Plan Review Details - Permit 16050577
Plan Review Stops For Permit 16050577
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-09 Cont ID  
Sent By wjolin Date 2016-08-09 Time 14:37 Rev Time 0.00
Received By wjolin Date 2016-08-09 Time 14:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-27 Cont ID  
Sent By wjolin Date 2016-05-27 Time 11:50 Rev Time 0.00
Received By wjolin Date 2016-05-27 Time 11:50 Sent To  
Notes
2016-05-27 11:50:195444 NORTH HAVERHILL ROAD (STADIUM & NATIONALS) -
 PERMIT #16050576
 5454 NORTH HAVERHILL ROAD (ASTROS) - PERMIT #16050577
 5450 NORTH HAVERHILL ROAD (TEAM STORE) - PERMIT
 #16050578
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: THE PLANS INDICATE A LOCATION OF "PALM BEACH"
 WHICH IS A TOWN EAST OF THE CITY OF WEST PALM BEACH.
 THE PLANS ALSO INCORRECTLY INDICATE A PLAN ADDRESS OF
 "5300 HAVERHILL ROAD" ON SOME SHEETS AND NONE OF THE
 SHEETS INDICATE THE ADDRESS OF 5454 NORTH HAVERHILL
 ROAD. PLEASE CORRECTLY ADDRESS EACH OF THE PLANS.
  
 GENERAL: FOR EACH AREA EXPOSED TO STRUCTURE (NO
 CEILING) INDICATE IF THE SPACE IS OBSTRUCTED
 CONSTRUCTION OR UNOBSTRUCTED CONSTRUCTION AND INDICATE
 THE MAXIMUM SPRINKLER DISTANCE LOCATED BELOW THE
 STRUCTURE OR ROOF DECK (IF OBSTRUCTED CONSTRUCTION).
  
 SHEET FP-2 -- FIELD EQUIPMENT STORAGE #11001 (REMOTE
 AREA #1): THE HYDRAULIC AREA SHALL BE MEASURED PARALLEL
 TO THE BRANCH LINES PER NFPA 13. THE ROOM DESIGN METHOD
 CANNOT BE USED AS THERE IS NO FIRE RATED WALLS
 SEPARATING THE ROOMS. SPRINKLERS ARE LOCATED AT AN
 ELEVATION OF ROUGHLY 12 FEET ABOVE FINISHED FLOOR;
 HOWEVER, THE AREA IS CALCULATED AS ORDINARY HAZARD
 GROUP 1 LIMITING THE STORAGE OF COMBUSTIBLES TO 8 FEET.
 THIS AREA MAY NEED TO BE CALCULATED AS ORDINARY HAZARD
 GROUP 2 TO PERMIT STORAGE GREATER THAN 8 FEET IN HEIGHT
 OR MEASURES SHALL BE SPECIFIED AS TO HOW THE
 COMBUSTIBLES WILL BE LIMITED TO 8 FEET.
  
 SHEET FP-2 -- MAINTENANCE SHOP #11125 (REMOTE AREA #2):
 THE HYDRAULIC AREA SHALL BE MEASURED PARALLEL TO THE
 BRANCH LINES PER NFPA 13. THE ROOM DESIGN METHOD CANNOT
 BE USED AS THERE IS NO FIRE RATED WALLS SEPARATING THE
 ROOMS AND THE AREA-REDUCTION METHOD FOR QUICK RESPONSE
 SPRINKLERS CANNOT BE USED DUE TO THE EXTRA HAZARD
 CLASSIFICATION. THE SPRINKLERS PROTECTING THE EXTRA
 HAZARD AREA (DENSITY 0.6 GPM/SF) ARE EXTENDED COVERAGE
 (K=11.2); HOWEVER, ACTUAL DENSITIES PROVIDED IN THE
 HYDRAULIC CALCULATIONS (0.27 GPM/SF OR 52.5 GPM) ARE
 WAY BELOW THE DESIGN DENSITY. FOR EXAMPLE SPRINKLER
 #101 IS PROTECTING AN SXL AREA OF ROUGHLY 12.5' X 7.0'.
 BEING EXTENDED COVERAGE, THE SPRINKLER AREA SHALL BE
 ROUNDED UP AND CALCULATED USING THE "RULE OF SQUARES"
 PER NFPA 13 SECTION 8.8.2.1.2. THIS WILL RESULT IN A
 COVERAGE AREA OF 14'X14' OR 196 SQUARE FEET AND A
 NEEDED FLOW OF 118 GPM PER SPRINKLER TO OBTAIN A DESIGN
 DENSITY OF 0.6 GPM/SF. ALSO THE TYCO MODEL ELOC K=11.2
 THAT WAS SUBMITTED IS ONLY LISTED FOR PROTECTING LIGHT
 HAZARD OCCUPANCIES, THIS WILL ALSO AFFECT REMOTE AREAS
 3 AND 4.
  
 SHEET FP-2: THE SPRINKLER SCHEDULE INDICATES THE
 SPRINKLER MODEL FOR THE K=11.2 TO BE "FRB;" HOWEVER,
 THE ACTUAL MODEL SUBMITTED IS THE "ELOC."
  
 SHEET FP-4: PLAN SCALE IS INDICATED AS 1/8"=1'-0"
 HOWEVER, THE PLAN IS NOT SCALABLE.
  
 SHEET FP-5: THE NATIONALS LOCKER ROOM SHOWS 5 AND 6
 SPRINKLERS SUPPLIED BY 1-INCH BRANCH LINES. THIS
 CONFIGURATION IS NOT SUPPORTED BY HYDRAULIC
 CALCULATIONS.
  
