Plan Review Details - Permit 16050775
Plan Review Stops For Permit 16050775
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By rmcdouga Date 2016-06-13 Time 10:55 Rev Time 0.00
Received By rmcdouga Date 2016-06-13 Time 10:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-31 Cont ID  
Sent By rmcdouga Date 2016-05-31 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2016-05-27 Time 12:44 Sent To P
Notes
2016-05-31 17:53:15REVISION DENIED FOR BUILDING
  
 1) THE WALL SCHEDULE IS MISSING FROM THE REVISED FLOOR
 PLAN SHEET A1.1. FBC 107.2.1
  
 2) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR NEW SIDE
 ENTRY DOOR THAT HAS BEEN ADDED. DOOR #2 IN THE SCHEDULE
 TYPE (VIII) A SINGLE OUTSWING GLAZED FRENCH DOOR PGT
 SERIES 750 REQUIES A PRODUCT APPROVAL THAT HAS BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD. FBC 107.3.4.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-31 Cont ID  
Sent By rmcdouga Date 2016-05-31 Time 17:53 Rev Time 0.00
Received By rmcdouga Date 2016-05-31 Time 17:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-13 Cont ID  
Sent By rmcdouga Date 2016-06-13 Time 10:56 Rev Time 0.00
Received By rmcdouga Date 2016-06-07 Time 10:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-13 Cont ID  
Sent By rmcdouga Date 2016-06-03 Time   Rev Time  
Received By rmcdouga Date 2016-05-18 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By rmcdouga Date 2016-06-13 Time 10:55 Rev Time 0.00
Received By rmcdouga Date 2016-06-13 Time 10:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-31 Cont ID  
Sent By rmcdouga Date 2016-05-31 Time 17:53 Rev Time 0.00
Received By rmcdouga Date 2016-05-31 Time 17:53 Sent To  
Notes
2016-05-31 18:14:06REVISION IS DENIED BY MECHANICAL.
  
 1) THE LOCATION OF THE CONDENSING UNIT HAS BEEN CHANGED
 ON THE FLOOR PLAN FOR UNIT C ON SHEET A-1.2 FROM THAT
 SHOWN ON THE MECHANICAL PLANS. PLEASE COORDINATE THE
 DRAWINGS.
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2016-06-02 Time   Rev Time  
Received By   Date 2016-06-02 Time   Sent To  
Notes
2016-06-07 14:16:11REVIEW BY TKL

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2016-06-03 Time   Rev Time  
Received By   Date 2016-06-03 Time   Sent To  
Notes
2016-06-07 14:19:37REVIEW BY FMITTNER