Plan Review Details - Permit 16050773
Plan Review Stops For Permit 16050773
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By rmcdouga Date 2016-06-13 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2016-06-13 Time 06:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-31 Cont ID  
Sent By rmcdouga Date 2016-05-31 Time 17:50 Rev Time 0.00
Received By rmcdouga Date 2016-05-31 Time 07:16 Sent To P
Notes
2016-05-31 17:50:46REVISION DENIED FOR BUILDING
  
 1) THE WALL SCHEDULE IS MISSING FROM THE REVISED FLOOR
 PLAN SHEET A1.1. FBC 107.2.1
  
 2) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR NEW SIDE
 ENTRY DOOR THAT HAS BEEN ADDED. DOOR #2 IN THE SCHEDULE
 TYPE (VIII) A SINGLE OUTSWING GLAZED FRENCH DOOR PGT
 SERIES 750 REQUIES A PRODUCT APPROVAL THAT HAS BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD. FBC 107.3.4.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-31 Cont ID  
Sent By rmcdouga Date 2016-05-31 Time 16:48 Rev Time 0.00
Received By rmcdouga Date 2016-05-31 Time 16:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-13 Cont ID  
Sent By rmcdouga Date 2016-06-13 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2016-06-07 Time 14:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-03 Cont ID  
Sent By lmarchan Date 2016-06-03 Time 12:17 Rev Time  
Received By lmarchan Date 2016-05-18 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By rmcdouga Date 2016-06-13 Time 08:35 Rev Time 0.00
Received By rmcdouga Date 2016-06-13 Time 06:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-31 Cont ID  
Sent By rmcdouga Date 2016-05-31 Time 16:49 Rev Time 0.00
Received By rmcdouga Date 2016-05-31 Time 07:16 Sent To  
Notes
2016-05-31 17:37:23REVISION IS DENIED BY MECHANICAL.
  
 1) THE RETURN DUCT FOR BEDROOM #2 IS UNDER-SIZED. THE
 PLAN HAS A 6" SUPPLY DUCT WITH A 7" RETURN DUCT FOR
 BEDROOM #2. FBCR M1602.4 REQUIRES THE TRANSFER DUCT TO
 BE 1.5 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY
 DUCT ENTERING THE ROOM.
  
 2) THE LOCATION OF THE CONDENSING UNIT HAS BEEN CHANGED
 ON THE FLOOR PLAN FOR UNIT B ON SHEET A-1.1. PLEASE
 COORDINATE THE DRAWINGS.
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-02 Cont ID  
Sent By tklarge Date 2016-06-02 Time 08:17 Rev Time 0.00
Received By tklarge Date 2016-06-02 Time 06:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-03 Cont ID  
Sent By fmittner Date 2016-06-03 Time 09:02 Rev Time 0.00
Received By fmittner Date 2016-06-03 Time 09:02 Sent To  
Notes
***NONE***