Plan Review Details - Permit 16050912
Plan Review Stops For Permit 16050912
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-03-04 Cont ID  
Sent By jwitmer Date 2017-03-04 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2017-03-04 Time 07:30 Sent To  
Notes
2017-03-04 08:23:45BUILDING PLAN REVIEW
 NORTON MUSEUM
 W. P. B. PERMIT: 16050912 BUILDING PERMIT
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: 561-236-7052
 E-MAIL: [email protected] MICHAEL IZZO
 E-MAIL: [email protected] MICHAEL J BEAUMIER
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: SAT. 04/ 2017
 ACTION: APPROVED / BUILDING PROVISO
  
 NOTICE: ROBERT BROWN HAS WRITTEN A LETTER OF APPROVAL
 FOR ALTERNATE MATERIALS AND DESIGN. E-MAIL MAY 04/2015
 AND DESIGN MEETING FROM TUES. JUNE 09/2015 WOULD
 REQUIRE ALTERNATE MATERIALS AND DESIGN METHODS,
 (PROPOSED COMPLIANCE METHOD), ERIC H. COTE SENIOR
 TECHNICAL ADVISOR.
  
 **THE TYPE IB CONSTRUCTION CLASSIFICATION IS BASED ON
 THE TOTAL COMBINED HEIGHT AND AREA OF ALL
 EXISTING-TO-REMAIN BUILDING PORTIONS+ PROPOSED
 ADDITIONS, INCLUDING PLANNED FUTURE ADDITIONS.
 ** THE MATERIALS OF CONSTRUCTION AND ASSOCIATED FIRE
 RESISTANCE RATINGS OF THE EXISTING TO REMAIN BUILDING
 PORTIONS WILL REMAIN UNCHANGED (I.E., PREDOMINATELY
 TYPE IIA, PROTECTED NONCOMBUSTIBLE CONSTRUCTION, OR
 BETTER, EXCEPT FOR EXISTING ROOF CONSTRUCTION IN THE
 CIRCA 1940-1942 PORTIONS).
 ** THE NEW AND EXISTING-TO-REMAIN BUILDING PORTIONS
 WILL FUNCTION AS A SINGLE BUILDING IN ALL RESPECTS.
  
  
 1) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. WITHIN THE STILLER
 AUDITORIUM THERE IS A PLATFORM LIFT TO GAIN ACCESS TO
 THE LOWER VIEWING AREA. COMPLIANCE FOR THE FLORIDA 2014
 ACCESSIBILITY CODE FOR VERTICAL ACCESSIBILITY IS BEING
 ACHIEVED BY THE PLATFORM LIFT, ACCESS CODE 207.1 AND AS
 PART OF A MEANS OF EGRESS IT ALSO HAS TO COMPLY WITH
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000
 EDITION AND THE 2001 SUPPLEMENT OR SECTION 1007 OF THE
 IBC-B 2003 EDITION. IN THE 2003 IBC-B 1007.5. PLATFORM
 LIFTS (WHEEL CHAIR) SHALL NOT SERVE AS PART OF AN
 ACCESSIBLE MEANS OF EGRESS, EXCEPT WHERE ALLOWED AS
 PART OF A REQUIRED ACCESSIBLE ROUTE IN SECTION 1109.7.
 PLATFORM
 LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE
 INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER
 SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO
 SERVE AS A PART OF A MEANS OF EGRESS.
  
 2) PROVISO: 2014FBC-ACCESSIBLITY CODE 703.4.1 HEIGHT
 ABOVE FINISH FLOOR OR GROUND. TACTILE CHARACTERS ON
 SIGNS SHALL BE LOCATED 48 INCHES (1220 MM) MINIMUM
 ABOVE THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM
 THE BASELINE OF THE LOWEST TACTILE CHARACTER AND 60
 INCHES (1525 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 HIGHEST TACTILE CHARACTER.
  
 3) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... 2014
 FBC-ACCESSIBILITY CODE THE USE OF PLATFORM LIFTS IS
 VERY LIMITED IN THEIR USE IN NEW CONSTRUCTION. PLEASE
 REVIEW THE 2014 FBC-ACCESS. CODE 206.7(1-10).
  
 4) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... SHEET
 0157_A420 DETAIL # 2 INDICATES THE USE OF FULLY ADHERED
 PVC ROOFING TO 5/8 INCH THERMAL BARRIER THEN METAL
 DECKING. PLEASE IDENTIFY THE 5/8 INCH THERMAL BARRIER
 COMPONENT, SHOW COMPLIANCE WITH FBC-B 603.
  
 5) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHOP DRAWINGS ARE TO BE SUBMITTED FOR THE TYPE OF WALL
 AND CEILING SHEATHING/ PANELING AND OR FOAM AND OR
 FABRIC FINISHES. THERE MAY BE USE OF A FOAM PANEL THE
 PLANS ARE NOT CLEAR, BUT THERE IS FABRIC PANELS AS
 SPECIFIED. PLEASE PROVIDE COMPLIANCE WITH FBC-B
 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS
 ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR
 NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR
 CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED
 IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN
 ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2 SHALL BE
 USED.
  
 6) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN
 EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS
 WOULD BE COVERED UNDER THE BUILDING PERMIT.
  
 7) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE ALSO
 WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME DETAIL
 SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL
 & PLUMBING DISCIPLES.
  
 8) COMPLIED. PRESSURES : SHEETS S008, S009, & S010.
  
 9) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
  
 10) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
  
 11) PROVISO: ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL
 IN RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 12) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 IF SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A
 FLORIDA ARCHITECT OR ENGINEER.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 13) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 14) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED
 WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET
 (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.
  
 15) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT
 SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT
 ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT
 ON THE MECHANICAL EQUIPMENT SCREEN.
  
 16) PROVISO: TYPE IB & IIA BUILDING REQUIRE FIRE
 RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601
 OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS
 SECTION OF THE CODE. FIRE PROTECTION SHOP DRAWING ARE
 TO BE PREPARED TO MEET TABLE 6501 OF THE 2014 FBC-B BY
 G. C. AND SUBMITTED TO THE DESIGNER OF RECORD FOR
 REVIEW AND APPROVAL BEFORE BEING SUBMITTED TO THE
 BUILDING DEPARTMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-01-23 Cont ID  
Sent By jwitmer Date 2017-01-23 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2017-01-09 Time 08:49 Sent To  
Notes
2017-01-23 13:57:50BUILDING PLAN REVIEW
 NORTON MUSEUM
 W. P. B. PERMIT: 16050912 BUILDING PERMIT
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: 561-236-7052
 E-MAIL: [email protected] MICHAEL IZZO
 E-MAIL: [email protected] MICHAEL J BEAUMIER
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JAN. 23/ 2017
 ACTION: DENIED
  
 NOTICE: ROBERT BROWN HAS WRITTEN A LETTER OF APPROVAL
 FOR ALTERNATE MATERIALS AND DESIGN. E-MAIL MAY 04/2015
 AND DESIGN MEETING FROM TUES. JUNE 09/2015 WOULD
 REQUIRE ALTERNATE MATERIALS AND DESIGN METHODS,
 (PROPOSED COMPLIANCE METHOD), ERIC H. COTE SENIOR
 TECHNICAL ADVISOR.
  
 1) COMPLIED.
  
 2) COMPLIED UNDER THE STRUCTURAL ONLY PERMIT 16080215,
 GEOTECHNICAL REPORT COMPLETED BY ARDAMAN 12/16/2014.
  
 4A-H) COMPLIED.
  
 4I) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. WITHIN THE STILLER
 AUDITORIUM THERE IS A PLATFORM LIFT TO GAIN ACCESS TO
 THE LOWER VIEWING AREA. COMPLIANCE FOR THE FLORIDA 2014
 ACCESSIBILITY CODE FOR VERTICAL ACCESSIBILITY IS BEING
 ACHIEVED BY THE PLATFORM LIFT, ACCESS CODE 207.1 AND AS
 PART OF A MEANS OF EGRESS IT ALSO HAS TO COMPLY WITH
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000
 EDITION AND THE 2001 SUPPLEMENT OR SECTION 1007 OF THE
 IBC-B 2003 EDITION. IN THE 2003 IBC-B 1007.5. PLATFORM
 LIFTS (WHEEL CHAIR) SHALL NOT SERVE AS PART OF AN
 ACCESSIBLE MEANS OF EGRESS, EXCEPT WHERE ALLOWED AS
 PART OF A REQUIRED ACCESSIBLE ROUTE IN SECTION 1109.7.
 PLATFORM
 LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE
 INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER
 SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO
 SERVE AS A PART OF A MEANS OF EGRESS.
  
 4J) PROVISO: 2014FBC-ACCESSIBLITY CODE 703.4.1 HEIGHT
 ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
  
  
  
  
 5A) COMPLIED.
  
 5B) 3RD REQUEST. TO CONSIDER THE EXIT PASSAGE WAY
 INDICATED AS CORRIDOR 101M TO BE AN EXTENSION OF THE
 VERTICAL EXIT, THERE WILL NEED TO HAVE A CUT SECTION
 THROUGH THE EXIT ACCESS CORRIDOR (EXIT PASSAGEWAY) EAST
 WEST THAT SHOWS THE FLOOR/ CEILING ASSEMBLIES BELOW AND
 ABOVE WITH THE RATING OF NOT ONLY THE HORIZONTAL
 ASSEMBLIES BUT OF THE VERTICAL SUPPORTING FRAMING. EXIT
 PASSAGEWAYS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711 OR BOTH. SINCE THERE IS
 ROOMS EITHER BELOW OR ABOVE THE EXIT PASSAGEWAY WILL
 NEED TO HAVE THE SAME RATING AS THE VERTICAL EXIT. THIS
 IS NOT CONSIDERED AN EXTENSION TO A STAIRWAY (EXIT
 PASSAGEWAY) IN SECTION 1022.3.1 A FIRE DOOR ASSEMBLY
 COMPLYING WITH SECTION 716.5 SHALL BE INSTALLED IN THE
 FIRE BARRIER TO PROVIDE A MEANS OF EGRESS FROM THE
 INTERIOR EXIT STAIRWAY TO THE EXIT PASSAGEWAY. THE DOOR
 PROTECTS THE VERTICAL EXIT FROM SMOKE AND FIRE. THIS
 REQUEST IS NOT ONLY FROM THE PLAN REVIEWER BUT ALSO THE
 BUILDING OFFICIAL ROBERT BROWN.
  
 2ND ROUND OF COMMENTS. RESPONSE INDICATES THE ENCLOSURE
 THAT CONNECTS THE OCCUPIED SPACE TO THE VERTICAL EXIT
 ENCLOSURE IS 2 HOUR RATED. IS THIS 2 HOUR RATING RATHER
 THAN HAVE A DOOR SEPARATING THE VERTICAL EXIT FROM THIS
 SPACE, ARE YOU LOOKING THIS IS ALTERNATE MATERIALS AND
 DESIGN METHODS? IF SO YOU WOULD NEED TO REQUEST SO IN
 WRITTEN FORM TO THE BUILDING OFFICIAL. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 104.11
 ALTERNATE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION.
  
 1ST ROUND OF COMMENTS. ON SHEET 0013_LS101M THERE IS A
 VERTICAL EXIT STAIR # 5 AND ADJACENT TO THE STAIR
 CORRIDOR 101M. THERE IS NO EXIT DOOR SEPARATING THE
 VERTICAL EXIT FROM EITHER AN EXIT ACCESS CORRIDOR OR AN
 EXIT PASSAGE WAY. HIS USE APPEARS TO BE AN EXIT ACCESS
 CORRIDOR MISSING THE DOOR TO THE VERTICAL EXIT.
 2014 FBC-B 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND
 RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH
 THE REQUIREMENTS OF SECTION 716. SEE TABLE 716.5.
 OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER
 THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO
 THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM
 NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE
 ENCLOSURE.
  
 6A) COMPLIED. 6B) EXISTING CONDITION.
  
 6C-G) COMPLIED.
  
 6H) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... 2014
 FBC-ACCESSIBILITY CODE THE USE OF PLATFORM LIFTS IS
 VERY LIMITED IN THEIR USE IN NEW CONSTRUCTION. PLEASE
 REVIEW THE 2014 FBC-ACCESS. CODE 206.7(1-10).
  
 6I-6J) COMPLIED.
  
 7) COMPLIED.
 8A) 2ND REQUEST. PLEASE CLARIFY IN THE F P DRAWINGS,
 WHICH SHEET COMPLIANCE CAN BE FOUND. SHEET 0171_A510
 DETAIL DOES PROVIDE A DETAIL FOR THE DRAFT CURTAIN BUT
 AGAIN THERE IS NO MENTION OF CLOSELY SPACED SPRINKLERS
 IN ACCORDANCE WITH NFPA 13.
  
 9) COMPLIED.
  
 10) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... SHEET
 0157_A420 DETAIL # 2 INDICATES THE USE OF FULLY ADHERED
 PVC ROOFING TO 5/8 INCH THERMAL BARRIER THEN METAL
 DECKING. PLEASE IDENTIFY THE 5/8 INCH THERMAL BARRIER
 COMPONENT, SHOW COMPLIANCE WITH FBC-B 603.
  
 11&12, A-C) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO
 BE SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHOP DRAWINGS ARE TO BE SUBMITTED FOR THE TYPE OF WALL
 AND CEILING SHEATHING/ PANELING AND OR FOAM AND OR
 FABRIC FINISHES. THERE MAY BE USE OF A FOAM PANEL THE
 PLANS ARE NOT CLEAR, BUT THERE IS FABRIC PANELS AS
 SPECIFIED. PLEASE PROVIDE COMPLIANCE WITH FBC-B
 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS
 ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR
 NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR
 CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED
 IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN
 ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE
 USED.
  
 13 & 14) COMPLIED.
  
 15) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN
 EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS
 WOULD BE COVERED UNDER THE BUILDING PERMIT.
  
 16) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE ALSO
 WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME DETAIL
 SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL
 & PLUMBING DISCIPLES.
  
 17) COMPLIED. PRESSURES : SHEETS S008, S009, & S010.
  
 18) COMPLIED SEE STRUCTURAL PERMIT: 16080215.
  
 19) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 19) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
  
 20) PROVISO: ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL
 IN RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 21) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 IF SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A
 FLORIDA ARCHITECT OR ENGINEER.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 22) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 23) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED
 WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET
 (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.
  
 24) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT
 SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT
 ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT
 ON THE MECHANICAL EQUIPMENT SCREEN.
  
 25) 2ND REQUEST TYPE IB & IIA BUILDING REQUIRE FIRE
 RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601
 OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS
 SECTION OF THE CODE. CLARIFICATION. PLEASE PROVIDE HOW
 CODE COMPLIANCE WILL BE ACHIEVED, USING WHAT METHODS
 AND MATERIALS. A SPECIFICATION IS JUST THAT, PLEAS
 PROVIDE THE DOCUMENTS HOW THE FIRE RATING OF STRUCTURAL
 MEMBERS WILL BE ACHIEVED.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 NEW COMMENT. TYPE IB & IIA BUILDING REQUIRE FIRE
 RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601
 OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS
 SECTION OF THE CODE. THANK YOU.
  
 26 ) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-29 Cont ID  
Sent By jwitmer Date 2016-10-29 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2016-10-28 Time 11:11 Sent To  
Notes
2016-10-29 10:24:36BUILDING PLAN REVIEW
 NORTON MUSEUM
 W. P. B. PERMIT: 16050912 BUILDING PERMIT
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: 561-236-7052
 E-MAIL: [email protected] MICHAEL IZZO
 E-MAIL: [email protected] MICHAEL J BEAUMIER
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. 29/ 2016
 ACTION: DENIED
  
 NOTICE: ROBERT BROWN IS SUPPOSE TO WRITE A LETTER OF
 APPROVAL FOR ALTERNATE MATERIALS AND DESIGN.
  
 1) COMPLIED.
  
 2) 2ND REQUEST, NOT COMPLETED UNDER THE FOUNDATION/
 STRUCTURE ONLY PERMIT. SHEET 0277_S003 HEADING
 FOUNDATIONS INDICATES THERE WAS A GEOTECHNICAL REPORT
 COMPLETED BY ARDAMAN 12/16/2014. PLEASE SUBMIT REPORT.
 NOTE WHEN SUBMITTED ELECTRONICALLY THE SOILS ENGINEER
 WILL NEED TO SUBMIT UNDER AN ELECTRONIC SEAL PER
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS (ELECTRONIC SEALS).
 OTHERWISE ONE PAPER ORIGINAL SIGNED AND SEALED DOCUMENT
 WILL BE RETAINED AND SCANNED INTO THE SYSTEM.
 PLEASE NOTE THE RESPONSE UNDER THE STRUCTURE ONLY
 PERMIT WAS THAT A PAPER COPY WAS ALREADY SUBMITTED TO
 THE BUILDING DEPARTMENT. I?VE CHECKED WITH THE
 ELECTRONIC PLAN REVIEW LIBRARIAN ON THE INCOMING
 APPLICATION AND ASSORTED PAPERWORK, THERE IS NO PAPER A
 GEOTECHNICAL REPORT COMPLETED BY ARDAMAN 12/16/2014
 WITHIN THE PAPERWORK, THE LIBRARIAN RECORDS SUCH PAPER
 DOCUMENTS SO I KNOW TO VERIFY THE REPORT IN PAPER IS
 THE SAME REPORT SUBMITTED ELECTRONICALLY AND VERIFY
 SIGNATURE ON THE PAPER DOCUMENT.
  
 4A-H) COMPLIED.
  
