Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-22 Cont ID  
Sent By jwitmer Date 2016-09-22 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2016-09-22 Time 15:55 Sent To  
Notes
2016-09-22 16:27:28BUILDING PLAN REVIEW
 W. P. B. PERMIT:16051222
 ADD: 8740 N STATE RD. 7
 CONT: FLORIDA DESIGN DRILLING CORP.
 TEL: 561-844-2966
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. SEPT. 22/2016
 ACTION: BUILDING PROVISO
  
 1) PLEASE NOTE SHEET S-3 SHOWS A CONCRETE VAULT BEING
 BUILT APPROX. 10 FEET BELOW GRADE. THE PLANS DO NOT
 INDICATE HOW THE DEWATERING OF THE SITE WILL OCCUR. THE
 SOILS REPORT SUBMITTED PROVIDES TO WHAT DEPTH THE
 DEWATERING NEEDS TO OCCUR TO PROVIDE A DRY WORKING
 SURFACE AND TO ALLOW FOR DENSITY TESTING AS PART OF THE
 FOUNDATION PREPARATION. THE CONTRACTOR IS RESPONSIBLE
 FOR THE DESIGN, MAINTENANCE AND OTHER FACTORS TO
 DEWATERING AND GROUNDWATER. TO DATE THE CONTRACTOR HAS
 NOT SUBMITTED A DEWATERING PLAN AND IS AT THERE OWN
 RISK!!!
  
 2014 FBC-B 3303.5 WATER ACCUMULATION. PROVISION SHALL
 BE MADE TO PREVENT THE ACCUMULATION OF WATER OR DAMAGE
 TO ANY FOUNDATIONS ON THE PREMISES OR THE ADJOINING
 PROPERTY.
  
 WITHOUT A DEWATERING PLAN THE SLOPES MAY NOT BE
 MAINTAINED BECAUSE OF THE INTRUSION OF GROUND WATER.
 CONTRACTOR IS AT OWN RISK!!!!
 3304.1.1 SLOPE LIMITS. . CUT SLOPES FOR PERMANENT
 EXCAVATIONS SHALL BE NOT STEEPER THAN ONE UNIT VERTICAL
 IN TWO UNITS HORIZONTAL (50-PERCENT SLOPE). DEVIATION
 FROM THE FOREGOING LIMITATIONS FOR CUT SLOPES SHALL BE
 PERMITTED ONLY UPON THE PRESENTATION OF A SOIL
 INVESTIGATION REPORT ACCEPTABLE TO THE BUILDING
 OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-23 Cont ID  
Sent By jwitmer Date 2016-06-23 Time 14:33 Rev Time 0.00
Received By jwitmer Date 2016-06-23 Time 14:01 Sent To  
Notes
2016-06-23 14:03:03BUILDING PLAN REVIEW
 W. P. B. PERMIT:16051222
 ADD: 8740 N STATE RD. 7
 CONT: FLORIDA DESIGN DRILLING CORP.
 TEL: 561-844-2966
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. JUNE 23/2016
 ACTION: DENIED
  
 1) PLEASE NOTE SHEET S-3 SHOWS A CONCRETE VAULT BEING
 BUILT APPROX. 10 FEET BELOW GRADE. THE PLANS DO NOT
 INDICATE HOW THE DEWATERING OF THE SITE WILL OCCUR, AND
 TO MAINTAIN A SAFE ALLOWABLE SAFE BEARING PRESSURE OF
 2,000 PSF BEFORE THE FOUNDARION IS PORED. 2014 FBC-B
 1803.5.4 GROUND -WATER TABLE.
 2014 FBC-B 3303.5 WATER ACCUMULATION. PROVISION SHALL
 BE MADE TO PREVENT THE ACCUMULATION OF WATER OR DAMAGE
 TO ANY FOUNDATIONS ON THE PREMISES OR THE ADJOINING
 PROPERTY.
 3304.1.1 SLOPE LIMITS. . CUT SLOPES FOR PERMANENT
 EXCAVATIONS SHALL BE NOT STEEPER THAN ONE UNIT VERTICAL
 IN TWO UNITS HORIZONTAL (50-PERCENT SLOPE). DEVIATION
 FROM THE FOREGOING LIMITATIONS FOR CUT SLOPES SHALL BE
 PERMITTED ONLY UPON THE PRESENTATION OF A SOIL
 INVESTIGATION REPORT ACCEPTABLE TO THE BUILDING
 OFFICIAL.
  
