Plan Review Details - Permit 16050609
Plan Review Stops For Permit 16050609
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-16 Cont ID  
Sent By jwitmer Date 2016-06-16 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2016-06-16 Time 07:15 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-19 Cont ID  
Sent By jwitmer Date 2016-05-19 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2016-05-19 Time 06:32 Sent To  
Notes
2016-05-19 07:09:25BUILDING PLAN REVIEW
 W. P. B. REVISION: 16050609
 W. P. B. PERMIT: 15050569
 ADD: 250 S. AUSTRALIAN AVE.
 CONT: EDD HELMS AIR CONDITIONING & ELEC.
 TEL: (305)653-2530
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAY 19/2016
 ACTION: DENIED
  
 1) SHEET THE PERMIT SET OF PLANS SHEET M3 CHILLER
 MOUNTING DATAIL PROVIDED HOW THE CHILLER WAS TO BE
 MOUNTED TO THE SLAB, THE REVISON NO LONGER PROVIDES
 THIS INFORMATION, NOR IS THE AREA CLOUDED WITH A
 REVISION WHERE THE MOUNTING INFORMATION WAS REMOVED.
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-16 Cont ID  
Sent By mvaldes Date 2016-06-16 Time 09:10 Rev Time 0.00
Received By mvaldes Date 2016-06-16 Time 09:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-16 Cont ID  
Sent By mvaldes Date 2016-06-16 Time 09:11 Rev Time 0.00
Received By mvaldes Date 2016-06-10 Time 11:18 Sent To  
Notes
2016-06-10 11:18:39RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-10 Cont ID  
Sent By lmarchan Date 2016-05-19 Time 11:18 Rev Time 0.00
Received By lmarchan Date 2016-05-16 Time 09:42 Sent To  
Notes
2016-05-17 09:43:05REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By ccole Date 2016-06-13 Time 09:36 Rev Time 0.00
Received By ccole Date 2016-06-13 Time 09:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-18 Cont ID  
Sent By ccole Date 2016-05-18 Time 11:01 Rev Time 0.00
Received By ccole Date 2016-05-18 Time 11:01 Sent To  
Notes
2016-05-18 11:07:071ST REVIEW: FBC 2014 MECHANICAL
 REVISION #16050609
 MASTER # 15050569
 5/18/16
  
 1) M-3: THE REVISED PLAN DOES NOT INDICATE HOW THE
 CHILLERS WILL BE ANCHORED TO THE SLAB.
 2) M-3: PROVIDE AN EQUIPMENT SCHEDULE FOR THE VAV AND
 INDICATE HOW THE UNIT WILL BE CONNECTED AND SUPPORTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  