 4I) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. WITHIN THE STILLER
 AUDITORIUM THERE IS A PLATFORM LIFT TO GAIN ACCESS TO
 THE LOWER VIEWING AREA. COMPLIANCE FOR THE FLORIDA 2014
 ACCESSIBILITY CODE FOR VERTICAL ACCESSIBILITY IS BEING
 ACHIEVED BY THE PLATFORM LIFT, ACCESS CODE 207.1 AND AS
 PART OF A MEANS OF EGRESS IT ALSO HAS TO COMPLY WITH
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000
 EDITION AND THE 2001 SUPPLEMENT OR SECTION 1007 OF THE
 IBC-B 2003 EDITION. IN THE 2003 IBC-B 1007.5. PLATFORM
 LIFTS (WHEEL CHAIR) SHALL NOT SERVE AS PART OF AN
 ACCESSIBLE MEANS OF EGRESS, EXCEPT WHERE ALLOWED AS
 PART OF A REQUIRED ACCESSIBLE ROUTE IN SECTION 1109.7.
 PLATFORM
 LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE
 INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER
 SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO
 SERVE AS A PART OF A MEANS OF EGRESS.
  
 4J) 2ND REQUEST. THE ISSUE IS WITH EXITING, AND AN
 ACCESSIBLE EXIT, NOT JUST FOR THIS ROOM BUT EXITS FOR
 THE WHOLE OF THE BUILDING. THE DRAWING INDEX INDICATES
 SHEET 0260.03_A933_SIGNAGE DETAILS . THE ARE NO DETAILS
 FOR ACCESSIBLE SIGNAGE AND FOR DOORS THAT ARE NOT PART
 OF AN ACCESSIBLE ROUTE. THE HEIGHT OF SIGNAGE THAT HAS
 TACTILE CHARACTERS WITH BRAILLE,2014 FBC-ACCESSIBILITY
 CODE 703.4.1.
 703.1 SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL
 AND TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN
 WITH BOTH VISUAL AND TACTILE CHARACTERS, OR TWO
 SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
 CHARACTERS, SHALL BE PROVIDED.
 2014 FBC-B 1011.4 RAISED CHARACTER AND BRAILLE EXIT
 SIGNS. A SIGN STATING EXIT IN RAISED CHARACTERS AND
 BRAILLE AND COMPLYING WITH ICC A117.1 SHALL BE PROVIDED
 ADJACENT TO EACH DOOR TO AN AREA OF REFUGE, AN EXTERIOR
 AREA FOR ASSISTED RESCUE, AN EXIT STAIRWAY, AN EXIT
 RAMP, AN EXIT PASSAGEWAY AND THE EXIT DISCHARGE.
  
 1ST ROUND COMMENTS. THE SOME OF THE EXITS DO NOT
 INDICATE IF THEY ARE ACCESSIBLE EGRESS DOORWAYS
 COMPLYING WITH 2014 FBC-ACCESSIBILITY CODE 207.1
 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH THE 2003
 IBC SECTION 1007. 2003 IBC-B 1007.1. WHERE 2 OR MORE
 MEANS OF EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1
 FROM ANY ACCESSIBLE PORTION OF THE SPACE SHALL BE
 SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS OF EGRESS.
 THE LIFE SAFETY PLAN IS VAGUE AT BEST. 1027.5 ACCESS TO
 A PUBLIC WAY. THE EXIT DISCHARGE SHALL PROVIDE A DIRECT
 AND UNOBSTRUCTED ACCESS TO A PUBLIC WAY.
  
 5A) COMPLIED.
  
 5B) 2ND REQUEST. RESPONSE INDICATES THE ENCLOSURE THAT
 CONNECTS THE OCCUPIED SPACE TO THE VERTICAL EXIT
 ENCLOSURE IS 2 HOUR RATED. IS THIS 2 HOUR RATING RATHER
 THAN HAVE A DOOR SEPARATING THE VERTICAL EXIT FROM THIS
 SPACE, ARE YOU LOOKING THIS IS ALTERNATE MATERIALS AND
 DESIGN METHODS? IF SO YOU WOULD NEED TO REQUEST SO IN
 WRITTEN FORM TO THE BUILDING OFFICIAL. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 104.11
 ALTERNATE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION.
  
 1ST ROUND OF COMMENTS. ON SHEET 0013_LS101M THERE IS A
 VERTICAL EXIT STAIR # 5 AND ADJACENT TO THE STAIR
 CORRIDOR 101M. THERE IS NO EXIT DOOR SEPARATING THE
 VERTICAL EXIT FROM EITHER AN EXIT ACCESS CORRIDOR OR AN
 EXIT PASSAGE WAY. HIS USE APPEARS TO BE AN EXIT ACCESS
 CORRIDOR MISSING THE DOOR TO THE VERTICAL EXIT.
 2014 FBC-B 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND
 RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH
 THE REQUIREMENTS OF SECTION 716. SEE TABLE 716.5.
 OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER
 THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO
 THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM
 NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE
 ENCLOSURE.
  
 6A) COMPLIED. 6B) EXISTING CONDITION.
  
 6C-G) COMPLIED.
  
 6H) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... 2014
 FBC-ACCESSIBILITY CODE THE USE OF PLATFORM LIFTS IS
 VERY LIMITED IN THEIR USE IN NEW CONSTRUCTION. PLEASE
 REVIEW THE 2014 FBC-ACCESS. CODE 206.7(1-10).
  
 6I-6J) COMPLIED.
  
 7) COMPLIED.
 8A) 2ND REQUEST. PLEASE CLARIFY IN THE F P DRAWINGS,
 WHICH SHEET COMPLIANCE CAN BE FOUND. SHEET 0171_A510
 DETAIL DOES PROVIDE A DETAIL FOR THE DRAFT CURTAIN BUT
 AGAIN THERE IS NO MENTION OF CLOSELY SPACED SPRINKLERS
 IN ACCORDANCE WITH NFPA 13.
  
 9) COMPLIED.
  
 10) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... SHEET
 0157_A420 DETAIL # 2 INDICATES THE USE OF FULLY ADHERED
 PVC ROOFING TO 5/8 INCH THERMAL BARRIER THEN METAL
 DECKING. PLEASE IDENTIFY THE 5/8 INCH THERMAL BARRIER
 COMPONENT, SHOW COMPLIANCE WITH FBC-B 603.
  
 11&12, A-C) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO
 BE SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHOP DRAWINGS ARE TO BE SUBMITTED FOR THE TYPE OF WALL
 AND CEILING SHEATHING/ PANELING AND OR FOAM AND OR
 FABRIC FINISHES. THERE MAY BE USE OF A FOAM PANEL THE
 PLANS ARE NOT CLEAR, BUT THERE IS FABRIC PANELS AS
 SPECIFIED. PLEASE PROVIDE COMPLIANCE WITH FBC-B
 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS
 ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR
 NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR
 CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED
 IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN
 ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE
 USED.
  
 13 & 14) COMPLIED.
  
 15) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN
 EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS
 WOULD BE COVERED UNDER THE BUILDING PERMIT.
  
 16) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE ALSO
 WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME DETAIL
 SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL
 & PLUMBING DISCIPLES.
  
 17) SEMI-COMPLIED. THE SHEETS S008, S009, & S010 ALL
 SHOW THE PRESSURES FROM THE WIND STUDY FOR ROOF ZONES
 1, 2 & 3. THESE 3 SHEETS LISTED ABOVE S008 IS THE ONLY
 SHEET WHICH SHOWS PRESSURES FOR ROOF ZONES 1, 2 & 3.
 THE ROOF ZONES DO NOT PROVIDE PRESSURES FOR ROOF TOP
 EQUIPMENT THAT WILL BE ANCHORED TO THE (MWFRS) MAIN
 WIND FORCE RESISTING SYSTEM.
 PLEASE PROVIDE THE PRESSURES FOR THE DOORS AND WINDOWS
 IN WALL ZONES 4 & 5. PLEASE PROVIDE THE PRESSURES FOR
 THE WINDOWS AND DOORS AS PER THE WIND STUDY THAT WAS
 COMPLETED. FBC-B 1609.1.1DETERMINATION OF WIND LOADS.
 EXCEPTION #6 WIND TUNNEL TESTING IN ACCORDANCE WITH
 CHAPTER 31 OF ASCE 7. PLEASE NOTE THIS MAY ALSO BE
 ACCOMPLISHED UNDER THE STRUCTURE ONLY PERMIT #
 16080215.
 18) 2ND REQUEST. IT SEEMS THE PLANS ARE INCOMPLETE
 PLEASE PROVIDE WHERE THE FOUNDATION SCHEDULE, CONCRETE
 COLUMN, HOOPS & VERTICAL REBAR AND BEAMS ARE LOCATED, I
 COULD NOT FIND THEM IN THE STRUCTURAL SHEETS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1.1. COMMERCIAL BUILDINGS/ BUILDING:
 FOUNDATION SCHEDULE
 COLUMN SCHEDULE
 BEAM ( CONCRETE/ LINTEL) SCHEDULE
  
 19) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 19) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
  
 20) PROVISO: ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL
 IN RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 21) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 IF SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A
 FLORIDA ARCHITECT OR ENGINEER.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 22) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 23) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED
 WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET
 (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.
  
 24) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT
 SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT
 ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT
 ON THE MECHANICAL EQUIPMENT SCREEN.
  
 25) NEW COMMENT. TYPE IB & IIA BUILDING REQUIRE FIRE
 RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601
 OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS
 SECTION OF THE CODE. THANK YOU.
  
 26 ) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By   Date 2016-07-11 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2016-07-07 Time 10:30 Sent To  
Notes
2016-07-11 07:43:15BUILDING PLAN REVIEW
 NORTON MUSEUM
 W. P. B. PERMIT: 16050912
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: 561-236-7052
 E-MAIL: [email protected] MICHAEL IZZO
 [email protected] MICHAEL J BEAUMIER
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JULY 09/ 2016
 ACTION: DENIED
  
 1) PLEASE BE AWARE THIS SCOPE OF WORK REQUIRES A
 THRESHOLD INSPECTOR, SEE F.S. THRESHOLD BUILDING FL S.
 S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 THE THRESHOLD INSPECTION FORMS WERE SENT TO:
 [email protected] MICHAEL IZZO 07/09/2016 7:24 AM
 [email protected] MICHAEL J BEAUMIER 07/09/2016
 7:37 AM
  
 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 2) SHEET 0277_S003 HEADING FOUNDATIONS INDICATES THERE
 WAS A GEOTECHNICAL REPORT COMPLETED BY ARDAMAN
 12/16/2014. PLEASE SUBMIT REPORT. NOTE WHEN SUBMITTED
 ELECTRONICALLY THE SOILS ENGINEER WILL NEED TO SUBMIT
 UNDER AN ELECTRONIC SEAL PER 61G15-23.005 PROCEDURES
 FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 (ELECTRONIC SEALS).
 OTHERWISE ONE PAPER ORIGINAL SIGNED AND SEALED DOCUMENT
 WILL BE RETAINED AND SCANNED INTO THE SYSTEM.
  
 3) UNDER SHEET 0008_A0004 THE PHASING PLAN THE PLANS
 SHOW EXISTING AND THE EXPANSION PLAN. PLEASE PROVIDE
 THE EXISTING TOTAL SQUARE FOOTAGE OF THE BUILDING AND
 THE TOTAL SQUARE FOOTAGE OF THE BUILDING AT THE END OF
 THIS EXPANSION. THIS INFORMATION WILL BE REQUIRED BY
 PALM BEACH COUNTY IMPACT FEE OFFICE TO DETERMINE IF
 IMPACT FEES ARE DUE. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 4) SHEET 0012_ LS101 VERSES 0097_A101;
  
 4A) THE LIFE SAFETY PLAN SEEMS INCOMPLETE, IT APPEARS
 THERE ARE EXISTING AREAS OF THE MUSEUM AND PORTIONS
 THAT ARE GOING TO BE REMODELED THAT PROVIDE THE SQUARE
 FOOTAGE OF THE ROOM AND OCCUPANT LOADS BUT THERE IS NO
 ROOM NUMBER TO BE ABLE TO IDENTIFY THE ROOM.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 4B) THE LIFE SAFETY PLANS CHARTS SHOWING EXIT CAPACITY
 AND OCCUPANT LOADS BUT THE PLAN DOES NOT SHOW
 THE EGRESS PATH FOR 50 % OF THE BUILDING. WHERE THE
 ROOMS THAT DO SHOW WHAT AMOUNT OF OCCUPANTS THAT ARE
 EXITING A ROOM, THEY DO NOT GIVE AN ACCUMULATIVE
 OCCUPANT LOAD OF THE EXIT ACCESS CORRIDORS, TO THE
 EXIT. DOOR SWINGS CANNOT BE EVALUATED BECAUSE THE PATH
 OF TRAVEL AND OCCUPANT LOADS IS UNKNOWN. FBC-B 1005.2
 MINIMUM WIDTH BASED ON COMPONENT. THE MINIMUM WIDTH, IN
 INCHES (MM), OF ANY MEANS OF EGRESS COMPONENTS SHALL
 NOT BE LESS THAN THAT SPECIFIED FOR SUCH COMPONENT,
 ELSEWHERE IN THIS CODE.
  
 4C) ROOM 120 THE EMILY & LEONARD LAUDER RESTAURANT
 INDICATES 3511 SQ. FT. AND AN OCCUPANT LOAD OF 235 IN
 THE LS101 SHEET. WHEREAS IN THE OCCUPANT LOAD CHART
 THIS SAME ROOM SHOWS 3,736 SQ. FT. AND AN OCCUPANT LOAD
 OF250.EVEN IF YOU FIGURE THE PRIVATE DINING ROOM 121
 THE SQ. FOOTAGE TOTALS UP TO 4286 SQ. FT. THERE IS A
 DISCREPANCY IN THE OCCUPANT LOADS FOR BOTH OF THESE
 ROOMS. THE PRIVATE DINING ROOM OF 775 SQ. FT. /15= 52
 OCCUPANTS NOT 49. THERE IS A DISCREPANCY IN THE PLANS.
 SEE FBC-B TABLE 1004.1.2.
  
 4D) WITHIN THIS SAME AREA ROOMS 120 & 121 THE TOTAL
 OCCUPANT LOAD 235 + 52 = 287 OCCUPANTS. THE PLANS ONLY
 ACCOUNT FOR 167 OCCUPANTS OF THE 287 OCCUPANT LOAD,
 THERE ARE 120 OCCUPANTS NOT ACCOUNTED FOR. PLEASE ALSO
 NOTE IN THE PRIVATE DINING ROOM 121 LABELED 49
 OCCUPANTS WHICH SHOULD BE 775/15= 52 OCCUPANTS. THE
 PLAN SHOWS ALL EXITING THROUGH ONE DOORWAY. PLEASE
 REVIEW THE 2014 FBC-B TABLE 1015.1 THE MAXIMUM
 ALLOWABLE WITH ONE EXIT IS 49 FOR ASSEMBLY OCCUPANCY.
 IF THE OCCUPANCY WAS FIGURED ON THE 775 SQ. FT. AS A
 NET @ 15 FT./OCCUPANT THEN THE OCCUPANT LOAD IS 52
 REQUIRING 2 EXITS, NOT PROVIDED.
  
 4E) ROOM 118 THE RESTAURANT LOBBY AREA DOES NOT HAVE AN
 OCCUPANT LOAD FIGURED IN, THE PLANS DO NOT INDICATE IF
 THIS IS A PRE-FUNCTION AREA WHERE THERE WOULD POSSIBLY
 BE A QUEUING LINE WHERE AN AREA WOULD BE ROPED OFF WITH
 BOLLARDS, THE EGRESS PATH IS UNKNOWN IN THIS CASE? THE
 OTHER UNKNOWN IS ROOM 119 SALTMAN CORRIDOR WHERE ARE
 THESE OCCUPANTS EXITING. FBC-B 1028.4 THIS SECTION IS
 FOR A-1 ASSEMBLY BUT MAYBE A SIMILAR TYPE USE.
  
 4F) AREA OF CONCERN WITH STAIR #2 AND EXIT C. THE 1ST
 FLOOR PLAN SHOWS A OCCUPANT LOAD OF 135 BEING TAKEN
 FROM THE 2ND FLOOR WORST CASE SCENARIO FLOOR DOWN THIS
 STAIR. THE EXIT DOOR C IS MAXED OUT AT 340/ 340
 OCCUPANT LOAD. WHEN VIEWING ON SHEET 0014_LS 102 THE
 TOTAL OCCUPANT LOAD OF THE 2ND FLOOR OF 463 THERE IS
 ONLY 443 OCCUPANTS ACCOUNTED FOR IN THE (4) STAIR
 WELLS, STAIR 1 (136 OCC.), STAIR 2 (135) STAIR 4 (68)
 AND STAIR 5(104), 136 + 135 + 68 + 104= 443 OCCUPANTS/
 SHORT 20 OCCUPANTS IN THE STAIRWELLS!!!! ALTHOUGH
 STAIRWELL # 2 COULD ACCOMMODATE MORE OCCUPANTS THE
 LIMITING FACTOR IS AT EXIT DOOR C, IS FULL 340/ 340
 OCCUPANTS. SEE FBC-B 1005.3.2 AND ALSO THE EXCEPTION.
  
 4G) CLOAK ROOM NOR CLOSETS SHOW OCCUPANT LOADS. FBC-B
 TABLE 1004.1.2.
  
 4H) THE COMBINATION FOYERS/ VESTIBULE 110 & 145 SHOW AN
 OCCUPANT LOAD OF ONLY 9. THIS AREA MAY ALSO BE A
 QUEUING AREA FOR THE A1 THEATER OCCUPANCY. THE PLANS DO
 NOT INDICATE IF THIS IS TO BE A PRE-FUNCTION AREA WHERE
 THERE WOULD POSSIBLY BE A QUEUING LINE WHERE AN AREA
 WOULD BE ROPED OFF WITH BOLLARDS; THE EGRESS PATH IS
 UNKNOWN IN THIS CASE? FBC-B 1028.4 THIS SECTION IS FOR
 A-1 ASSEMBLY USAGE.
  
 4I) WITHIN THE STILLER AUDITORIUM THERE IS A PLATFORM
 LIFT TO GAIN ACCESS TO THE LOWER VIEWING AREA.
 COMPLIANCE FOR THE FLORIDA 2014 ACCESSIBILITY CODE FOR
 VERTICAL ACCESSIBILITY IS BEING ACHIEVED BY THE
 PLATFORM LIFT, ACCESS CODE 207.1 AND AS PART OF A MEANS
 OF EGRESS IT ALSO HAS TO COMPLY WITH 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE 2000 EDITION AND THE 2001
 SUPPLEMENT OR SECTION 1007 OF THE IBC-B 2003 EDITION.
 IN THE 2003 IBC-B 1007.5. PLATFORM LIFTS (WHEEL CHAIR)
 SHALL NOT SERVE AS PART OF AN ACCESSIBLE MEANS OF
 EGRESS, EXCEPT WHERE ALLOWED AS PART OF A REQUIRED
 ACCESSIBLE ROUTE IN SECTION 1109.7. PLATFORM
 LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE
 INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER
 SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO
 SERVE AS A PART OF A MEANS OF EGRESS.
  
 4J) THE SOME OF THE EXITS DO NOT INDICATE IF THEY ARE
 ACCESSIBLE EGRESS DOORWAYS COMPLYING WITH 2014
 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE MEANS OF EGRESS
 SHALL COMPLY WITH THE 2003 IBC SECTION 1007. 2003 IBC-B
 1007.1. WHERE 2 OR MORE MEANS OF EGRESS IS REQUIRED BY
 SECTION 1014.1 OR 1018.1 FROM ANY ACCESSIBLE PORTION OF
 THE SPACE SHALL BE SERVED BY NOT LESS THAN TWO
 ACCESSIBLE MEANS OF EGRESS. THE LIFE SAFETY PLAN IS
 VAGUE AT BEST. 1027.5 ACCESS TO A PUBLIC WAY. THE EXIT
 DISCHARGE SHALL PROVIDE A DIRECT AND UNOBSTRUCTED
 ACCESS TO A PUBLIC WAY.
  
 5) SHEET 0013_LS101M & 0098_A101M:
  
 5A) ON SHEET 0013_LS101M JUST TO THE RIGHT OF CORRIDOR
 101M THERE IS A SMALL ROOM AND DOOR. THERE IS ALSO A
 NOTE ON THE PLANS PLEASE CLARIFY ROOM AND DOOR
 ARRANGEMENT. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 5B) ON SHEET 0013_LS101M THERE IS A VERTICAL EXIT STAIR
 # 5 AND ADJACENT TO THE STAIR CORRIDOR 101M. THERE IS
 NO EXIT DOOR SEPARATING THE VERTICAL EXIT FROM EITHER
 AN EXIT ACCESS CORRIDOR OR AN EXIT PASSAGE WAY. HIS USE
 APPEARS TO BE AN EXIT ACCESS CORRIDOR MISSING THE DOOR
 TO THE VERTICAL EXIT.
 2014 FBC-B 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND
 RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH
 THE REQUIREMENTS OF SECTION 716. SEE TABLE 716.5.
 OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER
 THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO
 THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM
 NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE
 ENCLOSURE.
  
 6) SHEET 0014_LS102 & 0099_A102:
  
 6A) BETWEEN THE 2 SHEETS THERE IS A DISCREPANCY IN THE
 STAIR IDENTIFICATION NUMBER LS SHEET LIST STAIR AS
 STAIR # 01 WHEREAS 0099_A102 ON GRIDLINES X3 5.3X XF-3
 IDENTIFIES THE STAIR AS STAIR # 3 B217. DISCREPANCY IN
 PLANS. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6B) THE LOWER RIGHT CORNER OF THE PLAN STAIR LABEL BOTH
 1 & 3 HAVE (2) OTHER ROOMS WITHIN THE VERTICAL STAIR
 ENCLOSURE. ONE NOT LABELED THE OTHER B215 SECURITY
 CLOSET. PLEASE REVIEW THE 2014 FBC-B 1022.4 OPENINGS.
 INTERIOR EXIT STAIRWAY AND RAMP OPENING PROTECTIVES
 SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 716. OPENINGS IN INTERIOR EXIT STAIRWAYS OTHER THAN
 UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE
 NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM
 NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE
 ENCLOSURE. ELEVATORS SHALL NOT OPEN INTO INTERIOR EXIT
 STAIRWAYS AND RAMPS.
  
 6C) THE 2ND FLOOR IS OPEN TO THE 1ST FLOOR IN THE GRAND
 HALL AND ADMISSIONS. PLEASE PROVIDE A NORTH / SOUTH
 SECTION THROUGH THE CENTER OF THIS AREA. SHEET 0099 THE
 2ND FLOOR SHOWS WHAT APPEARS TO BE A 2 STORY ATRIUM.
 THE LIFE SAFETY PLAN 0014 THE 2ND FLOOR SHOWS A SMOKE
 PARTITION RATED WALL. THE SHEET 0015_LS 103 THE 3RD
 STORY SHOWS A SMOKE RATED PARTITION DOWN TO THE 2ND
 FLOOR. IF THIS IS A 3 STORY ATRIUM THEN COMPLIANCE WITH
 404.4 & 404.5.
  
 6D) 2014 FBC-B 404.4 FIRE ALARM SYSTEM. A FIRE ALARM
 SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 907.2.14.
  
 404.5 SMOKE CONTROL. A SMOKE CONTROL SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 909.
 EXCEPTION: SMOKE CONTROL IS NOT REQUIRED FOR ATRIUMS
 THAT CONNECT ONLY TWO STORIES.
  
 6E) THE OTHER ISSUE IS THE PLANS CALL OUT FOR THE
 PARTITIONS ON THE 2ND AND 3RD FLOORS TO BE SMOKE
 PARTITIONS.
 THE PLANS DO NOT INDICATE THERE WILL BE A SMOKE CONTROL
 SYSTEM FBC-B 404.6 EXCEPTION # 3 DIES STATE:
 A FIRE BARRIER IS NOT REQUIRED BETWEEN THE ATRIUM AND
 THE ADJOINING SPACES OF ANY THREE FLOORS OF THE ATRIUM
 PROVIDED SUCH SPACES ARE ACCOUNTED FOR IN THE DESIGN OF
 THE SMOKE CONTROL SYSTEM.
  
 6F) FOR THE ATRIUM SMOKE CONTROL SYSTEM WILL ALSO NEED
 TO COMPLY WITH: FBC-B 404.7 STANDBY POWER. EQUIPMENT
 REQUIRED TO PROVIDE SMOKE CONTROL SHALL BE CONNECTED TO
 A STANDBY POWER SYSTEM IN ACCORDANCE WITH SECTION
 909.11.
  
 6G) FBC-B 404.8 ATRIUM. INTERIOR FINISH. THE INTERIOR
 FINISH OF WALLS AND CEILINGS OF THE ATRIUM SHALL BE NOT
 LESS THAN CLASS B WITH NO REDUCTION IN CLASS FOR
 SPRINKLER PROTECTION.
  
 6H)(1) THE PLANS INDICATE THE USE OF A LULA ELEVATOR
 FROM CORRIDOR 216 TO THE LIBRARY 220. WITH IN THIS
 SPACE THERE IS A SET OF STAIRS. PLEASE IDENTIFY IF THIS
 IS NEW CONSTRUCTION OR MODIFICATIONS TO EXISTING
 CONSTRUCTION. WITHIN THE 2014 FBC-ACCESSIBILITY CODE
 THE USE OF PLATFORM LIFTS IS VERY LIMITED IN THEIR USE
 IN NEW CONSTRUCTION. PLEASE REVIEW THE 2014 FBC-ACCESS.
 CODE 206.7(1-10).
  
 6H)(2) IF ALLOWED AS PART OF A RENOVATION PROJECT THEN
 SHOW COMPLIANCE WITH: FLORIDA 2014 ACCESSIBILITY CODE
 FOR VERTICAL ACCESSIBILITY IS BEING ACHIEVED BY THE
 PLATFORM LIFT, ACCESS CODE 207.1 AND AS PART OF A MEANS
 OF EGRESS IT ALSO HAS TO COMPLY WITH 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE 2000 EDITION AND THE 2001
 SUPPLEMENT OR SECTION 1007 OF THE IBC-B 2003 EDITION.
 IN THE 2003 IBC-B 1007.5. PLATFORM LIFTS (WHEEL CHAIR)
 SHALL NOT SERVE AS PART OF AN ACCESSIBLE MEANS OF
 EGRESS, EXCEPT WHERE ALLOWED AS PART OF A REQUIRED
 ACCESSIBLE ROUTE IN SECTION 1109.7. PLATFORM LIFTS IN
 ACCORDANCE WITH SECTION 2702 SHALL BE INSTALLED IN
 ACCORDANCE WITH ASME A18.1. STANDBY POWER SHALL BE
 PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO SERVE AS A
 PART OF A MEANS OF EGRESS.
  
 6I) DISCREPANCY IN IDENTIFICATION OF STAIRS, SHEET
 0014_LS102 IDENTIFIES THE STAIR AS 05 WHERE AS SHEET
 0099_A102 IDENTIFIES THE SAME STAIR AS 1A. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 6J) WITHIN THE SAME STAIR IDENTIFIED ABOVE THE TOP
 LANDING THERE IS A DOOR NOT IDENTIFIED BUT DOES NOT
 HAVE THE 18 INCHES MANEUVERING CLEARANCES ON THE INSIDE
 OF THE DOOR. ACCESS. CODE 404.2.4.
  
 7) SHEET 0015_LS103 & 0100_A103:
  
 7A) AGAIN ON THE LIFE SAFETY SHEET IN THE LOWER RIGHT
 HAND CORNER THE STAIRWELL IS LABELED STAIR 1 & 3.
 DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 8) GRAND STAIR CASE, STAIR # 2 IS A OPEN STAIR AS
 ALLOWED BY FBC-B 1009.3 EXCEPTION # 4. SHEETS 0014 &
 0015 DUE INDICATE THE USE OF DRAFT STOP WITH FIRE
 SPRINKLERS, SHEET 0012 THE 1ST FLOOR THERE IS NO
 MENTION OF A DRAFT CURTAIN OR FIRE SPRINKLERS. PLEASE
 SHOW COMPLIANCE WITH FBC-B 1009.3 EXC. # 4.
  
 8A) SHEET 0171_A510 DETAIL DOES PROVIDE A DETAIL FOR
 THE DRAFT CURTAIN BUT AGAIN THERE IS NO MENTION OF
 CLOSELY SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13.
 8B) SHEET 0166_A503 GRAND STAIR SECTION DETAIL 1 DOES
 NOT EVEN SHOW A DRAFT CURTAIN ON THE 3RD FLOOR.
 SHOW COMPLIANCE WITH: FBC-B 1009.3 EXC. # 4. IN OTHER
 THAN GROUP B AND M OCCUPANCIES, EXIT ACCESS STAIRWAY
 OPENINGS ARE NOT REQUIRED TO BE ENCLOSED PROVIDED THAT
 THE BUILDING IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1,
 THE FLOOR OPENING DOES NOT CONNECT MORE THAN FOUR
 STORIES, THE AREA OF THE FLOOR OPENING BETWEEN STORIES
 DOES NOT EXCEED TWICE THE HORIZONTAL PROJECTED AREA OF
 THE EXIT ACCESS STAIRWAY, AND THE OPENING IS PROTECTED
 BY A DRAFT CURTAIN AND CLOSELY SPACED SPRINKLERS IN
 ACCORDANCE WITH NFPA 13.
  
 9) SHEET 0228_A806 DOOR SCHEDULE: DOOR C310A MISSING 90
 MIN. LABEL. FBC-B TABLE 716.5 OPENING PROTECTIVES.
  
 10) SHEET 0157_A420 DETAIL # 2 INDICATES THE USE OF
 FULLY ADHERED PVC ROOFING TO 5/8 INCH THERMAL BARRIER
 THEN METAL DECKING. PLEASE IDENTIFY THE 5/8 INCH
 THERMAL BARRIER COMPONENT, SHOW COMPLIANCE WITH FBC-B
 603.
  
 11)SHEET 0173_ A601 RFC & SHEET 0258_A921 AUDITORIUM
 CEILING DETAILS:
  
 11A) DETAILS THIS SHEET SHOW A DROPPED DOWN CEILING
 FRAMING SYSTEM. THESE DETAILS DO NOT INDICATE THE
 MATERIALS OF THE FRAMING IS MADE FROM SIZE NOR SPACING.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 11B) DETAILS THIS SHEET SHOW A DROPPED DOWN CEILING BUT
 NO REFERENCE TO THE THICKNESS OF THE CEILING BOARD,
 TYPE OF MATERIAL, ETC? 107.3.5.1.1. 11 INTERIOR
 FINISHES. 803.11.2 SET-OUT CONSTRUCTION.
  
 11C) THERE MAYBE USE OF A FOAM PANEL THE PLANS ARE NOT
 CLEAR, BUT THERE IS FABRIC PANELS AS SPECIFIED. PLEASE
 PROVIDE COMPLIANCE WITH FBC-B 803.11.2 SET-OUT
 CONSTRUCTION. WHERE WALLS AND CEILINGS ARE REQUIRED TO
 BE OF FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE
 CONSTRUCTION AND WALLS ARE SET OUT OR CEILINGS ARE
 DROPPED DISTANCES GREATER THAN SPECIFIED IN SECTION
 803.11.1, CLASS A FINISH MATERIALS, IN ACCORDANCE WITH
 SECTION 803.1.1 OR 803.1.2, SHALL BE USED.
  
 12) SHEET 0173_A601 AUDITORIUM WALLS & SHEET 0255_A918:
  
 12A) BUILT OUT WALL DETAILS AS BEFORE COMMENTS, DO NOT
 INDICATE THE FRAMING MATERIAL SIZE NOR SPACING OF THE
 FRAMING MEMBERS. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 12B) ) DETAILS THIS SHEET SHOW A BUILT OUT WALL DETAILS
 BUT NO REFERENCE TO THE THICKNESS OF THE WALL BOARD,
 TYPE OF MATERIAL, ETC? 107.3.5.1.1. 11 INTERIOR
 FINISHES. 803.11.2 SET-OUT CONSTRUCTION.
  
 12C) THERE MAYBE USE OF A FOAM PANEL THE PLANS ARE NOT
 CLEAR, BUT THERE IS FABRIC PANELS AS SPECIFIED. PLEASE
 PROVIDE COMPLIANCE WITH FBC-B 803.11.2 SET-OUT
 CONSTRUCTION. WHERE WALLS AND CEILINGS ARE REQUIRED TO
 BE OF FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE
 CONSTRUCTION AND WALLS ARE SET OUT OR CEILINGS ARE
 DROPPED DISTANCES GREATER THAN SPECIFIED IN SECTION
 803.11.1, CLASS A FINISH MATERIALS, IN ACCORDANCE WITH
 SECTION 803.1.1 OR 803.1.2, SHALL BE USED.
  
 13) SHEET 0260_A930 ALL DETAILS SHOW ELECTRICAL FLOOR
 BOXES LOCATED IN CONCRETE STRUCTURAL SLABS WITH WOOD
 STRINGER BUILT UP FLOORING HEIGHT NOT GIVEN, WITH 2
 LAYERS OF SUB-FLOORING NOT IDENTIFIED. SHOW COMPLIANCE
 WITH 2014 FBC-B SECTIONS:
  
 805.1 APPLICATION. COMBUSTIBLE MATERIALS INSTALLED ON
 OR EMBEDDED IN FLOORS OF BUILDINGS OF TYPE I OR II
 CONSTRUCTION SHALL COMPLY WITH SECTIONS 805.1.1 THROUGH
 805.1.3.
 EXCEPTION: STAGES AND PLATFORMS CONSTRUCTED IN
 ACCORDANCE WITH SECTIONS 410.3 AND 410.4, RESPECTIVELY.
  
 805.1.1 SUBFLOOR CONSTRUCTION. FLOOR SLEEPERS, BUCKS
 AND NAILING BLOCKS SHALL NOT BE CONSTRUCTED OF
 COMBUSTIBLE MATERIALS, UNLESS THE SPACE BETWEEN THE
 FIRE-RESISTANCE-RATED FLOOR ASSEMBLY AND THE FLOORING
 IS EITHER SOLIDLY FILLED WITH NONCOMBUSTIBLE MATERIALS
 OR FIREBLOCKED IN ACCORDANCE WITH SECTION 718, AND
 PROVIDED THAT SUCH OPEN SPACES SHALL NOT EXTEND UNDER
 OR THROUGH PERMANENT PARTITIONS OR WALLS.
  
 805.1.2 WOOD FINISH FLOORING. WOOD FINISH FLOORING IS
 PERMITTED TO BE ATTACHED DIRECTLY TO THE EMBEDDED OR
 FIREBLOCKED WOOD SLEEPERS AND SHALL BE PERMITTED WHERE
 CEMENTED DIRECTLY TO THE TOP SURFACE OF
 FIRE-RESISTANCE-RATED FLOOR ASSEMBLIES OR DIRECTLY TO A
 WOOD SUBFLOOR ATTACHED TO SLEEPERS AS PROVIDED FOR IN
 SECTION 805.1.1.
  
 14) SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN
 EXHAUST HOODS THAT VENT UP THROUGH THE ROOF USUALLY.
 NOTE NONE OF THE FLOOR SHEETS SHOW A RATED SHAFT GOING
 FROM FLOOR THROUGH TO THE ROOF. 2014 FBC-B 713.1
 GENERAL. THE PROVISIONS OF THIS SECTION SHALL APPLY TO
 SHAFTS REQUIRED TO PROTECT OPENINGS AND PENETRATIONS
 THROUGH FLOOR/CEILING AND ROOF/CEILING ASSEMBLIES.
 713.4 FIRE-RESISTANCE RATING. SHAFT ENCLOSURES SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS
 WHERE CONNECTING FOUR STORIES OR MORE, AND NOT LESS
 THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR STORIES.
 THE NUMBER OF STORIES CONNECTED BY THE SHAFT ENCLOSURE
 SHALL INCLUDE ANY BASEMENTS BUT NOT ANY MEZZANINES.
 SHAFT ENCLOSURES SHALL HAVE A FIRE RESISTANCE RATING
 NOT LESS THAN THE FLOOR ASSEMBLY PENETRATED, BUT NEED
 NOT EXCEED 2 HOURS. SHAFT ENCLOSURES SHALL MEET THE
 REQUIREMENTS OF SECTION 703.2.
 713.11 ENCLOSURE AT THE BOTTOM. SHAFTS THAT DO NOT
 EXTEND TO THE BOTTOM OF THE BUILDING OR STRUCTURE SHALL
 COMPLY WITH ONE OF THE FOLLOWING:
  
 15) SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN
 EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS
 WOULD BE COVERED UNDER THE BUILDING PERMIT.
  
 16) SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE
 ALSO WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME
 DETAIL SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL,
 ELECTRICAL & PLUMBING DISCIPLES.
  
 17) SHEET S003 PROVIDES THE WIND DESIGN CRITERIA,
 PLEASE PROVIDE THE MEAN ROOF HEIGHT FOR THE BUILDING
 AND ASSOCIATED PRESSURES FOR ALL ROOF ZONES 1,2,& 3 AND
 WALL ZONES 4 & 5. 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 (5) . DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. TABLE
 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & EXPOSURE.
 PROVIDE THE MEAN ROOF HEIGHT FOR THE BUILDING.
  
 18) IT SEEMS THE PLANS ARE INCOMPLETE PLEASE PROVIDE
 WHERE THE FOUNDATION SCHEDULE, CONCRETE COLUMN, HOOPS &
 VERTICAL REBAR AND BEAMS ARE LOCATED, I COULD NOT FIND
 THEM IN THE STRUCTURAL SHEETS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1.1. COMMERCIAL BUILDINGS/ BUILDING:
 FOUNDATION SCHEDULE
 COLUMN SCHEDULE
 BEAM ( CONCRETE/ LINTEL) SCHEDULE
  
 19) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
  
 20) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 21) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. IF SO RAS 117 CALCULATIONS ARE REQUIRED BY
 EITHER A FLORIDA ARCHITECT OR ENGINEER.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 22) 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 23) FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED
 WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET
 (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.
  
 24) FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL
 EQUIPMENT SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN
 HEIGHT ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST
 POINT ON THE MECHANICAL EQUIPMENT SCREEN.
  
 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-06 Cont ID  
Sent By vperez Date 2017-01-06 Time 10:46 Rev Time 0.00
Received By vperez Date 2017-01-05 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-12 Cont ID  
Sent By vperez Date 2016-10-12 Time 12:06 Rev Time 0.00
Received By vperez Date 2016-10-12 Time 12:06 Sent To  
Notes
2016-10-12 12:07:52PROVISO:
  
 ENG HAS AGREED AS PER RESPONSE NARRATIVE TO PROVIDE AT
 A LATER DATE
  
 PROVIDE PHOTOMETRIC FOR ALL INTERIOR AND EXTERIOR
 LIGHTING AREAS, MINIMUM LIGHTINGS LEVELS TO BE
 MAINTAINED PER FBC.
  
 VAL PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-22 Cont ID  
Sent By vperez Date 2016-06-22 Time 10:32 Rev Time 0.00
Received By vperez Date 2016-06-20 Time 12:08 Sent To  
Notes
2016-06-22 10:33:15APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. SHEET E100/E200- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR ALL SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE
 WILL SUFFICE.
 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED
 TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA,
 SIGNAGE, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 3. PLEASE PROVIDE DETAILS OF ALL ELECTRICAL ROOMS
 IMPACTED BY SCOPE OF WORK. FBC 107.3.5
 4. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC
 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS
 AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS
 REQUIRED.
 5. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS.
 6. SHEET E-121.8K- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS FOR HOOD SUPPRESSION SYSTEMS.
 7. PROVIDE PHOTOMETRIC FOR ALL INTERIOR AND EXTERIOR
 LIGHTING AREAS, MINIMUM LIGHTINGS LEVELS TO BE
 MAINTAINED PER FBC.
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2016-10-21 Cont ID  
Sent By Mgonzale Date 2016-10-21 Time   Rev Time 1.00
Received By mgonzale Date 2016-10-21 Time   Sent To Z
Notes
2016-10-21 14:51:39PROJECT WILL BE REVIEWED THRU ENGINEERING.
  
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-07-20 Cont ID  
Sent By mgonzale Date 2016-07-20 Time   Rev Time 1.00
Received By mgonzale Date 2016-07-20 Time   Sent To Z
Notes
2016-07-20 14:19:46ADDRESS PLANNING'S COMMENTS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-03-07 Cont ID  
Sent By pleduc Date 2017-03-06 Time   Rev Time 0.00
Received By pleduc Date 2017-03-06 Time 09:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-12-22 Cont ID  
Sent By pleduc Date 2016-12-22 Time   Rev Time 0.00
Received By pleduc Date 2016-12-22 Time 13:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-17 Cont ID  
Sent By pleduc Date 2016-10-17 Time   Rev Time 0.00
Received By pleduc Date 2016-10-11 Time 16:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-24 Cont ID  
Sent By pleduc Date 2016-06-24 Time   Rev Time 0.00
Received By pleduc Date 2016-06-13 Time 12:07 Sent To  
Notes
2016-06-20 16:14:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET FS 200 - THERE IS NO INDICATION THAT THE HOOD
 VENTING WILL BE INSTALLED PER NFPA 96 AND UNDER
 SEPARATE SHOP DRAWINGS.
  
 NFPA 101
 CHAPTER 9 BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTS OF THIS STANDARD.
  
 PLEASE PROVIDE THE APPLICABLE NOTE.
  
  
 2) SHEET S 300 - THERE APPEARS TO LIGHTWEIGHT TRUSS
 CONSTRUCTION WITHIN AND ON THE STRUCTURE.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
 3) SHEET LS 001 & FP 100 - A STANDPIPE SYSTME IS
 INDICATED ON LS 100; HOWEVER, THERE IS NO INDICATIONS
 OF STANDPIPE(S) ON FP 100.
  
 PLEASE PROVIDE INDICATIONS AND LOCATIONS OF STANDPIPE
 PROTECTION.
  
  
 4) SHEET E 001 - THERE IS NO INDICATION THAT THE FIRE
 ALARM WILL BE INSTALLED PER NFPA 72 AND UNDER SEPARATE
 SHOP DRAWINGS.
  
 NFPA 101, CHAPTER 9 BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT
 9.6.1.3 A FIRE ALARM SYSTEM REQUIRED FOR LIFE SAFETY
 SHALL BE INSTALLED, TESTED, AND MAINTAINED IN
 ACCORDANCE WITH THE APPLICABLE REQUIREMENTS OF N
 FPA 70, NATIONAL ELECTRICAL CODE, AND NFPA
 72, NATIONAL FIRE ALARM AND SIGNALING CODE, UNLESS IT
 IS AN APPROVED EXISTING INSTALLATION, WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN USE.
  
 PLEASE PROVIDE A NOTE INDICATING THAT THE FIRE ALARM
 SHALL BE INSTALLED PER NFPA 72 AND UNDER SEPARATE SHOP
 DRAWINGS..
  
  
 5) SHEET LS 001 - THERE IS NO INDICATIONS THAT THE FIRE
 ALARM WILL BE SUBMITTED AND INSTALLED UNDER SEPARATE
 SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE.
  
  
 6) SHEET LS 001 - THERE IS INDICATION UNDER THE TILTE
 VERTICAL OPENINGS FOR THE INSTALLTION OF A DRAFT
 CURTAIN AND CLOSELY SPACED SPRINKLERS. SHEET FP 100 AND
 OTHER FP SHEETS DO NOT INCLUDE INDICATIONS OR DESIGN.
  
 PLEASE PROVIDE DESIGN INDICATORS FOR DRAFT CURTAINS AND
 CLOSELY SPACED SPRINKLERS IN THE APPLICABLE SPACES PER
 THE ENGINEER OF RECORD.
  
  
 7) SHEET A 806 - WITHIN THE DOOR SCHEDULE UNDER THE
 HDWR SET HEADING THERE IS REFERENCE TO "E" NUMBERS AND
 OTHER NUMBERS. THOSE INDICATORS COULD NOT BE READILY
 IDENTIFIED ON THIS SHEET OR ANOTHER SHEET TO CONFIRM
 PROPER HARDWARE.
  
 PLEASE CLARIFY OR IDENTFY THE CORRESPONDING SHEET.
  
 8) SHEET LS 101 & A 806 - DOOR 116 IS INDCIATED WITHIN
 A SMOKE BARRIER WALL; HOWEVER, THE DOOR SCHEDULE DOES
 NOT INDICATE IT WITH ANY FIRE RATING.
  
 PLEASE CORRECT OR VERIFY.
  
 9) SHEET LS 101 & A 806 - DOOR 118 D IS INDICATED
 WITHINA SMOKE BARRIER WALL; HOWEVER, THE DOOR SCHEDULE
 DOES NOT INDICATE IT WITH ANY FIRE RATING.
  
 10) SHEET LS 101 & A 806 - DOOR 123 IS INDICATED WITHIN
 A 2 HR FIRE RATED WALL; HOWEVER, THE DOOR SCHEDULE
 INDICATES AS A SMOKE BARRIER DOOR.
  
 PLEASE COORECT TO 90 MIN. DOOR OR VERIFY.
  
 11) SHEET LS 101, A 121 & A 806 - THE FLOOR LAYOUT
 AROUND DOOR 105 IS SLIGHTLY DIFFERENT; HOWEVER, DOOR
 105 IS WITHIN A 2 HR FIRE RATED WALL AND THE DOOR
 SCHEDULE DOES NOT INDICATE ANY FIRE RATING.
  
 PLEASE CORRECT TO 90 MIN DOOR OR VERIFY.
  
 12) SHEET LS 102 & A 806 - DOOR 226E IS INDICATED
 WITHIN A SMOKE BARRIER WALL; HOWEVER, THE DOOR SCHEDULE
 DOES NOT INDICATE IT WITH ANY FIRE RATING.
  
 PLEASE COORECT TO 90 MIN. DOOR OR VERIFY.
  
 13 ) SHEET LS 102 & A 806 - DOOR 225A IS INDICATED
 WITHIN A SMOKE BARRIER WALL; HOWEVER, THE DOOR SCHEDULE
 DOES NOT INDICATE IT WITH ANY FIRE RATING.
  
 PLEASE COORECT TO 90 MIN. DOOR OR VERIFY.
  
 14) SHEET LS 101M & A 806 - DOOR 101 MA IS INDICATED
 WITHIN A 2 HR FIRE RATED WALL; HOWEVER, THE DOOR
 SCHEDULE INDICATES NO RATING.
  
 PLEASE COORECT TO 90 MIN. DOOR OR VERIFY.
  
 15) SHEET LS 101 & A 806 - DOOR 124 IS INDICATED WITHIN
 A 2 HR FIRE RATED WALL; HOWEVER, THE DOOR SCHEDULE
 INDICATES NO RATING.
  
 PLEASE COORECT TO 90 MIN. DOOR OR VERIFY.
  
 16) SHEET LS 101 & A 806 - THE DOOR CONNECTING VESTIBLE
 124 AND THE STAIRWELL DOES NOT APPEAR TO BE INDICATED
 WITH A DOOR NUMBER AND IS NOT ON THE DOOR SCHEDULE.
  
 PLEASE COORECT OR VERIFY.
  
 17) SHEET A 806 - THERE IS INDICATIONS WITHIN THE DOOR
 SCHEDULE OF HARDWARE SET ID NUMBERS. I AM NOT ABLE TO
 READLITY LOCATE THE SHEET THAT IDENTIFIES THE
 CORRESPONDING HARDWARE SETS FOR VERIFICATION PURPOSES.
  
 PLEASE CORRECT OF VERIFY.
  
 18) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-03-06 Cont ID  
Sent By gjohnson Date 2017-03-06 Time 16:19 Rev Time 0.00
Received By gjohnson Date 2017-03-06 Time 16:19 Sent To  
Notes
2017-03-06 16:19:47PROVISO 2ND REQUEST
 PLUMBING
 1. PROVIDE A CLEAR AND CONCISE ISOMETRIC DRAWING FOR
 THE STORM DRAIN SHOWING ALL SIZES SLOPE OF PIPE, SQ FT
 AND LEVEL. THE ONE IN THE PLAN SET IS NOT CLEAR AND
 DOES NOT SHOW ALL THE REQUIRED INFORMATION. MUST BE
 APPROVED BY BUILDING DEPARTMENT PRIOR TO FIST ROUGH
 INSPECTION.
 GAS
 1. PROVIDE COMBUSTION AIR CALCULATIONS FOR GAS
 APPLIANCES IN THE KITCHEN. MUST BE APPROVED BY BUILDING
 DEPARTMENT PRIOR TO FIST ROUGH INSPECTION.
 2. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDE FOR GAS APPLIANCES. MUST BE APPROVED BY BUILDING
 DEPARTMENT PRIOR TO FIST ROUGH INSPECTION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-01-20 Cont ID  
Sent By gjohnson Date 2017-01-20 Time 09:47 Rev Time 0.00
Received By gjohnson Date 2017-01-20 Time 09:47 Sent To  
Notes
2017-01-20 09:47:56PROVISO
 PLUMBING
 1. PROVIDE A CLEAR AND CONCISE ISOMETRIC DRAWING FOR
 THE STORM DRAIN SHOWING ALL SIZES SLOPE OF PIPE, SQ FT
 AND LEVEL. THE ONE IN THE PLAN SET IS NOT CLEAR AND
 DOES NOT SHOW ALL THE REQUIRED INFORMATION. MUST BE
 APPROVED BY BUILDING DEPARTMENT PRIOR TO FIST ROUGH
 INSPECTION.
 GAS
 1. PROVIDE COMBUSTION AIR CALCULATIONS FOR GAS
 APPLIANCES IN THE KITCHEN. MUST BE APPROVED BY BUILDING
 DEPARTMENT PRIOR TO FIST ROUGH INSPECTION.
 2. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDE FOR GAS APPLIANCES. MUST BE APPROVED BY BUILDING
 DEPARTMENT PRIOR TO FIST ROUGH INSPECTION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-10-28 Cont ID  
Sent By gjohnson Date 2016-10-28 Time 11:50 Rev Time 0.00
Received By gjohnson Date 2016-10-28 Time 11:50 Sent To  
Notes
2016-10-28 11:54:341ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS ENCLUDE
 EXISTING PER FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. ENCLUDE ANY EXISTING REFER TO THE FBC-2014
 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1)
 THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-03-13 Cont ID  
Sent By cpuell Date 2017-03-13 Time 15:58 Rev Time 0.00
Received By cpuell Date 2017-02-17 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-23 Cont ID  
Sent By jwitmer Date 2017-01-23 Time 13:58 Rev Time 0.00
Received By jwitmer Date 2016-12-16 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-08 Cont ID  
Sent By jwitmer Date 2016-12-08 Time 08:54 Rev Time 0.00
Received By lmarchan Date 2016-10-05 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-22 Cont ID  
Sent By cpuell Date 2016-07-22 Time 09:02 Rev Time 0.00
Received By cpuell Date 2016-06-03 Time 08:00 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2017-01-09 Cont ID  
Sent By jwitmer Date 2017-01-09 Time 16:22 Rev Time 0.00
Received By jwitmer Date 2017-01-09 Time 16:22 Sent To  
Notes
2017-01-09 16:23:09P. B. C. IMPACT FEES WERE PAID UNDER STRUCTURAL PERMIT
 16080215.
 RECEIPT NUMBER 2016-1018-70
 MU RECEIPT: 2016-024353-0000
 FEES: $3,805.74
 J. WITMER PX
2016-11-04 11:09:12IMPACT FEES GIVEN TO JWITMER

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-10-28 Cont ID  
Sent By jwitmer Date 2016-10-28 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2016-10-28 Time 16:46 Sent To  
Notes
2016-10-28 16:46:26BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-06-28 Cont ID  
Sent By jwitmer Date 2016-06-28 Time 14:47 Rev Time 0.00
Received By jwitmer Date 2016-06-28 Time 14:47 Sent To  
Notes
2016-06-28 14:58:12IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-03-09 Cont ID  
Sent By ccole Date 2017-03-09 Time 15:56 Rev Time 0.00
Received By ccole Date 2017-02-24 Time 07:33 Sent To  
Notes
2017-03-09 16:14:06MECHANICAL PROVISOS.
 NORTON MUSEUM OF ART
 PERMIT #16050912
 3/9/2017
  
 1) THE MECHANICAL PLANS HAVE BEEN APPROVED
 CONDITIONALLY. A REVISION TO THE PLANS IS REQUIRED TO
 CORRECT THE DEFICIENCIES LISTED BELOW.
  
 A) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN SYSTEMS
 OF THE AHU'S.
  
 B) PROVIDE FIRE DAMPERS FOR ALL DUCTS PENETRATING THE
 FIRE-RATED WALL OF MECHANICAL ROOM 302.
  
 C) A NEW CHILLER (CH-1) IS BEING INSTALLED IN THE
 EXISTING MECHANICAL ROOM. ADDITIONAL VENTILATION FOR
 NORMAL AND EMERGENCY VENTILATION MAY BE REQUIRED. REFER
 TO SECTIONS 1105.6- 1105.6.3.2 FBC-14 MECHANICAL AND
 PROVIDE EXHAUST VENTILATION CALCULATIONS FOR BOTH
 NORMAL AND EMERGENCY CONDITIONS AS REQUIRED BY SECTIONS
 1105.6.3.1 AND 1105.6.3.2. SHOW LOCATIONS OF ALL
 COMPONENTS OF THE VENTILATION SYSTEM INCLUDING EXHAUST
 FANS AND AIR INTAKES. INCLUDE EQUIPMENT SCHEDULES FOR
 ALL EXISTING FANS OR NEW FANS (EXHAUST OR INTAKE)
 INDICATING THEIR CAPACITIES, AND THE DIMENSIONS OF ALL
 AIR INTAKE OPENINGS. PLEASE NOTE THE NEW CH-3 USES A
 DIFFERENT REFRIGERANT THAN THE EXISTING CH-1 AND CH-2,
 THEREFORE THE EXISTING LEAK DETECTOR MAY NOT BE
 COMPATIBLE.
 SUBMIT SPECIFICATIONS FOR THE LEAK DETECTOR.
  
 D) AHU HEATING COIL: CORRECT OR CLARIFY THE CONFLICTS
 BETWEEN THE AC CALCULATIONS FOR THE HEATING COIL
 SELECTION VERSUS THE HEATING CAPACITIES SHOWN IN THE
 EQUIPMENT SCHEDULES: AHU'S 3, 14, 18, 19, 20, & 22.
  
 2) DEFERRED SUBMITTALS: AS REQUESTED BY THE CONTRACTOR
 PLEASE REVIEW THE FOLLOWING LIST OF DEFERRED
 SUBMITTALS. PLEASE NOTE:) DEFERRED SUBMITTALS SECTION
 107.3.4.2 WPB AMENDMENTS TO THE FBC. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 A) STRUCTURAL ENGINEERING FOR INSTALLATION OF THE
 COOLING TOWERS INCLUDING THE SUPPORT BASE, ACCESS
 STAIRS, WALKWAYS AND PLATFORM.
  
 B) MECHANICAL AND ELECTRICAL POWER AND LIGHTING SYSTEMS
 COMMISSIONING: PRELIMINARY AND FINAL REPORTS.
  
 C) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 FOR LOUVERS PROTECTING OUTSIDE AIR AND EXHAUST OUTLET
 OPENINGS. PLEASE NOTE:) PRODUCT APPROVALS- THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 D) MANUFACTURER'S SPECIFICATIONS FOR THE GLOBAL PLASMA
 SOLUTIONS IAQ EQUIPMENT AND DEVICES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-01-10 Cont ID  
Sent By ccole Date 2017-01-10 Time 17:39 Rev Time 0.00
Received By ccole Date 2017-01-10 Time 14:18 Sent To  
Notes
2017-01-10 17:47:303RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16050912
 NORTON MUSUEM
 1/10/17
  
 1) 3RD REQUEST FOR AC COOLING AND HEATING CALCULATIONS.
  
 2) THE REVISED ENERGYGAUGE COMPLIANCE FORM WAS
 SUBMITTED WITHOUT THE OWNER/AGENT'S SIGNATURE.
  
 3) 3RD REQUEST FOR COMPLETE VENTILATION CALCULATIONS.
 THE CALCULATIONS ON M607 ARE FOR THE ROOMS AND SPACES
 UTILIZING THE IAQ PROCEDURE - SYSTEMS 3, 18, 19,20,21,&
 22, HOWEVER MINIMUM VENTILATION CALCULATIONS ARE
 REQUIRED FOR ALL OF THE OTHER ROOMS AND SPACES I.E. THE
 FIRST FLOOR GALLERIES AND DINING AREAS ON THE SOUTH
 END- SYSTEMS 14 & 15. PLEASE NOTE THAT DEMAND
 CONTROLLED VENTILATION MAY BE REQUIRED- SEE SECTION
 C403.2.5.1 FBC-14 ENERGY CONSERVATION.
  
 4) 3RD REQUEST FOR EXHAUST VENTILATION CALCULATIONS FOR
 THE CHILLER ROOM , AND AN EQUIPMENT SCHEDULE FOR EF-9.
  
 5) 3RD REQUEST FOR DUCT SMOKE DETECTORS TO BE SHOWN IN
 THE RETURN AIR SYSTEMS OF THE AHU'S.
  
 6) 3RD REQUEST TO SHOW THE MISSING SMOKE AND FIRE
 DAMPERS:
 REFER TO SECTION 607.5.4.AND PROVIDE SMOKE DAMPERS FOR
 ALL DUCTS LISTED BELOW THAT PENETRATE SMOKE BARRIERS,
 UNLESS MEETING ONE OF THE THREE EXCEPTIONS LISTED UNDER
 THE SECTION.
 M121.5- 12X10 DUCT AT SMITH GALLERY 131/RESTROOM WALL.
 M121.8- 38X14 & 42X14 DUCTS AT LAUDER RESTAURANT
 120/LOBBY 118/CORRIDOR 113 WALLS.
 M122.8- 12X12 AT CONFERENCE 223/MCGRAW 225.
 30X12 AT MCGRAW 225/VESTIBULE 226.
 14X10 AT MARDEN 226/MCGRAW 225.
 M123.7- ALL DUCTS TRAVERSING THROUGH THE MARDEN GALLERY
 226/ CLASSROOM 221/ THE ADMISSIONS/GRAND HALL/& OFFICES
 209 & 210.
 M123.8- DUCTS AT CORRIDOR 301/MEP & GROSS GALLERY 304.
 M123.8:FSD'S FOR DUCTS PENETRATING THE SHAFT AT
 CORRIDOR 301.
 PROVIDE KEY NOTES AT ALL FD, FSD, AND SD DAMPER
 LOCATIONS.
 .
 7) INDICATE HOW ACCESS WILL BE PROVIDED TO THE FIRE
 DAMPERS LOCATED AT THE FLOOR/CEILING ASSEMBLY ABOVE THE
 STILLER AUDITORIUM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 CCOLE
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-26 Cont ID  
Sent By ccole Date 2016-10-26 Time 08:22 Rev Time 0.00
Received By ccole Date 2016-10-24 Time 17:41 Sent To  
Notes
2016-10-26 08:23:332ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16050912
 NORTON MUSEUM OF ART
 10/25/16
  
 THE SECOND REVIEW OF THE RESUBMITTED PLANS AND
 DOCUMENTS INDICATE THAT MANY OF THE 1ST REVIEW COMMENTS
 STILL EXIST EITHER ENTIRELY OR PARTIALLY. THOSE
 COMMENTS AND THE DESIGN PROFESSIONAL'S NARRATIVE
 RESPONSES WILL BE REFERENCED IN THIS FOLLOW-UP REVIEW
  
 1) COMMENT #1 FROM THE 1ST REVIEW: AS REQUESTED BY THE
 ENGINEER IN THE NARRATIVE, THE COMMISSIONING OF THE
 BUILDING MECHANICAL AND ELECTRICAL POWER AND LIGHTING
 SYSTEMS IS ACCEPTABLE AS A DEFERRED SUBMITTAL, HOWEVER
 AN OUTLINE OF THE PROCEDURES MUST BE PLACED ON THE
 MECHANICAL AND ELECTRICAL PLANS.
  
 2) COMMENT #2, 1ST REVIEW: THE REQUESTED AC COOLING AND
 HEATING CALCULATIONS WERE NOT SUBMITTED- PLEASE
 PROVIDE.
  
 3) COMMENT #3: THE ENERGYGAUGE COMPLIANCE SUBMITTAL
 MUST BE SIGNED BY THE OWNER/AGENT.
  
 4) COMMENT #4: PLEASE REFER TO SECTION 6.3.6 ASHRAE
 62.1- 2010 AND SUBMIT DOCUMENTATION TO CLARIFY THE IAQ
 PROCEDURE.
  
 6.3.6 DOCUMENTATION. WHEN THE IAQ PROCEDURE IS USED,
 THE FOLLOWING INFORMATION SHALL BE INCLUDED IN THE
 DESIGN DOCUMENTATION:
 THE CONTAMINANTS OF CONCERN CONSIDERED IN THE
 DESIGN PROCESS, THE SOURCES AND EMISSION RATES OF THE
 CONTAMINANTS
 OF CONCERN, THE CONCENTRATION LIMITS AND EXPOSURE
 PERIODS
 AND THE REFERENCES FOR THESE LIMITS, AND THE ANALYTICAL
 APPROACH USED TO DETERMINE VENTILATION RATES AND AIR
 CLEANING
 REQUIREMENTS. THE CONTAMINANT MONITORING AND OCCUPANT
 AND/
 OR VISITOR EVALUATION PLANS SHALL ALSO BE INCLUDED IN
 THE DOCUMENTATION.
  
 5) COMMENTS #5 & 6: DEFERRED SUBMITTALS FOR THE O/A
 LOUVERS ARE ACCEPTABLE PER THE NARRATIVE REQUEST,
 HOWEVER THE LOCATIONS AND CLEARANCES FOR THE AIR
 INTAKES MOST BE SHOWN ON THE PLANS.
  
 6) COMMENT #7: THE NARRATIVE REFERENCES SHEET M-604 IN
 RESPONSE TO THE COMMENT, HOWEVER THAT PLAN SHEET HAS
 NOT BEEN UPLOADED FOR REVIEW.
  
 7) COMMENT #8: THE REQUESTED EXHAUST VENTILATION
 CALCULATIONS FOR THE CHILLER ROOM AND FAN SCHEDULE WERE
 NOT PROVIDED- SEE SECTIONS 1105.6.3.1 AND 1105.6.3.2
 AND INDICATE COMPLIANCE.
  
 8) COMMENT #10: THE NARRATIVE RESPONSE SUBMITTED TO
 THIS COMMENT STATES THAT THE ANCHORAGE OF THE COOLING
 TOWERS WILL BE ENGINEERED AND INSTALLED BY THE
 CONTRACTOR. PLEASE NOTE THAT THE STRUCTURAL PLANS AND
 DETAILS FOR INSTALLATION OF THE COOLING TOWERS
 INCLUDING THE SUPPORT BASES AND ATTACHMENTS SHALL BE
 DESIGNED BY A FL. LICENSED ENGINEER IN ACCORDANCE WITH
 FLORIDA STATUTE 471. PLEASE PROVIDE THE REQUESTED
 ENGINEERING AND SUBMITTAL DOCUMENTS.
  
 9) COMMENT #12: PLEASE CORRECT THE ENERGY SUBMITTAL
 WHICH INDICATES 1 CHILLER INSTEAD OF THE 3 BEING
 INSTALLED, AND SUBMIT MANUFACTURER'S SPECIFICATIONS AS
 PREVIOUSLY REQUESTED.
  
 10) PLEASE REFER BACK TO COMMENT #14 FROM THE 1ST
 REVIEW AND ADD THE REQUESTED KEY NOTES TO IDENTIFY DUCT
 DROPS AND RISERS AND THEIR RESPECTIVE AHU'S.
  
 A) SEE SECTIONS 606.2.1 AND 606.2.3 AND SHOW THE
 LOCATIONS OF ALL REQUIRED DUCT SMOKE DETECTORS.
  
 B) REFER TO SECTION 607.5.4. AND PROVIDE SMOKE DAMPERS
 FOR ALL DUCTS LISTED BELOW THAT PENETRATE SMOKE
 BARRIERS, UNLESS MEETING ONE OF THE THREE EXCEPTIONS
 LISTED UNDER THE SECTION.
 M121.5- 12X10 DUCT AT SMITH GALLERY 131/RESTROOM WALL.
 M121.8- 38X14 & 42X14 DUCTS AT LAUDER RESTAURANT
 120/LOBBY 118/CORRIDOR 113 WALLS.
 M122.8- 12X12 AT CONFERENCE 223/MCGRAW 225.
 30X12 AT MCGRAW 225/VESTIBULE 226.
 14X10 AT MARDEN 226/MCGRAW 225.
 M123.7- ALL DUCTS TRAVERSING THROUGH THE MARDEN GALLERY
 226/ CLASSROOM 221/ THE ADMISSIONS/GRAND HALL/& OFFICES
 209 & 210.
 M123.8- DUCTS AT CORRIDOR 301/MEP & GROSS GALLERY 304.
 PROVIDE KEY NOTES AT ALL FD, FSD, AND SD DAMPER
 LOCATIONS.
  
 C) M122.5B: SHOW HORIZONTAL DAMPERS AT DUCT
 PENETRATIONS OF THE FLOOR/CEILING ASSEMBLY IN THE
 MECHANICAL EQUIPMENT ROOM. THIS COMMENT SHALL APPLY TO
 ALL PLAN SHEETS SHOWING DUCTS PENETRATING HORIZONTAL
 MEMBRANES
  
 D) AS PREVIOUSLY REQUESTED PLEASE IDENTIFY ALL ROOMS ON
 THE MECHANICAL PLANS.
  
 12) COMMENT #16: PROVIDE A CONDENSATE DISPOSAL RISER
 AND LAYOUT PLAN SHOWING ALL PIPING RUNS, PIPE TYPES AND
 SIZES, AND DISCHARGE LOCATIONS.
  
 13) PLEASE PROVIDE A MECHANICAL SYMBOL AND LEGEND PLAN
 SHEET.
  
 14) REFER TO SECTION 107.3.4.2 WPB AMENDMENTS OF THE
 FBC AND PROVIDE ON THE PLAN OR IN DOCUMENT FORM A LIST
 OF ALL MECHANICAL EQUIPMENT AND COMPONENTS THAT ARE
 REQUESTED TO BE DEFERRED SUBMITTALS.
  
 A) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 B) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-22 Cont ID  
Sent By ccole Date 2016-06-22 Time 15:48 Rev Time 0.00
Received By ccole Date 2016-06-15 Time 17:33 Sent To  
Notes
2016-06-22 15:48:38NORTON MUSUEM
 PERMIT #16050512
 1ST REVIEW MECHANICAL
 6/16/16
  
 PLEASE REFER TO SECTION 107.3.5.1 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE- MINIMUM PLAN
 REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. THE UPLOADED
 PLANS AND DOCUMENTS ARE NOT MEETING THE MINIMUM
 REQUIREMENTS, AND MORE DETAILS AND SUBMITTALS WILL BE
 REQUIRED FOR A THOROUGH REVIEW OF THE PROJECT. PLEASE
 REVIEW THE COMMENT LIST BELOW AND PROVIDE A RESPONSE
 NARRATIVE FROM THE DESIGN PROFESSIONAL CORRESPONDING TO
 THE RESUBMITTED AND CORRECTED PLANS AND DOCUMENTS.
  
 1) REFER TO SECTION C408.2 FBC-14 ENERGY CONSERVATION
 AND PROVIDE A COMMISSIONING PLAN AS OUTLINED IN SECTION
 C408.2.1.
  
 2) REFER TO SECTION C403.2.1 AND PROVIDE AC COOLING AND
 HEATING CALCULATIONS FOR ALL NEW SYSTEMS SHOWN IN THE
 PLANS AND THE SCHEDULES.
  
 3) REFER TO SECTION C103.1.1.1.2: THE SUBMITTED ENERGY
 CALCULATIONS MUST BE SIGNED BY ALL OF THE DESIGN
 PROFESSIONALS INVOLVED WITH THE PROJECT.
  
 4) PROVIDE MINIMUM VENTILATION CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.3 FBC-14 MECHANICAL. PROVIDE
 ON THE PLAN A SCHEDULE INDICATING BOTH THE REQUIRED AND
 PROVIDED CFM'S OF OUTDOOR AIR FOR ALL ROOMS AND SPACES.
  
 5) SHOW THE LOCATIONS OF ALL OUTDOOR AIR INTAKES-
 GRAVITY OR MECHANICAL- WITH REQUIRED CLEARANCE
 DISTANCES AS REQUIRED BY SECTION 401.4.
  
 6) REFER TO SECTION 401.5 FOR ALL AIR INTAKES OPENINGS
 TO BE PROTECTED BY LOUVERS. PRODUCT APPROVALS AND/OR
 MIAMI-DADE NOA'S MUST BE LISTED ON THE PLANS AND
 DOCUMENTS MUST BE SUBMITTED WITH THE DESIGN
 PROFESSIONAL'S APPROVAL SIGNATURE. THIS INCLUDES THE 45
 SF AIR INTAKE SHOWN ON M123.8.
  
 7) PROVIDE EXHAUST VENTILATION CALCULATIONS THAT
 CORRELATE WITH ALL FANS SHOWN IN THE SCHEDULE AND ALL
 OTHER ROOMS AND SPACES REQUIRING EXHAUST PER TABLE
 403.3 FBC-14 MECHANICAL, AND TABLE 6-4 ASHRAE
 62.1-2010. SEE COMMENT #8 BELOW FOR THE MECHANICAL ROOM
 VENTILATION REQUIREMENTS. A) REFER TO SECTION 501.3.1
 AND INDICATE ALL REQUIRED CLEARANCES FOR THE EXHAUST
 OUTLET TERMINATIONS. B) PROVIDE AIR BALANCE
 CALCULATIONS THAT CORRELATE WITH THE REQUIRED MINIMUM
 VENTILATION CALCS- SEE COMMENT #4 ABOVE. ADVISORY:
 SEPARATE PERMITS, PLANS, AND CALCULATIONS FOR THE
 KITCHEN EXHAUST HOOD AND FIRE SUPPRESSION SYSTEMS ARE
 REQUIRED, HOWEVER THE EXHAUST CFM'S MUST BE INCLUDED IN
 THE AIR BALANCE CALCULATIONS.
  
 8) SHEET M121.7: A NEW CHILLER (CH-1) IS BEING
 INSTALLED IN THE EXISTING MECHANICAL ROOM. ADDITIONAL
 VENTILATION FOR NORMAL AND EMERGENCY VENTILATION MAY BE
 REQUIRED. REFER TO SECTIONS 1105.6- 1105.6.3.2 AND
 PROVIDE EXHAUST VENTILATION CALCULATIONS FOR BOTH
 NORMAL AND EMERGENCY CONDITIONS AS REQUIRED BY SECTIONS
 1105.6.3.1 AND 1105.6.3.2. SHOW LOCATIONS OF ALL
 COMPONENTS OF THE VENTILATION SYSTEM INCLUDING EXHAUST
 FANS AND AIR INTAKES. INCLUDE EQUIPMENT SCHEDULES FOR
 ALL EXISTING FANS OR NEW FANS (EXHAUST OR INTAKE)
 INDICATING THEIR CAPACITIES, AND THE DIMENSIONS OF ALL
 AIR INTAKE OPENINGS. PLEASE NOTE: A) EF-9 SHOWN IN THE
 DRAWING IS NOT INCLUDED IN THE SCHEDULE. IS THIS AN
 EXISTING FAN? B) THE NEW CH-3 USES A DIFFERENT
 REFRIGERANT THAN THE EXISTING CH-1 AND CH-2, THEREFORE
 THE EXISTING LEAK DETECTOR MAY NOT BE COMPATIBLE. C)
 WHERE ARE THE NOTES OR DETAILS THAT CORRESPOND WITH THE
 M91, 92, 93, & 94 TAGS SHOWN AT THE MECHANICAL ROOM.
 THE M TAG IS USED IN OTHER PLAN LOCATIONS BUT I HAVE
 NOT LOCATED ANY CORRESPONDING NOTES OR DETAILS.
  