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-14 Cont ID  
Sent By vperez Date 2016-09-14 Time 11:18 Rev Time 0.00
Received By vperez Date 2016-09-14 Time 11:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-23 Cont ID  
Sent By vperez Date 2016-06-23 Time 10:04 Rev Time 0.00
Received By vperez Date 2016-06-23 Time 09:52 Sent To  
Notes
2016-06-23 10:04:37INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADDRESS THE POSSIBLE EXHAUST SYSTEM REQUIRED
 BY MECHANICAL REVIEWER FOR AN ELECTRICAL APPROVAL.
 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-09-01 Cont ID  
Sent By Mgonzale Date 2016-09-01 Time   Rev Time 1.00
Received By mgonzale Date 2016-09-01 Time   Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-06-08 Cont ID  
Sent By wjolin Date 2016-06-08 Time 13:03 Rev Time 0.00
Received By wjolin Date 2016-06-08 Time 13:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-10-20 Cont ID  
Sent By ccole Date 2016-10-20 Time 14:13 Rev Time 0.00
Received By ccole Date 2016-10-17 Time 15:04 Sent To  
Notes
2016-10-18 15:04:24RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-14 Cont ID  
Sent By ccole Date 2016-10-14 Time 07:58 Rev Time 0.00
Received By ccole Date 2016-10-12 Time 14:09 Sent To  
Notes
2016-10-13 14:10:04RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-11 Cont ID  
Sent By gjohnson Date 2016-10-11 Time 11:04 Rev Time 0.00
Received By gjohnson Date 2016-09-09 Time 15:08 Sent To  
Notes
2016-09-09 15:08:50C23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-01 Cont ID  
Sent By lmarchan Date 2016-09-01 Time 14:18 Rev Time 0.00
Received By lmarchan Date 2016-05-27 Time 08:47 Sent To  
Notes
2016-05-31 08:47:44C23

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-10-20 Cont ID  
Sent By ccole Date 2016-10-20 Time 14:13 Rev Time 0.00
Received By ccole Date 2016-10-20 Time 14:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-10-14 Cont ID  
Sent By ccole Date 2016-10-14 Time 07:57 Rev Time 0.00
Received By ccole Date 2016-10-14 Time 07:57 Sent To  
Notes
2016-10-17 10:13:573RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16051222
 10/14/16
  
 1) THE RESUBMITTED SHEET P-06-02 THAT WAS MISSING IS AN
 OUTDATED 8/4/16 VERSION OF THE SHEET. THE REVISED
 APPROVED SHEET HAS A 9/7/16 DATE ON IT.
  
 2) AS PREVIOUSLLY REQUESTED, PLEASE DO NOT SUBMIT LOOSE
 PLANS SHEETS- ATTACH THEM INTO THE PLAN SETS- SECTION
 107 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-20 Cont ID  
Sent By ccole Date 2016-09-20 Time 11:15 Rev Time 0.00
Received By ccole Date 2016-09-20 Time 11:15 Sent To  
Notes
2016-09-20 11:26:512ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16051222
 9/20/16
  
 1) SUBMIT A DUPLICATE COPY OF THE UPDATED P-06-02 PLAN
 SHEET- ONLY ONE NEW SHEET WAS SUBMITTED. PLEASE
 PERMANENTLY ATTACH THE REPLACED SHEETS INTO THE PLAN
 SETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-03 Cont ID  
Sent By ccole Date 2016-06-03 Time 14:11 Rev Time 0.00
Received By ccole Date 2016-06-03 Time 14:11 Sent To ENG
Notes
2016-06-03 14:18:121ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 16051222
 6/3/16
  
 1) CLARIFY HOW THE AC SYSTEM WAS SIZED- PROVIDE
 CALCULATIONS.
  
 2 PLEASE REFER TO SECTION 414.1.3 FBC-14 BUILDING AND
 SUBMIT THE REQUIRED REPORT FOR THE SODIUM HYPOCHLORITE
 AND ALL OTHER CHEMICALS TO BE STORED ON USED FOR
 PROCESSING IN THE BUILDING. PLEASE NOTE THAT A
 HAZARDOUS EXHAUST VENTILATION SYSTEM MAY BE REQUIRED-
 SEE SECTION 510 FBC-14 MECHANICAL FOR CODE
 REQUIREMENTS.
  
 3) PROVIDE SUBMITTALS FOR THE SODIUM HYPOCHLORITE TANK,
 AND THE PROCESS PIPING, VALVES, AND FITTINGS WITH SHOP
 DRAWING APPROVAL SIGNATURES FROM THE DESIGN
 PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2016-10-11 Cont ID  
Sent By gjohnson Date 2016-10-11 Time 11:04 Rev Time 0.00
Received By gjohnson Date 2016-10-11 Time 09:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2016-07-06 Cont ID  
Sent By tklarge Date 2016-07-06 Time 06:19 Rev Time 0.00
Received By tklarge Date 2016-06-30 Time 08:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-09-22 Cont ID  
Sent By jroach Date 2016-09-22 Time 09:56 Rev Time 0.00
Received By jroach Date 2016-09-21 Time 15:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-22 Cont ID  
Sent By jroach Date 2016-06-22 Time 09:12 Rev Time 0.00
Received By jroach Date 2016-06-22 Time 09:12 Sent To L
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved