ONSITE WELDING OF EMBEDS TO PANEL SYSTEMS EITHER
 WALL OR ROOF PANELS WILL NEED TO BE COMPLETED BY A
 CERTIFIED WELDER, PLEASE PROVIDE PAPERWORK INDICATING
 THEIR CERTIFICATION.
  
 3) PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) PANEL WALLS: WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 4) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5) SHEET S2 THE WALL INTERIOR ZONE # 4 PRESSURES ARE IN
 VULT PLEASE PROVIDE THE PRESSURES IN VASD SINCE THE
 PRODUCT APPROVALS ARE ALL IN VASD. 2014 FBC-B 1609.3.1
 WIND SPEED CONVERSION VULT TO VASD.
  
 6) SHEET S2 SHOWS COMPONENT AND CLADDING PRESSURES FOR
 THE WALL ZONES BUT THERE ARE NO PRESSURES FOR THE FLAT
 CONCRETE ROOF ZONES 1, 2 NOR 3. 2014 FBC-B 1603.1.4
 WIND DESIGN DATA. PLEASE CONVERT PRESSURES TO VASD.
 2014 FBC-B 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-19 Cont ID  
Sent By vperez Date 2016-09-19 Time 08:34 Rev Time 0.00
Received By vperez Date 2016-09-19 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-24 Cont ID  
Sent By vperez Date 2016-06-24 Time 11:49 Rev Time 0.00
Received By vperez Date 2016-06-24 Time 11:49 Sent To  
Notes
2016-06-24 11:49:54INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADDRESS MECHANICAL REVIEWER EXHAUST COMMENTS
 FOR AN ELECTRICAL APPROVAL. FBC 107.3.5
 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-07-11 Cont ID  
Sent By Mgonzale Date 2016-07-11 Time   Rev Time 0.50
Received By mgonzale Date 2016-07-11 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-09-16 Cont ID  
Sent By wjolin Date 2016-09-16 Time 13:42 Rev Time 0.00
Received By wjolin Date 2016-09-16 Time 13:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-06-08 Cont ID  
Sent By wjolin Date 2016-06-08 Time 10:26 Rev Time 0.00
Received By wjolin Date 2016-06-08 Time 10:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-02-24 Time 15:19 Sent To  
Notes
2017-02-27 15:19:21RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-13 Cont ID  
Sent By gjohnson Date 2016-10-13 Time 14:52 Rev Time 0.00
Received By gjohnson Date 2016-09-14 Time 13:14 Sent To  
Notes
2016-09-15 13:14:47C19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-13 Cont ID  
Sent By lmarchan Date 2016-07-13 Time 10:34 Rev Time 0.00
Received By lmarchan Date 2016-05-27 Time 08:27 Sent To  
Notes
2016-05-31 08:28:30C13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-21 Cont ID  
Sent By ccole Date 2016-09-21 Time 07:00 Rev Time 0.00
Received By ccole Date 2016-09-21 Time 07:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-10 Cont ID  
Sent By ccole Date 2016-06-10 Time 07:44 Rev Time 0.00
Received By ccole Date 2016-06-10 Time 07:44 Sent To  
Notes
2016-06-10 07:45:441ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 16051235
 6/10/16
  
 1) AN AC SYSTEM, EXHAUST FAN, AND MOTORIZED LOUVER ARE
 SHOWN ON SHEET D-01-01- THE CHEMICAL FEED SHELTER
 BUILDING: PLEASE PROVIDE MECHANICAL PLANS INCLUDING:
 A) AC SYSTEM, EXHAUST FAN, AND LOUVER EQUIPMENT
 SCHEDULES
 B) AC LOAD CALCULATIONS
 C) EXHAUST VENTILATION CALCULATIONS
 D) SEQUENCE OF OPERATIONS FOR THE AC, FAN, AND LOUVER
 E) WIIND LOAD ENGINEERING FOR INSTALLATION OF THE FAN
 AND LOUVER.
  
 2) PROVIDE CLEARANCE DISTANCE MEASUREMENTS FOR THE AIR
 INTAKE LOUVER AS REQUIRED BY SECTION 401.4, AND INTAKE
 OPENING PROTECTION DETAILS PER 401.5. SUBMIT A FL.
 PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE LOUVER WITH
 APPROVAL SIGNATURE BY THE DESIGN PROFESSIONAL OF
 RECORD.
  
 3) PROVIDE CLEARANCE DISTANCE MEASUREMENTS FOR THE FAN
 DISCHARGE AS REQUIRED BY SECTION 501.3.1, AND OPENING
 PROTECTION DETAILS PER 501.3.2. SUBMIT A FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE FAN WITH APPROVAL
 SIGNATURE BY THE DESIGN PROFESSIONAL OF RECORD.
  
 4) PLEASE REFER TO SECTION 414.1.3 FBC-14 BUILDING AND
 SUBMIT THE REQUIRED REPORT FOR THE SODIUM HYPOCHLORITE
 AND ALL OTHER CHEMICALS TO BE STORED ON USED FOR
 PROCESSING IN THE BUILDING. PLEASE NOTE THAT A
 HAZARDOUS EXHAUST VENTILATION SYSTEM MAY BE REQUIRED-
 SEE SECTION 510 FBC-14 MECHANICAL FOR CODE
 REQUIREMENTS.
  
 5) PROVIDE SUBMITTALS FOR ALL PROCESS PIPING, VALVES,
 AND FITTINGS WITH SHOP DRAWING APPROVAL SIGNATURES FROM
 THE DESIGN PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-10-13 Cont ID  
Sent By gjohnson Date 2016-10-13 Time 14:50 Rev Time 0.00
Received By gjohnson Date 2016-10-13 Time 14:50 Sent To  
Notes
2016-10-13 14:51:32IRRIGATION APPROVED
  
 SEPARATE PERMIT REQUIRED
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-13 Cont ID  
Sent By gjohnson Date 2016-10-13 Time 14:50 Rev Time 0.00
Received By gjohnson Date 2016-10-13 Time 14:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-14 Cont ID  
Sent By gearl Date 2016-06-14 Time 13:59 Rev Time 0.00
Received By gearl Date 2016-06-14 Time 13:58 Sent To  
Notes
2016-06-14 13:58:10NEED SPEC ON SUMP PUMP
 NEED SIZE OF PIPING ON SUMP PUMP DISCHARGE AND AND
 CONNECTION OF DISCHARGE
 NEED VAC BREAKER ON WATER HOSE WHEEL

Review Stop Z ZONING
Rev No 2 Status P Date 2016-09-22 Cont ID  
Sent By jroach Date 2016-09-22 Time 13:44 Rev Time 0.00
Received By jroach Date 2016-09-22 Time 10:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-22 Cont ID  
Sent By jroach Date 2016-06-22 Time 09:53 Rev Time 0.00
Received By jroach Date 2016-06-22 Time 09:53 Sent To L
Notes
***NONE***