Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-13 Cont ID  
Sent By jwitmer Date 2016-07-13 Time   Rev Time 0.00
Received By jwitmer Date 2016-07-13 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-31 Cont ID  
Sent By jwitmer Date 2016-05-31 Time 17:32 Rev Time 0.00
Received By jwitmer Date 2016-05-31 Time 16:51 Sent To  
Notes
2016-05-31 17:32:30 
 BUILDING PLAN REVIEW
 W. P. B. REVISION: 16050644
 W. P. B. PERMIT: 16030363
 ADD: 901 NORTHPOINT PKWY. SUITE # 105-107
 CONT: CUTTING EDGE BUILDING SYSTEMS, INC.
 TEL: 561-282-8265
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 31/ 2016
 ACTION: DENIED
  
 1) THE REVISION FORM UNDERTHE HEADING OF SCOPE OF
 REVISION INDICATES: CHANGE IMPACT-RATED GLASS BLOCK
 WINDOW TO IMPACT RATED ALUMNIUM STOREFRONT WINDOW.
 PLEASE NOTE THE PLANS DO NOT SHOW A REVISION # 2 WHERE
 A STOREFRONT WINDOW IS TO BE INSTALLED. THE SUBMITTED
 REVISION NOR THE APPROVED PLANS SHOW ANY IMPACT RATED
 GLASS BLOCK WITHIN THE EXTERIOR WALL. ON THE ORIGINAL
 PERMITED PLANS BOTH SHEETS A-1 AND LS-1 OFFICE LABELED
 # 116 SHOWS AN EXTERIOR WALL INFILE. THIS SAME DETAIL
 IS SHOWN ON THE REVISION WITH THE NOTE SEE ELEV. 2/A-2
 WHICH IS A WALL DETAIL FOR INFILE OF AN EXTERIOR WALL.
 PLEASE UPDATE PLANS TO SHOW THE NEW STOREFRONT GLAZING
 SYSTEM.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.4 EXTERIOR WALL ENVELOPE.
 CONSTRUCTION DOCUMENTS FOR ALL BUILDINGS SHALL DESCRIBE
 THE EXTERIOR WALL ENVELOPE IN SUFFICIENT DETAIL TO
 DETERMINE COMPLIANCE WITH THIS CODE. THE
 CONSTRUCTION DOCUMENTS SHALL PROVIDE DETAILS OF THE
 EXTERIOR WALL ENVELOPE.
  
 2) THE SUBMITED YKK STOREFRONT APPROVAL FOR YHS 50 FS
 DOES NOT INDICATE THAT IT IS A MIAMI-DADE NOA OR A
 FLORIDA APPROVAL UNDER THE CURRENT CODE, ONLY THE
 TECHNICAL SHEETS WERE SUBMITTED.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS: (31)(B) WINDOWS.
  
 3) 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 4) THERE SHOULD BE A INCREASE IN THE VALUE OF WORK FROM
 A INFILE EXTERIOR WALL TO IMPACT RATED GLAZING SYSTEM.
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION15110652
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-20 Cont ID  
Sent By vperez Date 2016-05-20 Time 13:41 Rev Time 0.00
Received By vperez Date 2016-05-20 Time 13:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-19 Cont ID  
Sent By pleduc Date 2016-05-19 Time   Rev Time 0.00
Received By pleduc Date 2016-05-18 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-13 Cont ID  
Sent By jwitmer Date 2016-07-13 Time 16:14 Rev Time 0.00
Received By jwitmer Date 2016-07-05 Time 08:38 Sent To  
Notes
2016-07-06 08:39:22JWITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-31 Cont ID  
Sent By shill Date 2016-05-31 Time 17:32 Rev Time  
Received By jwitmer Date 2016-05-16 Time 15:53 Sent To  
Notes
2016-05-26 18:01:49C05
  
  
2016-05-16 15:53:09C12

Review Stop P PLUMBING
Rev No 1 Status N Date 2016-06-01 Cont ID  
Sent By gjohnson Date 2016-05-20 Time 17:49 Rev Time 0.00
Received By gjohnson Date 2016-05-20 Time 17:49 Sent To  
Notes
2016-06-01 13:03:18GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  
 THERE IS NO PLUMBING TO BE REVISED.
  
 PER JAN A. "JJ" WOLFE, JR.
 CGC024813
 CUTTING?EDGE?BUILDING?SYSTEMS, IN
  
2016-05-20 17:54:441ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. WATER COOLER IS IN THE SAME LOCATION THAT IS SHOWN
 ON ORIGINAL PLAN ON THE REVISION FORM IT STATES
 RELOCATE WATER COOLER (+/- 15 LF) PLEASE CLARIFY. WPB
 AMEND. TO FBC SEC. 107.2.1