 9) PROVIDE AN ENLARGED DRAWING OF THE MECHANICAL ROOM
 SHOWING ALL EQUIPMENT, PIPING LAYOUTS, WORKING
 CLEARANCES, EQUIPMENT ANCHORING, AND RELIEF PIPINGS AND
 VENTS.
  
 10) SHEET M122.7: PROVIDE ENLARGED DRAWINGS OF THE NEW
 COOLING TOWERS INCLUDING SITE SPECIFIC WIND LOAD
 ENGINEERING FOR ANCHORING THE SUPPORT BASE TO THE ROOF
 STRUCTURE, AND THE TOWERS TO THE SUPPORT STEEL. PROVIDE
 MANUFACTURER'S SPECIFICATIONS FOR THE COOLING TOWERS
 APPROVED WITH SIGNATURES BY THE EOR.
  
 11) M601: REFER TO TABLES C403.2.3(7) AND C40.2.3(8)
 FBC-14 ENERGY CONSERVATION AND PROVIDE IN THE EQUIPMENT
 SCHEDULES THE EFFICIENCY AND PERFORMANCE RATINGS FOR
 THE CHILLER AND THE COOLING TOWERS. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE CHILLER, TOWERS,
 AND PUMPS WITH APPROVAL SIGNATURES BY THE EOR.
  
 12) M105: REFER TO SECTION 301.15 FBC-14 MECHANICAL AND
 SECTION 1609 FBC-14 BUILDING AND SHOW THE LOCATIONS OF
 ALL ROOFTOP MECHANICAL EQUIPMENT, AND PROVIDE WIND LOAD
 ENGINEERING FOR TIE DOWN OF ALL APPLIANCES, EQUIPMENT,
 CURBS AND STANDS TO THE ROOF STRUCTURE. A) SHOW THE
 REQUIRED CLEARANCE DISTANCES FOR ALL EXHAUST OUTLETS TO
 AIR INTAKES. B) SHOW THE CLEARANCE DISTANCS FROM THE
 SERVICEABLE EQUIPMENT TO THE ROOF EDGES- SECTION
 304.11.
  
 13) M601: AHU'S 23, 30, 31, 32, 33, & 34 LISTED AS NEW
 IN THE SCHEDULE ARE NOT SHOWN IN THE ENERGY
 CALCULATIONS. PLEASE DARKEN THE PRINTED NOTES UNDER THE
 AHU SCHEDULE- THEY ARE TOO FAINT TO READ.
  
 14) SHEETS M121.7- M123.8B, 1ST, 2ND, & 3RD FLOOR
 MECHANICAL PLANS: MANY OF THE SAME DEFICIENCIES AND
 OMISSIONS EXIST ON ALL OF THESE PLAN SHEETS. IT MAY BE
 HELPFUL TO ADD KEY NOTES TO ALL THESE SHEETS AND LEGEND
 SYMBOLS TO CLARIFY THE SCOPE OF WORK AND EXPEDITE THE
 REVIEW, I.E. IT IS DIFFICULT TO TELL WHICH AC SYSTEMS
 THE DUCT DROPS ARE CONNECTED TO. AN AC LABEL AT THESE
 LOCATIONS WOULD BE VERY HELPFUL A) DUCT SMOKE DETECTORS
 IN THE RETURN AIR SYSTEMS NOT SHOWN- SEE SECTIONS
 606.2.1 AND 606.2.3. B) FIRE AND SMOKE DAMPERS NOT
 SHOWN AT DUCTS PENETRATED FIRE AND SMOKE BARRIERS AND
 PARTITIONS. IT MAY BE HELPFUL TO OVERLAY THE WALLS ON
 THE MECHANICAL PLAN THAT ARE FIRE OR SMOKE RATED, AND
 AGAIN, KEY NOTES ARE HELPFUL FOR LOCATING REQUIRED
 DAMPERS AND DUCT SMOKE DETECTORS. C) IDENTIFY AND LABEL
 ALL DUCT SHAFTS AND PIPE CHASES. D) LABEL ALL DIFFUSERS
 AND RETURN GRILLS ON THE PLANS AND INCLUDE THE CFM
 AIRFLOW RATES- MANY OF THE SLOT AND CEILING DIFFUSERS
 ON THE PLANS ARE NOT LABELED. E) MANY OF THE BRANCH AND
 TRANSFER DUCT SIZES ARE NOT INDICATED AS WELL AS SOME
 OF THE MAIN DUCT TRUNKS. F) INSTALLATION AND SUPPORT
 DETAILS FOR THE AIR HANDLERS NOT SHOWN. G) SHOW ACCESS
 PANEL LOCATIONS FOR MAINTENANCE AND REPLACEMENT OF THE
 AIR HANDLERS AND ALL OTHER ABOVE CEILING EQUIPMENT. H)
 IDENTIFY ALL ROOMS AND SPACES ON THE PLANS (THE PRINT
 IS VERY FAINT). PLEASE REVIEW AND REVISE THE PLANS
 ACCORDINGLY.
  
 15) PLEASE REVIEW SECTION C403.2.4.4 (SHUTOFF DAMPER
 CONTROLS), AND C403.2.5.1 (DEMAND CONTROLLED
 VENTILATION) AND REVISE THE PLANS TO SHOW COMPLIANCE
 WHERE REQUIRED.
  
 16) REFER TO SECTION 307 AND PROVIDE PRIMARY AND
 SECONDARY CONDENSATE DISPOSAL PLANS FOR THE AIR
 HANDLERS.
  
 17) PROVIDE EQUIPMENT SCHEDULES FOR THE BOILERS AND
 SHOW THEIR LOCATIONS ON THE PLANS.
  
 18) SHOW THE LOCATION OF THE ERU-1S ON THE PLANS.
  
 19) THE MECHANICAL REVIEW IS SUSPENDED AT THIS TIME DUE
 TO DEFICIENCIES IN THE PLANS AND THE LACK OF
 SUBMITTALS. PLEASE NOTE THAT THERE MAY BE ADDITIONAL
 COMMENTS AFTER REVISED AND CORRECTED PLANS ARE
 RESUBMITTED FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-03-06 Cont ID  
Sent By gjohnson Date 2017-03-06 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2017-03-06 Time 16:18 Sent To  
Notes
2017-03-06 16:19:01PROVISO 2ND REQUEST
 PLUMBING
 1. PROVIDE A CLEAR AND CONCISE ISOMETRIC DRAWING FOR
 THE STORM DRAIN SHOWING ALL SIZES SLOPE OF PIPE, SQ FT
 AND LEVEL. THE ONE IN THE PLAN SET IS NOT CLEAR AND
 DOES NOT SHOW ALL THE REQUIRED INFORMATION. MUST BE
 APPROVED BY BUILDING DEPARTMENT PRIOR TO FIST ROUGH
 INSPECTION.
 GAS
 1. PROVIDE COMBUSTION AIR CALCULATIONS FOR GAS
 APPLIANCES IN THE KITCHEN. MUST BE APPROVED BY BUILDING
 DEPARTMENT PRIOR TO FIST ROUGH INSPECTION.
 2. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDE FOR GAS APPLIANCES. MUST BE APPROVED BY BUILDING
 DEPARTMENT PRIOR TO FIST ROUGH INSPECTION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-01-20 Cont ID  
Sent By gjohnson Date 2017-01-20 Time 08:50 Rev Time 0.00
Received By gjohnson Date 2017-01-19 Time 13:20 Sent To  
Notes
2017-01-20 08:52:17PROVISO
 PLUMBING
 1. PROVIDE A CLEAR AND CONCISE ISOMETRIC DRAWING FOR
 THE STORM DRAIN SHOWING ALL SIZES SLOPE OF PIPE, SQ FT
 AND LEVEL. THE ONE IN THE PLAN SET IS NOT CLEAR AND
 DOES NOT SHOW ALL THE REQUIRED INFORMATION. MUST BE
 APPROVED BY BUILDING DEPARTMENT PRIOR TO FIST ROUGH
 INSPECTION.
 GAS
 1. PROVIDE COMBUSTION AIR CALCULATIONS FOR GAS
 APPLIANCES IN THE KITCHEN. MUST BE APPROVED BY BUILDING
 DEPARTMENT PRIOR TO FIST ROUGH INSPECTION.
 2. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDE FOR GAS APPLIANCES. MUST BE APPROVED BY BUILDING
 DEPARTMENT PRIOR TO FIST ROUGH INSPECTION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-10-27 Cont ID  
Sent By gjohnson Date 2016-10-27 Time 14:45 Rev Time 0.00
Received By gjohnson Date 2016-10-25 Time 12:43 Sent To  
Notes
2016-10-27 14:47:022ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
  
 1.NOT COMPLIED. IT APPEARS THAT THE FIXTURE COUNT IS TO
 LOW FOR THE OCCUPANT LOAD. PLEASE PROVIDE A BREAKDOWN
 OF FIXTURES REQUIRED AND FIXTURES PROVIDED. PER FBC PL
 TABLE 403.1
 USING THE OCCUPANT LOAD FROM THE LIFE SAFETY PAGES THE
 REQUIRED NUMBER OF WATER CLOSETS FOR THE WOMEN WOULD BE
 26 TOTAL I CAN ONLY FIND 16 ON THE PLAN. THE REQUIRED
 NUMBER OF WATER CLOSETS FOR THE MEN IS 16 I FOUND 12 ON
 THE PLAN. IF YOU PROVIDE A BREAKDOWN SHOWING OCCUPANT
 LOAD FOR EACH OCCUPANT TYPE AND THE REQUIRED FIXTURE
 COUNT AND WHAT IS PROVIDED> IT MIGHT CLARIFY THIS
 PROBLEM.
  
 3. NOT COMPLIED SHT. P101-104 PLEASE IDENTIFY PIPING
 AND SIZES. PERWPB AMEND. TO FBC 107.2.1
  
 6. NOT COMPLIED PROVIDE ISOMETRIC RISER DIAGRAM FOR ANY
 NEW STORM WITH SQFT. THAT IS BEING DRAINED ON EACH
 PIPE. PER WPB AMEND. TO FBC 107.3.5.1.3(13)
 SHT. P505
 A) THEIR ARE PIPES ON THE RISER DIAGRAM THAT END WITH
 NO INDICATION OF WHERE THEY GO OR WHAT SIZE PLEASE
 IDENTIFY EACH PEACE OF PIPE TO COINCIDE WITH A LOCATION
 .
 B) PROVIDE SQUARE FOOTAGE AND SLOPE ON EACH SECTION OF
 PIPE.
 C) SHOW LEVEL AND LOCATION OF EACH ROOF DRAIN.
  
 11.NOT COMPLIED SHT A703 DETAIL 3A SHOW GRAB BARS IN
 AMBULATORY TOILET COMPARTMENT.PER FBC ACC. 604.8.2.3
  
 NEW COMMENTS:
  
 1. SHT. P504 THE VENTS ON THE FLOOR SINKS CAN NOT RUN
 HORIZONTALLY. PER FBC PL SEC 905.3 VENT CONNECTION TO
 DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
  
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 2.SHT. P121.5-P123.8 WHAT ARE THE SYMBOLS OF THE
 CIRCLES WITH THE P50-P58 PLEASE SHOW ON THE PLAN. PER
 WPB AMEND. TO FBC 107.2.1
  
 3. ON THE SANITARY RISER DIAGRAM PLEASE PROVIDE A WAY
 TO IDENTIFY THE STACKS TO COINCIDE WITH THE FLOOR
 PLANS. PER WPB AMEND. TO FBC 107.2.1
  
 4. PROVIDE A ISOMETRIC RISER DIAGRAM FOR THE KITCHEN
 PLUMBING.. PER WPB AMEND. TO FBC 107.2.1
  
 5. PLEASE EXPAND OR ENLARGE ALL ISOMETRIC DRAWINGS TO
 INSURE THAT THEY CAN BE EASILY READ BY THE INSPECTORS
 IN THE FIELD. PER WPB AMEND. TO FBC 107.2.1
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-28 Cont ID  
Sent By gjohnson Date 2016-06-28 Time 11:13 Rev Time 0.00
Received By gjohnson Date 2016-06-21 Time 14:53 Sent To  
Notes
2016-06-28 14:15:491ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. IT APPEARS THAT THE FIXTURE COUNT IS TO LOW FOR THE
 OCCUPANT LOAD. PLEASE PROVIDE A BREAKDOWN OF FIXTURES
 REQUIRED AND FIXTURES PROVIDED. PER FBC PL TABLE 403.1
  
 2. SEPARATE PERMITS REQUIRED FOR ANY NEW BACKFLOW
 DEVICES AT METERS. PER WPB UTILITIES
  
 3. SHT. P101-104 PLEASE IDENTIFY PIPING AND SIZES.
 PERWPB AMEND. TO FBC 107.2.1
  
 4. SHT. P122.7-123.7-122.8-123.8 THE NOTE ON THE GAS
 MAIN AND COLD WATER MAIN READS 3IN GAS AND CW THE GAS
 MAIN IS SHOWN AS 2IN. IN OTHER AREAS PLEASE CLARIFY.
 PER WPB AMEND. TO FBC 107.2.1
  
 5. PLEASE PROVIDE SEPARATE SANITARY AND WATER ISOMETRIC
 DRAWINGS FOR THE KITCHEN, COFFEE BAR AND KITCHENETTE RM
 212 PER WPB AMEND. TO FBC 107.3.5.1.3(13)
  
 6. PROVIDE ISOMETRIC RISER DIAGRAM FOR ANY NEW STORM
 WITH SQFT. THAT IS BEING DRAINED ON EACH PIPE. PER WPB
 AMEND. TO FBC 107.3.5.1.3(13)
  
 7. SHT. P503 RISER FO RUMENS RM 143 THE URINALS ARE
 SHOWN AS WC-1 PLEASE CLARIFY. PER WPB AMEND. TO FBC
 107.2.1
  
 8. SHT. 503 SHOW FAMILY BATHROOM ON RISER DIAGRAM. PER
 WPB AMEND. TO FBC 107.2.1
  
 9. PROVIDE SIZING CALCULATIONS FOR GREASE INTERCEPTOR.
 PER WPB AMEND. TO FBC 107.2.1
  
 10. SHT. 501 DETAIL 13 PLEASE COMPLY WITH GREASE TRAP
 DETAIL
 NOTE
 1) INLET INVERT SHALL DISCHARGE A MINIMUM OF 2 ?? ABOVE
 THE LIQUID LEVEL LINE AND OUTLET PIPE SHALL HAVE A TEE
 WITH A MINIMUM DIAMETER OF 4? TO WITHIN 8? OF THE
 BOTTOM OF THE TANK.
 2) MANHOLES SHALL BE PROVIDED OVER THE INLET AND OUTLET
 OF EACH INTERCEPTOR AND BE BROUGHT TO GRADE. MINIMUM
 SIZE OF MANHOLES SHALL BE 24?.
 3) LID TYPE:
 A) REGULAR ? FOUR-INCH THICK REINFORCED CONCRETE OR
 APPROVED EQUIVALENT.
 B) TRAFFIC BEARING ? SIX-INCH THICK REINFORCED CONCRETE
 OR APPROVED EQUIVALENT.
 4) A TWO-WAY CLEANOUT TEE, BROUGHT TO GRADE, SHALL BE
 INSTALLED ENTERING AND LEAVING EACH GREASE INTERCEPTOR.
 5) CLEANOUTS INSTALLED IN VEHICULAR TRAFFIC PAVED AREAS
 SHALL BE PROTECTED BY USE OF A CLEANOUT BOX WITH METAL
 LID.
 6) WALLS SHALL BE A MINIMUM OF 3? THICK AND BOTTOM
 SHALL BE A MINIMUM OF 4? THICK REINFORCED CONCRETE.
 7) TANK MUST BE TRAFFIC BEARING.
 8) PROVIDE ENGINEER OF RECORD APPROVED DETAIL/SHOP
 DRAWINGS.
 9) SIZE: SIZE OF THE GREASE TRAP SHALL BE BASED UPON
 THE ANTICIPATED FLOW RATE, WATER TEMPERATURE AND GREASE
 CONCENTRATION. ADEQUATE DETENTION TIME SHALL BE
 PROVIDED TO ALLOW THE GREASE TO BE DEPOSITED WITHIN THE
 GREASE TRAP BEFORE ENTERING THE CITY WASTEWATER SYSTEM.
 MINIMUM CAPACITY SIZE: 750 GALLONS. MAXIMUM CAPACITY
 SIZE: 1250 GALLONS.
 FOR SIZE APPROVAL, PLEASE CONTACT THE UTILITIES
 DEPARTMENT, ENVIRONMENTS COMPLIANCE (HOLLY MCGRATH
 LABORATORY) SUPERVISOR: (561) 822-2271 E-MAIL:
 [email protected]
 10) ALTERNATE MATERIALS AND DESIGN SHALL BE SUBMITTED
 FOR INDIVIDUAL APPROVAL.
  