 SHEET FP-5: WEIGHT ROOM #11318; NO SPRINKLER COVERAGE
 FOR THE EAST PORTION OF THE ROOM.
  
 SHEET FP-5: STORAGE ROOM #11325, STORAGE #11220 AND
 LAUNDRY ROOM #11313 THE SXL COVERAGE FOR ONE OR MORE
 SPRINKLERS EXCEEDS 130 SQ.FT.
  
 SHEET FP-6: APPEARS THERE IS NO SPRINKLER COVERAGE IN
 JANITOR #11430 OR NOOK DIRECTLY WEST OF THE JANITOR'S
 ROOM.
  
 SHEET FP-8: STORAGE ROOM #11714 AND LAUNDRY #11706 THE
 SXL COVERAGE FOR ONE OR MORE SPRINKLERS EXCEEDS 130
 SQ.FT.
  
 SHEET FP-12: LOBBY #11408 IS OPEN TO THE LEVEL BELOW SO
 THE SPRINKLERS SHALL BE SUPPLIED FROM THE FLOOR BELOW
 TO AVOID LOCATION CONFUSION WHEN THE FIRE IS ON THE
 CLUBHOUSE LEVEL BUT THE FLOW SWITCH ALARM SHOWS THE
 FIRE IS ON THE UPPER CONCOURSE LEVEL. COORDINATION IS
 NEEDED WITH THE ARCHITECT -- SHEET A2.324 1ST FLOOR
 LOBBY #11408 IS OPEN TO THE SECOND FLOOR CORRIDOR
 #12412B. PER SECTION 8.6.9.2 UNENCLOSED VERTICAL
 OPENINGS CREATED BY CONVENIENCE STAIRWAYS SHALL BE
 PERMITTED AS FOLLOWS: 1) THE CONVENIENCE STAIR OPENING
 SHALL BE PROTECTED IN ACCORDANCE WITH THE METHOD
 DETAILED FOR THE PROTECTION OF VERTICAL OPENINGS IN
 NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
 SYSTEMS UTILIZING 18" DEEP DRAFT CURTAINS AND CLOSELY
 SPACED SPRINKLERS.
  
 SHEET FP-15: LOBBY #11711 IS OPEN TO THE LEVEL BELOW SO
 THE SPRINKLERS SHALL BE SUPPLIED FROM THE FLOOR BELOW
 TO AVOID LOCATION CONFUSION WHEN THE FIRE IS ON THE
 CLUBHOUSE LEVEL BUT THE FLOW SWITCH ALARM SHOWS THE
 FIRE IS ON THE UPPER CONCOURSE LEVEL. COORDINATION IS
 NEEDED WITH THE ARCHITECT -- SHEET A2.227: 1ST FLOOR
 LOBBY #11711 IS OPEN TO THE SECOND FLOOR RECEPTION
 #12704. PER SECTION 8.6.9.2 UNENCLOSED VERTICAL
 OPENINGS CREATED BY CONVENIENCE STAIRWAYS SHALL BE
 PERMITTED AS FOLLOWS: 1) THE CONVENIENCE STAIR OPENING
 SHALL BE PROTECTED IN ACCORDANCE WITH THE METHOD
 DETAILED FOR THE PROTECTION OF VERTICAL OPENINGS IN
 NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
 SYSTEMS UTILIZING 18" DEEP DRAFT CURTAINS AND CLOSELY
 SPACED SPRINKLERS.
  
 REMOTE AREA AND HYDRAULIC CALCULATIONS (SPECIFICALLY
 REMOTE AREAS #1, 2, 7,8, 10,12 & 14): NO AREAS INDICATE
 THE USE OF THE ROOM DESIGN METHOD AND ONLY REMOTE AREA
 #9 INDICATES THE USE OF THE AREA REDUCTION METHOD FOR
 QUICK RESPONSE SPRINKLERS; HOWEVER SEVERAL OTHER AREAS
 DO NOT CALCULATE A FULL 1,500 SQ.FT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-19 Cont ID  
Sent By ccole Date 2016-08-19 Time 16:59 Rev Time 0.00
Received By ccole Date 2016-08-05 Time 13:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-17 Cont ID  
Sent By ccole Date 2016-06-17 Time 13:54 Rev Time 0.00
Received By ccole Date 2016-05-27 Time 11:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-19 Cont ID  
Sent By ccole Date 2016-08-19 Time 16:58 Rev Time 0.00
Received By ccole Date 2016-08-19 Time 16:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-17 Cont ID  
Sent By ccole Date 2016-06-17 Time 13:53 Rev Time 0.00
Received By ccole Date 2016-06-17 Time 13:53 Sent To  
Notes
2016-06-17 13:54:421ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050577
 5/27/16
  
 1) COMPLY WITH FIRE DEPT. REVIEW COMMENTS.
 2) PLEASE UPLOAD AND ADD THE SPECS FOR THE QUICK
 RESPONSE DRY SPRINKLER HEADS TO THE THE SPRINKLER
 SUBMITTAL PACKAGE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-09-12 Cont ID  
Sent By ccole Date 2016-09-12 Time 08:25 Rev Time 0.00
Received By ccole Date 2016-09-12 Time 08:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-08-19 Cont ID  
Sent By ccole Date 2016-08-19 Time 16:59 Rev Time 0.00
Received By ccole Date 2016-08-19 Time 16:59 Sent To  
Notes
2016-08-19 17:02:36PERMIT #16050577
 8/19/16
  
 MASTER PLANS #16050576 MUST BE ELECTRONICALLY SIGNED
 AND SEALED BY A FL. LICENSED ENGINEER.
  