 11. SHT A703 DETAIL 3A SHOW GRAB BARS IN AMBULATORY
 TOILET COMPARTMENT.PER FBC ACC. 604.8.2.3
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2017-03-06 Cont ID  
Sent By jwitmer Date 2017-03-04 Time 08:26 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
2017-03-06 16:32:233/6/17 SHEETS THAT ARE MISSING ELECTRONIC SIGNATURE
 FP-100, FP-501, FP-121M.7, P-501, P502, P-504, P-505,
 P-121.5
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
2017-03-04 08:26:05SAT. MARCH 04/ 2017. BUILDING 4TH SIGNATURE REVIEW,
 SHEETS MISSING THE ELECTRONIC SIGNATURE:
 SHEETS ARCHITECTURAL & STRUCTURALS SHEETS MISSING
 SIGNATURES.61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.JAMES A.
 WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-03-20 Cont ID  
Sent By skennedy Date 2017-03-20 Time 13:52 Rev Time 0.00
Received By skennedy Date 2017-03-20 Time 13:52 Sent To  
Notes
2016-10-29 10:57:48BUILDING 2ND SIGNATURE REVIEW, SHEETS MISSING THE
 ELECTRONIC SIGNATURE:
 SHEETS ARCHITECTURAL & STRUCTURALS SHEETS MISSING
 SIGNATURES.61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.JAMES A.
 WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2016-10-28 Cont ID  
Sent By jwitmer Date 2016-10-28 Time 16:45 Rev Time 0.00
Received By jwitmer Date 2016-10-28 Time 16:45 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By jwitmer Date 2016-07-11 Time 07:38 Rev Time 0.00
Received By jwitmer Date 2016-07-11 Time 07:38 Sent To  
Notes
2016-07-11 07:39:19SEE BUILDING COMMENT # 1.

Review Stop Z ZONING
Rev No 4 Status P Date 2017-03-13 Cont ID  
Sent By jroach Date 2017-03-13 Time 15:31 Rev Time 0.00
Received By jroach Date 2017-03-13 Time 15:31 Sent To  
Notes
2017-03-13 15:36:56ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.13.2017
 PERMIT NO.: 16050912
 ADDRESS: 1451 S OLIVE AVENUE
 CONTRACTOR/CONTACT: MICHAEL IZZO
 TELEPHONE NO.:
 SCOPE OF REVIEW: NORTON MUSEUM EXPANSION
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THE SCOPE OF THIS APPROVAL IS FOR CONSTRUCTION OF THE
 BUILDING ONLY...AND DOES NOT INCLUDE ANY SITE WORK,
 LANDSCAPING, ETC. THIS REVIEW HAS BEEN PASSED SUBJECT
 TO THE FOLLOWING PROVISOS:
  
 1. ANY REQUIRED EASEMENTS (I.E. DRAINAGE, UTILITIES,
 PUBLIC ACCESS, ETC.) SHALL BE PROVIDED VIA PLAT OR
 SEPARATE LEGAL INSTRUMENT.
  
 2. ALL CHAINLINK FENCING SHALL BE COMPLETELY SCREENED
 FROM VIEW UTILIZING SHRUBS, HEDGING, OR OTHER
 ACCEPTABLE LANDSCAPE MATERIAL.
  
 3. THE DEVELOPER SHALL BE RESPONSIBLE FOR THE
 INSTALLATION OF IRRIGATION AND LANDSCAPING WITHIN THE
 RIGHTS-OF-WAY ADJACENT TO THE CSPD, AND SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF SUCH IMPROVEMENTS,
 IN PERPETUITY.
  
 4. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS,
 ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM
 EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY. IT
 APPEARS THAT THERE ARE CONFLICTS BETWEEN SUCH UTILITY
 ELEMENTS AND FENCING, ETC. ALL CONFLICTS SHALL BE
 RESOLVED AND SUFFICIENT SCREENING PROVIDED.
  
 5. IMPROVEMENTS WITHIN THE SOUTH DIXIE RIGHT-OF-WAY
 (INCLUDING NEW CURBING, BOLLARDS, LIGHTING, SIDEWALKS,
 ETC.) SHALL BE SUBJECT TO PERMITTING BY FDOT.
 MAINTENANCE AGREEMENTS MAY BE REQUIRED.
  
 6. ALL IMPROVEMENTS WITHIN THE JEFFERSON ROAD,
 CRANESNEST WAY, AND SOUTH OLIVE AVENUE RIGHT-OF-WAY
 (I.E. ON-STREET PARKING, RESURFACING, ETC.) SHALL BE
 SUBJECT TO A CITY OF WPB RIGHT-OF-WAY PERMIT, OBTAINED
 FROM THE CITY'S ENGINEERING DEPARTMENT.
  
 7. ALL SIGNAGE (WALL MOUNTED, FREESTANDING, ETC.) SHALL
 BE SUBMITTED AND REVIEWED UNDER SEPARATE PERMITS.
  
 8. PRIOR TO THE ISSUANCE OF ANY CERTIFICATE OF
 OCCUPANCY:
  
  A. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE WITH
 ALL APPLICABLE STATUTES, REGULATIONS, AND THE CITY?S
 POLICIES AND PROCEDURES.
  
  B. JEFFERSON ROAD, BETWEEN SOUTH DIXIE HIGHWAY AND
 SOUTH OLIVE AVENUE SHALL BE MILLED AND RESURFACED. ALL
 APPLICABLE PERMITS SHALL BE OBTAINED FROM THE CITY?S
 PUBLIC WORKS DEPARTMENT.
  
  C. ANY DAMAGE TO EXISTING UTILITIES RESULTING FROM THE
 DEVELOPER'S CONSTRUCTION ACTIVITIES SHALL BE REPAIRED,
 AT THE DEVELOPER'S EXPENSE.
  
 THE FOLLOWING COMMENTS SHALL BE ADDRESSED PRIOR TO
 AUTHORIZING ANY SITE WORK (AS REFERENCED ABOVE):
  
 9. A MINOR AMENDMENT SHALL BE APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION
 PROVIDING DETAILED LANDSCAPE PLANS FOR CONSTRUCTION
 IMPLEMENTATION. SUCH PLANS SHALL:
  
  A. SPECIFY THE EXACT SPECIES AND LOCATION OF ALL
 TREES, SHRUBS, HEDGES, GROUNDCOVER, ETC. AND BE IN
 COMPLIANCE WITH ARTICLE XIV OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS, EXCEPT FOR THOSE
 PREVIOUSLY WAIVERS GRANTED
  
  B. IDENTIFY THE LOCATION OF ALL TREES/PALMS THAT ARE
 TO BE RELOCATED ON-SITE;
  
  C. IDENTIFY THE LOCATIONS REQUIRED FOR ROOT BARRIERS;
  
  I. INCLUDE A SHRUB PLANTING PLAN FOR THE OFF-SITE
 PARKING LOT LOCATED ON THE WEST SIDE OF SOUTH DIXIE
 HIGHWAY;
  
  II. PROVIDE THE DETAILED LANDSCAPE IMPROVEMENTS
 PROPOSED WITHIN THE SOUTH DIXIE HIGHWAY RIGHT-OF-WAY.
 PLEASE NOTE THAT ANY PLANTINGS SHALL NOT IMPEDE WITH
 THE SITE DISTANCE AND SHALL BE APPROVED BY FDOT.
  
 10. ALL LANDSCAPING SHALL BE SUBMITTED AND REVIEWED AS
 A SEPARATE PERMIT APPLICATION, SUBMITTED TO THE CITY'S
 BUILDING DIVISION.
  
 11. PHOTOMETRIC PLAN SHALL BE PROVIDED AND SHALL NOT
 EXCEED 1.0 FOOTCANDLES WHEN MEASURED AT THE PROPERTY
 LINE.
  
 12. THE DATA TABLE ON SHEET L102 SHOWS SIGNIFICANT
 CHANGES FROM WHAT WAS APPROVED BY THE CITY COMMISSION.
 MODIFICATIONS SHALL BE APPROVED THROUGH A MINOR PD
 AMENDMENT, UNLESS TRIGGERING ONE OF THE PROVISIONS OF
 SEC. 94-207(E)(1) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS. ALSO, THERE ARE
 INCONSISTENCIES IN THE DATA TABLE, SUCH AS SQUARE
 FOOTAGE FOR THE MUSEUM. NOTE THAT AN INCREASE IN SQUARE
 FOOTAGE MAY NECESSITATE ADDITIONAL PARKING, ETC. IN
 YOUR RESPONSE TO THIS COMMENT PREVIOUSLY, IT WAS
 INDICATED THAT SOME OF THE EXISTING SHEDS ARE TO BE
 PARTIALLY DEMOLISHED AND THAT THE NEW SERVICE YARD SHED
 IS LARGER. THERE ARE A COUPLE ISSUES WITH THIS...THE
 EXISTING SHEDS ARE LOCATED WITHIN THE BOUNDARIES OF THE
 HISTORIC SINGLE FAMILY HOMES AND REQUIRE APPROVAL OF
 THE CITY'S HISOTORIC PRESERVATION DIVISION PRIOR TO ANY
 DEMOLITION / RENOVATION. ADDITIONALLY, THESE WERE NOT
 COUNTED TOWARD THE NORTON'S PARKING REQUIREMENTS AS
 THEY WERE NOT DEEMED A PART OF THE MUSEUM ITSELF;
 HOWEVER, THE SERVICE YARD SHED WAS AND IT'S INCREASE IN
 SIZE DOES AFFECT THE PARKING REQUIREMENT, ETC.
  
 13. THROUGHOUT THE PERMIT SET VARIOUS TRADES ARE USING
 DIFFERENT VARIATIONS OF SITE / LANDSCAPE PLANS AS THE
 BASIS FOR THEIR DRAWINGS. ALL PLANS ACROSS ALL TRADES
 NEED TO BE CONSISTENT AND MATCH...AND THEY ALL SHOULD
 MATCH THOSE PLANS THAT HAVE BEEN APPROVED DURING THE
 PLANNED DEVELOPMENT (PD) PROCESS.
  
 14. AS INDICATED PREVIOUSLY, STAFF HAS SIGNFICANT
 CONCERNS REGARDING SOME OF THE PROPOSED REVISIONS TO
 THE SITE / LANDSCAPE PLANS, SUCH AS RECONFIGURATION OF
 THE PARKING / DROP-OFF AT THE CORNER OF JEFFERSON AND
 DIXIE, PROPOSED HEDGING / FENCING, ETC. THESE ISSUES
 NEED TO BE RESOLVED, INCORPORATED INTO THE REVISED
 PLANS, AND APPROVED THROUGH THE PLANNED DEVELOPMENT
 (PD) PROCESS BEFORE PERMITTING SUCH WORK.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status F Date 2017-01-19 Cont ID  
Sent By jroach Date 2017-01-19 Time 14:50 Rev Time 0.00
Received By jroach Date 2017-01-19 Time 14:50 Sent To  
Notes
2017-01-19 15:30:06ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.19.2017
 PERMIT NO.: 16050912
 ADDRESS: 1451 S OLIVE AVENUE
 CONTRACTOR/CONTACT: MICHAEL IZZO
 TELEPHONE NO.:
 SCOPE OF REVIEW: NORTON MUSEUM EXPANSION
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 ZONING STAFF DOES NOT HAVE ANY OBJECTION TO THE SCOPE
 OF WORK PERTAINING TO THE CONFINES OF THE BUILDING AND
 WILL PASS ITS REVIEW (SUBJECT TO PROVISOS) ONCE THE
 PERMIT IS READY TO BE ISSUED BY THE OTHER TRADES.
 PLEASE NOTE THAT CONCERNS / COMMENTS REMAIN WITH REGARD
 TO THE PROPOSED SITE WORK (PARKING LOTS, SIDEWALKS,
 LANDSCAPING, ETC.) AND WILL NEED TO BE RESOLVED BEFORE
 ZONING STAFF AUTHORIZES THE PROJECT TO PROCEED WITH
 THOSE ASPECTS OF THE PROJECT.
  
 THE FOLLOWING COMMENTS WILL REMAIN AS PROVISOS SO THAT
 ALL PARTIES ARE AWARE THROUGHOUT THE DURATION OF THE
 CONSTRUCTION:
  
 1. ANY REQUIRED EASEMENTS (I.E. DRAINAGE, UTILITIES,
 PUBLIC ACCESS, ETC.) SHALL BE PROVIDED VIA PLAT OR
 SEPARATE LEGAL INSTRUMENT.
  
 2. ALL CHAINLINK FENCING SHALL BE COMPLETELY SCREENED
 FROM VIEW UTILIZING SHRUBS, HEDGING, OR OTHER
 ACCEPTABLE LANDSCAPE MATERIAL.
  
 3. THE DEVELOPER SHALL BE RESPONSIBLE FOR THE
 INSTALLATION OF IRRIGATION AND LANDSCAPING WITHIN THE
 RIGHTS-OF-WAY ADJACENT TO THE CSPD, AND SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF SUCH IMPROVEMENTS,
 IN PERPETUITY.
  
 4. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS,
 ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM
 EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY. IT
 APPEARS THAT THERE ARE CONFLICTS BETWEEN SUCH UTILITY
 ELEMENTS AND FENCING, ETC. ALL CONFLICTS SHALL BE
 RESOLVED AND SUFFICIENT SCREENING PROVIDED.
  
 5. IMPROVEMENTS WITHIN THE SOUTH DIXIE RIGHT-OF-WAY
 (INCLUDING NEW CURBING, BOLLARDS, LIGHTING, SIDEWALKS,
 ETC.) SHALL BE SUBJECT TO PERMITTING BY FDOT.
 MAINTENANCE AGREEMENTS MAY BE REQUIRED.
  
 6. ALL IMPROVEMENTS WITHIN THE JEFFERSON ROAD,
 CRANESNEST WAY, AND SOUTH OLIVE AVENUE RIGHT-OF-WAY
 (I.E. ON-STREET PARKING, RESURFACING, ETC.) SHALL BE
 SUBJECT TO A CITY OF WPB RIGHT-OF-WAY PERMIT, OBTAINED
 FROM THE CITY'S ENGINEERING DEPARTMENT.
  
 7. ALL SIGNAGE (WALL MOUNTED, FREESTANDING, ETC.) SHALL
 BE SUBMITTED AND REVIEWED UNDER SEPARATE PERMITS.
  
 8. PRIOR TO THE ISSUANCE OF ANY CERTIFICATE OF
 OCCUPANCY:
  
  A. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE WITH
 ALL APPLICABLE STATUTES, REGULATIONS, AND THE CITY?S
 POLICIES AND PROCEDURES.
  
  B. JEFFERSON ROAD, BETWEEN SOUTH DIXIE HIGHWAY AND
 SOUTH OLIVE AVENUE SHALL BE MILLED AND RESURFACED. ALL
 APPLICABLE PERMITS SHALL BE OBTAINED FROM THE CITY?S
 PUBLIC WORKS DEPARTMENT.
  
  C. ANY DAMAGE TO EXISTING UTILITIES RESULTING FROM THE
 DEVELOPER'S CONSTRUCTION ACTIVITIES SHALL BE REPAIRED,
 AT THE DEVELOPER'S EXPENSE.
  
 THE FOLLOWING COMMENTS SHALL BE ADDRESSED PRIOR TO
 AUTHORIZING ANY SITE WORK (AS REFERENCED ABOVE):
  
 5. A MINOR AMENDMENT SHALL BE APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION
 PROVIDING DETAILED LANDSCAPE PLANS FOR CONSTRUCTION
 IMPLEMENTATION. SUCH PLANS SHALL:
  
  A. SPECIFY THE EXACT SPECIES AND LOCATION OF ALL
 TREES, SHRUBS, HEDGES, GROUNDCOVER, ETC. AND BE IN
 COMPLIANCE WITH ARTICLE XIV OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS, EXCEPT FOR THOSE
 PREVIOUSLY WAIVERS GRANTED
  
  B. IDENTIFY THE LOCATION OF ALL TREES/PALMS THAT ARE
 TO BE RELOCATED ON-SITE;
  
  C. IDENTIFY THE LOCATIONS REQUIRED FOR ROOT BARRIERS;
  
  I. INCLUDE A SHRUB PLANTING PLAN FOR THE OFF-SITE
 PARKING LOT LOCATED ON THE WEST SIDE OF SOUTH DIXIE
 HIGHWAY;
  
  II. PROVIDE THE DETAILED LANDSCAPE IMPROVEMENTS
 PROPOSED WITHIN THE SOUTH DIXIE HIGHWAY RIGHT-OF-WAY.
 PLEASE NOTE THAT ANY PLANTINGS SHALL NOT IMPEDE WITH
 THE SITE DISTANCE AND SHALL BE APPROVED BY FDOT.
  
 6. ON SHEET C102, THERE ARE SIGNS SHOWN IN THE SOUTH
 DIXIE HIGHWAY PEDESTRIAN SIDEWALK. PLEASE CLARIFY.
  
 7. ALL LANDSCAPING SHALL BE SUBMITTED AND REVIEWED AS A
 SEPARATE PERMIT APPLICATION, SUBMITTED TO THE CITY'S
 BUILDING DIVISION.
  
 8. PHOTOMETRIC PLAN SHALL BE PROVIDED AND SHALL NOT
 EXCEED 1.0 FOOTCANDLES WHEN MEASURED AT THE PROPERTY
 LINE.
  
 9. THE DATA TABLE ON SHEET L102 SHOWS SIGNIFICANT
 CHANGES FROM WHAT WAS APPROVED BY THE CITY COMMISSION.
 MODIFICATIONS SHALL BE APPROVED THROUGH A MINOR PD
 AMENDMENT, UNLESS TRIGGERING ONE OF THE PROVISIONS OF
 SEC. 94-207(E)(1) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS. ALSO, THERE ARE
 INCONSISTENCIES IN THE DATA TABLE, SUCH AS SQUARE
 FOOTAGE FOR THE MUSEUM. NOTE THAT AN INCREASE IN SQUARE
 FOOTAGE MAY NECESSITATE ADDITIONAL PARKING, ETC. IN
 YOUR RESPONSE TO THIS COMMENT PREVIOUSLY, IT WAS
 INDICATED THAT SOME OF THE EXISTING SHEDS ARE TO BE
 PARTIALLY DEMOLISHED AND THAT THE NEW SERVICE YARD SHED
 IS LARGER. THERE ARE A COUPLE ISSUES WITH THIS...THE
 EXISTING SHEDS ARE LOCATED WITHIN THE BOUNDARIES OF THE
 HISTORIC SINGLE FAMILY HOMES AND REQUIRE APPROVAL OF
 THE CITY'S HISOTORIC PRESERVATION DIVISION PRIOR TO ANY
 DEMOLITION / RENOVATION. ADDITIONALLY, THESE WERE NOT
 COUNTED TOWARD THE NORTON'S PARKING REQUIREMENTS AS
 THEY WERE NOT DEEMED A PART OF THE MUSEUM ITSELF;
 HOWEVER, THE SERVICE YARD SHED WAS AND IT'S INCREASE IN
 SIZE DOES AFFECT THE PARKING REQUIREMENT, ETC.
  
 10. THROUGHOUT THE PERMIT SET VARIOUS TRADES ARE USING
 DIFFERENT VARIATIONS OF SITE / LANDSCAPE PLANS AS THE
 BASIS FOR THEIR DRAWINGS. ALL PLANS ACROSS ALL TRADES
 NEED TO BE CONSISTENT AND MATCH...AND THEY ALL SHOULD
 MATCH THOSE PLANS THAT HAVE BEEN APPROVED DURING THE
 PLANNED DEVELOPMENT (PD) PROCESS.
  
 11. AS INDICATED PREVIOUSLY, STAFF HAS SIGNFICANT
 CONCERNS REGARDING SOME OF THE PROPOSED REVISIONS TO
 THE SITE / LANDSCAPE PLANS, SUCH AS RECONFIGURATION OF
 THE PARKING / DROP-OFF AT THE CORNER OF JEFFERSON AND
 DIXIE, PROPOSED HEDGING / FENCING, ETC. THESE ISSUES
 NEED TO BE RESOLVED, INCORPORATED INTO THE REVISED
 PLANS, AND APPROVED THROUGH THE PLANNED DEVELOPMENT
 (PD) PROCESS BEFORE PERMITTING SUCH WORK.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-11-16 Cont ID  
Sent By jroach Date 2016-11-16 Time 14:05 Rev Time 0.00
Received By jroach Date 2016-11-16 Time 14:05 Sent To  
Notes
2016-11-16 14:05:04ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.16.2016
 PERMIT NO.: 16050912
 ADDRESS: 1451 S OLIVE AVENUE
 CONTRACTOR/CONTACT: MICHAEL IZZO
 TELEPHONE NO.:
 SCOPE OF REVIEW: NORTON MUSEUM EXPANSION
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ANY REQUIRED EASEMENTS (I.E. DRAINAGE, UTILITIES,
 PUBLIC ACCESS, ETC.) SHALL BE PROVIDED VIA PLAT OR
 SEPARATE LEGAL INSTRUMENT.
  
 2. ALL CHAINLINK FENCING SHALL BE COMPLETELY SCREENED
 FROM VIEW UTILIZING SHRUBS, HEDGING, OR OTHER
 ACCEPTABLE LANDSCAPE MATERIAL.
  
 3. THE DEVELOPER SHALL BE RESPONSIBLE FOR THE
 INSTALLATION OF IRRIGATION AND LANDSCAPING WITHIN THE
 RIGHTS-OF-WAY ADJACENT TO THE CSPD, AND SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF SUCH IMPROVEMENTS,
 IN PERPETUITY.
  
 4. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS,
 ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM
 EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY. IT
 APPEARS THAT THERE ARE CONFLICTS BETWEEN SUCH UTILITY
 ELEMENTS AND FENCING, ETC. ALL CONFLICTS SHALL BE
 RESOLVED AND SUFFICIENT SCREENING PROVIDED.
  
 5. A MINOR AMENDMENT SHALL BE APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION
 PROVIDING DETAILED LANDSCAPE PLANS FOR CONSTRUCTION
 IMPLEMENTATION. SUCH PLANS SHALL:
  
  A. SPECIFY THE EXACT SPECIES AND LOCATION OF ALL
 TREES, SHRUBS, HEDGES, GROUNDCOVER, ETC. AND BE IN
 COMPLIANCE WITH ARTICLE XIV OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS, EXCEPT FOR THOSE
 PREVIOUSLY WAIVERS GRANTED
  
  B. IDENTIFY THE LOCATION OF ALL TREES/PALMS THAT ARE
 TO BE RELOCATED ON-SITE;
  
  C. IDENTIFY THE LOCATIONS REQUIRED FOR ROOT BARRIERS;
  
  I. INCLUDE A SHRUB PLANTING PLAN FOR THE OFF-SITE
 PARKING LOT LOCATED ON THE WEST SIDE OF SOUTH DIXIE
 HIGHWAY;
  
  II. PROVIDE THE DETAILED LANDSCAPE IMPROVEMENTS
 PROPOSED WITHIN THE SOUTH DIXIE HIGHWAY RIGHT-OF-WAY.
 PLEASE NOTE THAT ANY PLANTINGS SHALL NOT IMPEDE WITH
 THE SITE DISTANCE AND SHALL BE APPROVED BY FDOT.
  
 6. ON SHEET C102, THERE ARE SIGNS SHOWN IN THE SOUTH
 DIXIE HIGHWAY PEDESTRIAN SIDEWALK. PLEASE CLARIFY.
  
 7. IMPROVEMENTS WITHIN THE SOUTH DIXIE RIGHT-OF-WAY
 (INCLUDING NEW CURBING, BOLLARDS, LIGHTING, SIDEWALKS,
 ETC.) SHALL BE SUBJECT TO PERMITTING BY FDOT.
 MAINTENANCE AGREEMENTS MAY BE REQUIRED.
  
 8. ALL IMPROVEMENTS WITHIN THE JEFFERSON ROAD,
 CRANESNEST WAY, AND SOUTH OLIVE AVENUE RIGHT-OF-WAY
 (I.E. ON-STREET PARKING, RESURFACING, ETC.) SHALL BE
 SUBJECT TO A CITY OF WPB RIGHT-OF-WAY PERMIT, OBTAINED
 FROM THE CITY'S ENGINEERING DEPARTMENT.
  
 9. ALL LANDSCAPING SHALL BE SUBMITTED AND REVIEWED AS A
 SEPARATE PERMIT APPLICATION, SUBMITTED TO THE CITY?S
 BUILDING DIVISION.
  
 10. ON SHEET L103, THE EXISTING EAST ENTRANCE HAS A
 LABEL INDICATING "EXISTING PATH TO BE REMOVED", BUT
 DOES NOT SHOW WHAT THE PROPOSED IMPROVEMENTS ARE. THE
 SITE PLAN SHOULD BE AN ACCURATE REFLECTION OF THE
 COMPLETED PROJECT.
  
 11. ON SHEET L102 NOT ALL OF THE PARKING LOT STRIPING
 IS SHOWN. THIS SHALL BE PROVIDED TO ENSURE COMPLIANCE
 WITH THE NUMBER OF PARKING SPACES REQUIRED.
  
 12. PHOTOMETRIC PLAN SHALL BE PROVIDED AND SHALL NOT
 EXCEED 1.0 FOOTCANDLES WHEN MEASURED AT THE PROPERTY
 LINE.
  
 13. ALL SIGNAGE (WALL MOUNTED, FREESTANDING, ETC.)
 SHALL BE SUBMITTED AND REVIEWED UNDER SEPARATE PERMITS.
  
 14. PRIOR TO THE ISSUANCE OF ANY CERTIFICATE OF
 OCCUPANCY:
  
  A. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE WITH
 ALL APPLICABLE STATUTES, REGULATIONS, AND THE CITY?S
 POLICIES AND PROCEDURES.
  
  B. JEFFERSON ROAD, BETWEEN SOUTH DIXIE HIGHWAY AND
 SOUTH OLIVE AVENUE SHALL BE MILLED AND RESURFACED. ALL
 APPLICABLE PERMITS SHALL BE OBTAINED FROM THE CITY?S
 PUBLIC WORKS DEPARTMENT.
  
  C. ANY DAMAGE TO EXISTING UTILITIES RESULTING FROM THE
 DEVELOPER'S CONSTRUCTION ACTIVITIES SHALL BE REPAIRED,
 AT THE DEVELOPER'S EXPENSE.
  
  
 15. SHEET L103, L104 DOES NOT MATCH SHEET L101.
  
 16. SHEET L003 (MASTER PLAN) DOES NOT MATCH THE MASTER
 PLAN APPROVED BY THE CITY COMMISSION. SITE IMPROVEMENTS
 (PARKING,ETC.) HAVE BEEN MODIFIED AND THE BOUNDARY
 IDENTIFYING THE HISTORIC PROPERTY HAS BEEN MOVED.
  
 17. THE DATA TABLE ON SHEET L102 SHOWS SIGNIFICANT
 CHANGES FROM WHAT WAS APPROVED BY THE CITY COMMISSION.
 MODIFICATIONS SHALL BE APPROVED THROUGH A MINOR PD
 AMENDMENT, UNLESS TRIGGERING ONE OF THE PROVISIONS OF
 SEC. 94-207(E)(1) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS. ALSO, THERE ARE
 INCONSISTENCIES IN THE DATA TABLE, SUCH AS SQUARE
 FOOTAGE FOR THE MUSEUM. NOTE THAT AN INCREASE IN SQUARE
 FOOTAGE MAY NECESSITATE ADDITIONAL PARKING, ETC.
  
 18. SHEET E200 DOES NOT MATCH SHEET L101.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-20 Cont ID  
Sent By jroach Date 2016-07-20 Time 13:53 Rev Time 0.00
Received By jroach Date 2016-07-20 Time 13:53 Sent To  
Notes
2016-07-20 13:54:39ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.20.2016
 PERMIT NO.: 16050912
 ADDRESS: 1451 S OLIVE AVENUE
 CONTRACTOR/CONTACT: MICHAEL IZZO
 TELEPHONE NO.:
 SCOPE OF REVIEW: NORTON MUSEUM EXPANSION
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY EXISTING
 TREES, A TREE ALTERATION PERMIT SHALL BE OBTAINED FROM
 THE DEVELOPMENT SERVICES DEPARTMENT ? PLANNING
 DIVISION.
  
 2. ANY REQUIRED EASEMENTS (I.E. DRAINAGE, UTILITIES,
 PUBLIC ACCESS, ETC.) SHALL BE PROVIDED VIA PLAT OR
 SEPARATE LEGAL INSTRUMENT.
  
 3. ALL CHAINLINK FENCING SHALL BE COMPLETELY SCREENED
 FROM VIEW UTILIZING SHRUBS, HEDGING, OR OTHER
 ACCEPTABLE LANDSCAPE MATERIAL.
  
 4. THE DEVELOPER SHALL BE RESPONSIBLE FOR THE
 INSTALLATION OF IRRIGATION AND LANDSCAPING WITHIN THE
 RIGHTS-OF-WAY ADJACENT TO THE CSPD, AND SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF SUCH IMPROVEMENTS,
 IN PERPETUITY.
  
 5. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS,
 ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM
 EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY. IT
 APPEARS THAT THERE ARE CONFLICTS BETWEEN SUCH UTILITY
 ELEMENTS AND FENCING, ETC. ALL CONFLICTS SHALL BE
 RESOLVED AND SUFFICIENT SCREENING PROVIDED.
  
 6. A MINOR AMENDMENT SHALL BE SUBMITTED TO AND APPROVED
 BY THE DEVELOPMENT SERVICES DEPARTMENT ? PLANNING
 DIVISION PROVIDING DETAILED LANDSCAPE PLANS FOR
 CONSTRUCTION IMPLEMENTATION. SUCH PLANS SHALL:
  
  A. SPECIFY THE EXACT SPECIES AND LOCATION OF ALL
 TREES, SHRUBS, HEDGES, GROUNDCOVER, ETC. AND BE IN
 COMPLIANCE WITH ARTICLE XIV OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS, EXCEPT FOR THOSE
 PREVIOUSLY WAIVERS GRANTED
  
  B. IDENTIFY THE LOCATION OF ALL TREES/PALMS THAT ARE
 TO BE RELOCATED ON-SITE;
  
  C. IDENTIFY THE LOCATIONS REQUIRED FOR ROOT BARRIERS;
  
  I. INCLUDE A SHRUB PLANTING PLAN FOR THE OFF-SITE
 PARKING LOT LOCATED ON THE WEST SIDE OF SOUTH DIXIE
 HIGHWAY;
  
  II. PROVIDE THE DETAILED LANDSCAPE IMPROVEMENTS
 PROPOSED WITHIN THE SOUTH DIXIE HIGHWAY RIGHT-OF-WAY.
 PLEASE NOTE THAT ANY PLANTINGS SHALL NOT IMPEDE WITH
 THE SITE DISTANCE AND SHALL BE APPROVED BY FDOT.
  
 7. ALL OF THE LANDSCAPING ON THE APPROVED LANDSCAPE
 PLANS SHALL BE INSTALLED. PLEASE CLARIFY WHY
 SIGNIFICANT AMOUNTS OF THE PREVIOUSLY-APPROVED
 LANDSCAPE PLAN ARE BEING EXCLUDED.
  
 8. A CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN
 SHALL BE REVIEWED AND APPROVED BY THE CITY OF WEST PALM
 BEACH POLICE DEPARTMENT ? CRIME PREVENTION UNIT. A COPY
 OF THE MANAGEMENT PLAN AND APPROVAL LETTER FROM THE
 CRIME PREVENTION UNIT SHALL BE PROVIDED TO THE
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION.
  
 9. THE CITY OF WEST PALM BEACH POLICE DEPARTMENT ?
 CRIME PREVENTION UNIT SHALL REVIEW AND APPROVE ALL
 CONSTRUCTION DRAWINGS TO ENSURE THEY ADHERENCE TO
 GENERALLY-ACCEPTED CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED) PRINCIPLES. A LETTER FROM
 THE CRIME PREVENTION UNIT INDICATING THAT SUCH PLANS
 HAVE BEEN REVIEWED AND APPROVED SHALL BE PROVIDED TO
 THE DEVELOPMENT SERVICES DEPARTMENT ? PLANNING
 DIVISION.
  
 10. ON SHEET C102, PLEASE CLARIFY WHY THE NEW CURB ON
 SOUTH DIXIE HIGHWAY IS NOT IN LINE WITH THE EXISTING
 CURB LINE AT JEFFERSON ROAD AND CRANESNEST WAY. THIS
 DOES NOT MATCH WHAT IS SHOWN ON SHEET L101 AND THE
 APPROVED SITE PLAN.
  
 11. ON SHEET C102, THERE ARE MULTIPLE SIGNS SHOWN IN
 THE SOUTH DIXIE HIGHWAY PEDESTRIAN SIDEWALK. PLEASE
 CLARIFY.
  
 12. IMPROVEMENTS WITHIN THE SOUTH DIXIE RIGHT-OF-WAY
 (INCLUDING NEW CURBING, BOLLARDS, LIGHTING, SIDEWALKS,
 ETC.) SHALL BE SUBJECT TO PERMITTING BY FDOT.
 MAINTENANCE AGREEMENTS MAY BE REQUIRED.
  
 13. ALL IMPROVEMENTS WITHIN THE JEFFERSON ROAD,
 CRANESNEST WAY, AND SOUTH OLIVE AVENUE RIGHT-OF-WAY
 (I.E. ON-STREET PARKING, RESURFACING, ETC.) SHALL BE
 SUBJECT TO A CITY OF WPB RIGHT-OF-WAY PERMIT, OBTAINED
 FROM THE CITY?S ENGINEERING DEPARTMENT.
  
 14. ALL LANDSCAPING SHALL BE SUBMITTED AND REVIEWED AS
 A SEPARATE PERMIT APPLICATION, SUBMITTED TO THE CITY?S
 BUILDING DIVISION.
  
 15. ON SHEET L101, REMOVE ALL LANDSCAPE MATERIAL FROM
 THE PLAN.
  
 16. ON SHEET L101 THERE IS A LOT OF DEMARCATION AND
 MARKINGS THAT ARE NOT CLEARLY IDENTIFIED/LABELED,
 LABELS ARE IN THE WRONG LOCATION, DETAILS ARE NOT
 REFERENCED, ETC.
  
 17. ON SHEET L101, THE EXISTING EAST ENTRANCE HAS A
 LABEL INDICATING ?EXISTING PATH TO BE REMOVED?, BUT
 DOES NOT SHOW WHAT THE PROPOSED IMPROVEMENTS ARE. THE
 SITE PLAN SHOULD BE AN ACCURATE REFLECTION OF THE
 COMPLETED PROJECT.
  
 18. SITE DATA TABLE SHALL BE PROVIDED. THIS WAS ON
 SHEET L102 OF THE APPROVED SITE PLAN BUT IS NO LONGER
 SHOWN.
  
 19. ON SHEET L102 NOT ALL OF THE PARKING LOT STRIPING
 IS SHOWN. THIS SHALL BE PROVIDED TO ENSURE COMPLIANCE
 WITH THE NUMBER OF PARKING SPACES REQUIRED.
  
 20. PHOTOMETRIC PLAN SHALL BE PROVIDED AND SHALL NOT
 EXCEED 1.0 FOOTCANDLES WHEN MEASURED AT THE PROPERTY
 LINE.
  
 21. PLEASE PROVIDE INFORMATION PERTAINING TO THE USE FO
 THE EXTERIOR IMAGE PROJECTOR. WHAT IS THE INTENDED USE?
 WHERE WILL IT BE PROJECTING TO? WHAT INFORMATION WILL
 BE PROJECTED?
  
 22. ALL SIGNAGE (WALL MOUNTED, FREESTANDING, ETC.)
 SHALL BE SUBMITTED AND REVIEWED UNDER SEPARATE PERMITS.
  
 23. PRIOR TO THE ISSUANCE OF ANY CERTIFICATE OF
 OCCUPANCY:
  
  A. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE WITH
 ALL APPLICABLE STATUTES, REGULATIONS, AND THE CITY?S
 POLICIES AND PROCEDURES.
  
  B. JEFFERSON ROAD, BETWEEN SOUTH DIXIE HIGHWAY AND
 SOUTH OLIVE AVENUE SHALL BE MILLED AND RESURFACED. ALL
 APPLICABLE PERMITS SHALL BE OBTAINED FROM THE CITY?S
 PUBLIC WORKS DEPARTMENT.
  
  C. ANY DAMAGE TO EXISTING UTILITIES RESULTING FROM THE
 DEVELOPER?S CONSTRUCTION ACTIVITIES SHALL BE REPAIRED,
 AT THE DEVELOPER?S EXPENSE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved