Plan Review Details - Permit 16050413
Plan Review Stops For Permit 16050413
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-09-15 Cont ID  
Sent By jwitmer Date 2016-09-15 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2016-09-15 Time 06:00 Sent To  
Notes
2016-09-15 07:34:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050413
 ADD: 4800 DREHER TRAIL N
 CONT: GAST CONSTRUCTION
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. SEPT. 15/ 2016
 ACTION: BUILDING PROVISO
  
 1) BEFORE A CERTIFICATE OF COMPLETION WILL BE ISSUED A
 UNITY OF TITLE WILL BE REQUIRED, THE BUILDING SETS ON 2
 LOTS. SEE PALM BEACH COUNTY PROPERTY APPRAISERS SITE,
 PCN 74-43-44-04-00-000-3010 & 74-43-44-04-00-005-0020.
 BUILDINGS CANNOT BE BUILT ON 2 LOTS, PROPERTY LINES.
 2014 FBC-B TABLE 602. A UNITY OF TITLE IS REQUIRED. A
 HOLD WILL BE PUT ON THE PRINTING OF A CERTIFICATE OF
 COMPLETION. SEE ATACHMENT, E-MAIL SENT 08/30/2016 VINCE
 NOEL CITY SURVEYOR.
 .
 2) HOLD FOR FINAL INSPECTION, FLOOD ZONE CERTIFICATE
 REQUIRED FOR ALL SLABS, INTERIOR FINISH FLOOR, AND ANY
 EXTERIOR SERVICE EQUIPMENT PADS (A/C PADS, GENERATORS,
 ETC. THIS BUILDING LIES IN AN A7 (ELEV. 12.0 NGVD)
 FLOOD ZONE. SECTION 94-546 (B)(2) NONRESIDENTIAL
 CONSTRUCTION. 2014 FLORIDA BUILDING CODE W 2014 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 110.3 REQUIRED INSPECTIONS.
 A. BUILDING. 6. FINAL INSPECTION. TO BE MADE AFTER THE
 BUILDING IS COMPLETED AND READY FOR OCCUPANCY. 6.1.
 LOWEST FLOOR ELEVATION. IN FLOOD HAZARD AREAS, AS PART
 OF THE FINAL INSPECTION, A FINAL CERTIFICATION OF THE
 LOWEST FLOOR ELEVATION SHALL BE SUBMITTED TO THE
 AUTHORITY HAVING JURISDICTION.
  
 3) DEFERRED SUBMITTALS 107.3.4.2. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.1. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-05 Cont ID  
Sent By   Date 2016-08-05 Time   Rev Time 0.00
Received By jwitmer Date 2016-08-05 Time 11:06 Sent To  
Notes
2016-08-05 12:25:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050413
 ADD: 4800 DREHER TRAIL N
 CONT: GAST CONSTRUCTION
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. AUGUST 05/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST. PLEASE SUBMIT A SURVEY SHOWING THE
 LOCATION OF THE BUILDING THAT HOUSES THE WEST PALM
 BEACH GARDEN CLUB.
  
 1A) 2ND REQUEST. THE BUILDING APPEARS TO BE LOCATED ON
 (2) DIFFERENT LOTS. SEE PALM BEACH COUNTY PROPERTY
 APPRAISERS SITE, PCN 74-43-44-04-00-000-3010 &
 74-43-44-04-00-005-0020. BUILDINGS CAN NOT BE BUILT ON
 2 LOTS, PROPERTY LINES. 2014 FBC-B TABLE 602. A UNITY
 OF TITLE IS REQUIRED.
  
 1B) 2ND REQUEST. PLEASE ALSO ON THE SURVEY INDICATE THE
 BOUNDARIES OF THE A7 FLOOD ZONE AND THE FINISHED FLOOR
 ELEVATIONS OF THE BUILDING AND SURROUNDING MECHANICAL
 EQUIPMENT PADS. IT APPEARS THIS BUILDING LIES IN THE
 FLOOD ZONE. SECTION 94-546 (B)(2) NONRESIDENTIAL
 CONSTRUCTION. PLEASE NOTE THAT A FLOOD ELEVATION
 CERTIFICATE WAS SUBMITTED AND IF THIS RENOVATION IS
 CONSIDERED SUBSTANTIAL IMPROVEMENT THEN THE LOWEST
 ELEVATION OF EQUIPMENT SERVING THE STRUCTURE FOUND TO
 BE 11.5 FT. NGVD ON THE ELEVATION CERTIFICATE WILL ALSO
 NEED TO BE ELEVATED TO THE MINIMUM ELEVATION OF 12.5
 FT. NGVD.
  
 1C)2ND REQUEST. THE P. B. C. PROPERTY APPRAISERS OFFICE
 DOES NOT PROVIDE THE CURRENT VALUE OF THE STRUCTURE
 BEFORE THE ALTERATIONS THAT ARE TO TAKE PLACE. UNTIL A
 VALUE FOR THE STRUCTURE IS KNOWN, SUBSTANTIAL
 IMPROVEMENT FOR THIS BUILDING CANNOT BE DETERMINED, NOR
 IF COMPLIANCE WITH SUBSTANTIAL IMPROVEMENT IS REQUIRED.
 SEE CITY WEST PALM BEACH MUNI-CODE;
 SECTION 94-611 DEFINITIONS. SUBSTANTIAL IMPROVEMENT.
 SECTION 94-546 (B)(2) NONRESIDENTIAL CONSTRUCTION.
 2014 FBC-B 1612.4 DESIGN AND CONSTRUCTION. THE DESIGN
 AND CONSTRUCTION OF BUILDINGS AND STRUCTURES LOCATED IN
 FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH HAZARD
 AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF ASCE 7
 AND WITH ASCE 24.
  
 2-4) COMPLIED.
  
 5) 2ND REQUEST. MISSING PRODUCT APPROVALS: 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 6) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) 2ND REQUEST, THE STRUCTURAL SHEETS SHOW STEEL
 FRAMING TO BE ADDED TO A BAR JOIST SYSTEM, M5 NOW SHOWS
 ANCHORING OF THE RTU?S CURB TO A CONCRETE DECK AND
 ANCHORING THE CURB TO THE DECK WITH REDHEADS. HOW IS
 THE DECK PART OF THE MWFRS? 2014 FBC-B 1604.4 ANALYSIS.
  
 1ST ROUND OF COMMENTS. SHEET M2 SHOWS ROOFTOP UNITS
 THAT WILL SIT ON ROOF TOP CURBS. NEITHER THE MECHANICAL
 NOR STRUCTURAL SHEETS SHOW HOW THESE UNITS ARE TO BE
 MOUNTED. SHEET M2 NOTE # 1 INDICATES THESE RTU'S ARE
 NEW UNITS. PLEASE PROVIDE FOR THE ADDITIONAL FRAMING
 AROUND THE NEW ROOF TOP PENETRATIONS, IF FRAMING
 MEMBERS WERE CUT, THE REINFORCEMENT AND HOW THE
 ADDITIONAL POINT LOADS WERE HANDLED? PLEASE ALSO
 PROVIDE THE CONNECTION OF THE ROOFTOP CURB TO THE ROOF
 FRAMING MEMBERS, THE ANCHORAGE OF THE RTU TO THE CURB.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 8-9) COMPLIED
  
 10) THE PROJECT INDICATES A DOLLAR VALUE OF
 $400,000.00. PLEASE PROVIDE A LIST OF ALL ACCESSIBLE
 FEATURES THAT ARE GOING TO BE CORRECTED AND THEIR
 DOLLAR AMOUNT. UP TO $80,000.00 IN VALUE. AT THIS POINT
 THE DISPROPORTIONATE COST HAVE BEEN MET. CONTRACTOR IS
 TO SUBMIT AN ITEMIZED LIST OF ELEMENTS WHERE THESE
 FUNDS HAVE BEEN SPENT IN ACCESSIBLE UPGRADES. THE LIST
 SHOULD FOLLOW THE SAME ORDER AS IN SECTION 202.4.2 IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION15110652
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-01 Cont ID  
Sent By jwitmer Date 2016-06-01 Time 13:25 Rev Time 0.00
Received By jwitmer Date 2016-06-01 Time 09:05 Sent To  
Notes
2016-06-01 09:50:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050413
 ADD: 4800 DREHER TRAIL N
 CONT: GAST CONSTRUCTION
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 01/ 2016
 ACTION: DENIED
  
 1) PLEASE SUBMIT A SURVEY SHOWING THE LOCATION OF THE
 BUILDING THAT HOUSES THE WEST PALM BEACH GARDEN CLUB.
  
 1A) THE BUILDING APPEARS TO BE LOCATED ON (2) DIFFERENT
 LOTS. SEE PALM BEACH COUNTY PROPERTY APPRAISERS SITE,
 PCN 74-43-44-04-00-000-3010. BUILDINGS CAN NOT BE BUILT
 ON 2 LOTS, PROPERTY LINES. 2014 FBC-B TABLE 602.
  
 1B) PLEASE ALSO ON THE SURVEY INDICATE THE BOUNDRIES OF
 THE A7 FLOOD ZONE AND THE FINISHED FLOOR ELEVATIONS OF
 THE BUILDING AND SURROUNDING MECHANICAL EQUIPMENT PADS.
 IT APPEARS THIS BUILDING LIES IN THE FLOOD ZONE.
 SECTION 94-546 (B)(2) NONRESIDENTIAL CONSTRUCTION.
  
 1C) THE P. B. C. PROPERTY APPRAISERS OFFICE DOES NOT
 PROVIDE THE CURRENT VALUE OF THE STRUCTURE BEFORE THE
 ALTERATIONS THAT ARE TO TAKE PLACE. UNTIL A VALUE FOR
 THE STRUCTURE IS KNOWN, SUBSTANTIAL IMPROVEMENT FOR
 THIS BUILDING CAN NOT BE DETERMINED, NOR IF COMPLIANCE
 WITH SUBSTANTIAL IMPROVEMENT IS REQUIRED.
 SEE CITY WEST PALM BEACH MUNI-CODE;
 SECTION 94-611 DEFINITIONS. SUBSTANTIAL IMPROVEMENT.
 SECTION 94-546 (B)(2) NONRESIDENTIAL CONSTRUCTION.
 2014 FBC-B 1612.4 DESIGN AND CONSTRUCTION. THE DESIGN
 AND CONSTRUCTION OF BUILDINGS AND STRUCTURES LOCATED IN
 FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH HAZARD
 AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF ASCE 7
 AND WITH ASCE 24.
  
 2) UNDER THE 1ST SUBMITION OF PLANS THERE WERE NO
 ENERGY CALCULATIONS SUBMITTED, PLEASESHOW HOW
 COMPLIANCE WITH FBC-ENERGY WILL BE ACHIEVED.
 C401.2.1 APPLICATION TO EXISTING BUILDINGS. ADDITIONS,
 ALTERATIONS AND REPAIRS TO EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE FOLLOWING:
 1. SECTIONS C402, C403, C404 AND C405; OR
 2. ANSI/ASHRAE/IESNA 90.1.
  
 DEFINITIONS: RENOVATED BUILDING. A RESIDENTIAL OR
 NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT
 VARIES OR CHANGES INSULATION, HVAC SYSTEMS, WATER
 HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS,
 PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE.
  
 3) SHEET S1 WIND LOAD SCHEDULE (FLAT ROOF):
  
 3A) THE SCHEDULE DOES NOT INDICATE IF THE VALUES GIVEN
 ARE IN VULT OR VASD. NOR DOES THE CHART GIVE THE SQUARE
 FT EACH VALUE REPRESENTS? ADDITIONAL INFORMATION IS
 REQUIRED.107.2.1.3. ASCE 7-10 COMPONENTS & CLADDING
 FIGURE 30.5.1.
  
 3B) THIS SAME CHART SHOWS THE SAME NEGATIVE VALUE FOR
 ROOF ZONES 1 & 2, A -63.7 PSF ASSUMED VULT BUT ZONE 3
 SHOWS A VALUE OF -96.1 WHICH WOULD BE CORRECT IF THIS
 WAS IN VASD FOR 10 SQ. FT. ASCE 7-10 COMPONENTS &
 CLADDING FIGURE 30.5.1.
  
 3C) FOR WALL ZONES 4 & 5 IF THE VALUES GIVEN FOR
 NEGATIVE PRESSURES ARE 10 SQ. FT./ EXPOSUE C/ VASD THE
 PRESSURES ARE LOW. ASCE 7-10 COMPONENTS & CLADDING
 FIGURE 30.5.1.
  
 4) SHEET S1 WIND LOAD SCHEDULE 4:12 (HIP);
  
 4A) THE SCHEDULE DOES NOT INDICATE IF THE VALUES GIVEN
 ARE IN VULT OR VASD. NOR DOES THE CHART GIVE THE SQUARE
 FT EACH VALUE REPRESENTS? ADDITIONAL INFORMATION IS
 REQUIRED.107.2.1.3. ASCE 7-10 COMPONENTS & CLADDING
 FIGURE 30.5.1.
  
 4B) ROOF PRESSURES GOOD FOR ROOF ZONES 1,2 & 3 FOR
 EXPOSURE C, 15 FT. MEAN ROOF, HIP ROOF IF FIGURED IN
 VASD @ 10 SQ. FT. THE ISSUE IS WHY THERE IS DIFFERENT
 WALL PRESSURES IN WALL ZONES 4 & 5 ? ASCE 7-10
 COMPONENTS & CLADDING FIGURE 30.5.1.
  
 5) MISSING PRODUCT APPROVALS: 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 6) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7) SHEET M2 SHOWS ROOFTOP UNITS THAT WILL SIT ON ROOF
 TOP CURBS. NEITHER THE MECHANICAL NOR STRUCTURAL SHEETS
 SHOW HOW THESE UNITS ARE TO BE MOUNTED. SHEET M2 NOTE #
 1 INDICATES THESE RTU'S ARE NEW UNITS. PLEASE PROVIDE
 FOR THE ADDITIONAL FRAMING AROUND THE NEW ROOF TOP
 PENETRATIONS, IF FRAMING MEMBERS WERE CUT, THE
 REINFORCEMENT AND HOW THE ADDTIONAL POINT LOADS WERE
 HANDLED? PLEASE ALSO PROVIDE THE CONNECTION OF THE
 ROOFTOP CURB TO THE ROOF FRAMING MEMBERS, THE ANCHORAGE
 OF THE RTU TO THE CURB.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 8) SHEET A1:
  
 8A) THE PLANS INDICATE AN OCCUPANT LOAD OF 163 WHICH
 REQUIRES 2 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH
 2014 FBC-ACCESSIBILITY CODE 207.1
 MEANS OF EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF
 THE INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION) (INCORPORATED BY
 REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1). .
 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF EGRESS IS
 REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO ACCESSIBLE MEANS OF EGRESS. SHOW THE EXIT
 DISCHAGE TO A PUBLIC WAY OR YARD FOR BOTH EXITS.
  
 8B) THERE APPEARS TO BE A ROADWAY ON THE LEFT SIDE OF
 THE BUILDING WHERE SECTIONS OF SIDEWALK ARE BEING
 CONSTRUCTED AS WELL AS A NEW ACCESBILE RAMP. IS THIS A
 STREET ? IF SO THE NEW SECTION OF THE SIDEWALK WOULD
 NEED TO SHOW COMPLIANCE WITH ACCESSIBILTY CODE
 705.1-705.2.
  
 8C) THE RAMP TO THE LEFT OF THE BUILDING (LEEDS TO DOOR
 101A) DOES NOT SHOW ANY DIMENSIONS FOR THE RAMP, NOR
 LANDINGS. SHOW COMPLIANCE WITH:
 405.3 CROSS SLOPE.
 405.4 FLOOR OR GROUND SURFACES.
 405.5 CLEAR WIDTH
 405.7 LANDINGS.
 FIGURE 405.7 RAMP LANDINGS
 405.7.4 CHANGE IN DIRECTION.
 405.7.5 DOORWAYS.
  
 8C) THE ACCESSIBLE RAMP (AT DOOR 105) TO THE RIGHT SIDE
 OF BUILDING HAS THE SAME ACCESSIBLR ISSUESAS LISTED
 ABOVE.
  
 8D) THE STAIRS AND LANDING AT DOOR 101B PLEASE ADD
 DIMENSIONS TO THE RIGHT OF THE DOOR IT APPEARS THERE IS
 ONLY 1 FOOT TO THE HANDRAIL. THE 2014 ACCESSIBILITY
 CODE DOES NOT COMPLY WITH SECTION 404.2.4, & TABLE
 404.2.4.1.
  
 8E) DOORS 103 & 104 BOTH LACK THE 18 INCHES ON THE
 LATCH SIDE OF THE DOOR FOR MANEUVERING CLEARANCES.
 ACCESS. CODE 404.2.4.
  
 8F) PLEASE NOTE THERE IS NO LIFE SAFETY SHEET SHOWING A
 FLOOR LAYOUT FOR THE MULTI-PURPOSE ROOM OR THE 2
 MEETING ROOMS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
  
 8G) PLEASE PROVIDE IF THE ISLAND IN THE WARMING KITCHEN
 IS TO BE USED FOR ACCESS. CODE. 904.5 FOOD SERVICE
 LINES. COUNTERS IN FOOD SERVICE LINES SHALL COMPLY WITH
 904.5.
  
 8H) THE MULTIPURPOSE ROOM IF USED AS A DINING ROOM
 WOULD ALSO NEED TO SHOW COMPLIANCE WITH: 2014 ACCESS.
 CODE 226.1. WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 8I) THE MULTIPURPOSE ROOM IF USED AS A DINING ROOM
 WOULD ALSO NEED TO SHOW COMPLIANCE WITH: 2014 ACCESS.
 CODE 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 9) THE PLANS DID NOT PROVIDE ANY SIGNAGE FOR
 ACCESSIBILITY.2014 FBC-ACCESS CODE 216.1 GENERAL. SIGNS
 SHALL BE PROVIDED IN ACCORDANCE WITH 216 AND SHALL
 COMPLY WITH 703.
  
  
 10) THE PROJECT INDIACATES A DOLLAR VALUE OF
 $400,000.00. PLEASE PROVIDE A LIST OF ALL ACCESSIBLE
 FEATURES THAT ARE GOING TO BE CORRECTED AND THEIR
 DOLLAR AMOUNT. UP TO $80,000.00 IN VALUE. AT THIS POINT
 THE DISPROPORTIONATE COST HAVE BEEN MET. 202.4.2
 ACCESSIBLE FEATURES IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION15110652
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-06 Cont ID  
Sent By vperez Date 2016-09-06 Time 08:00 Rev Time 0.00
Received By vperez Date 2016-09-06 Time 08:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-28 Cont ID  
Sent By vperez Date 2016-07-28 Time 08:03 Rev Time 0.00
Received By vperez Date 2016-07-28 Time 07:57 Sent To  
Notes
2016-07-28 08:06:03ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PROVISO COMMENTS:
  
 1. PLEASE SHOW CIRCUIT # FOR EXHAUST FAN #4 ON ASBUILT
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-19 Cont ID  
Sent By vperez Date 2016-05-19 Time 11:11 Rev Time 0.00
Received By vperez Date 2016-05-19 Time 10:15 Sent To  
Notes
2016-05-19 11:28:29INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS (GATES), CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION.
 3. LABEL MAINS TO INDICATE MAIN 1 OF 2 AND 2 OF 2, FOR
 THE 400A SERVICE SHOWN. NEC 230.2
 4. SHOW ON PANEL BOARD SCHEDULE ALL BRANCH CIRCUIT
 CONDUCTOR SIZES. FBC 107.3.5
 5. LABEL CIRCUIT LA-15 TO BE GFCI PROTECTED FOR THE
 DRINKING FOUNTAIN. NEC 422.52
 6. PLEASE LABEL THE KITCHEN RECEPTACLE OUTLET WITHIN
 6FT OF SINK TO BE GFCI PROTECTED. NEC 210.8B2 AND NOTE
 THAT ALL 125V 20A RECEPTACLES WITHIN THE FOOD
 PREPARATION AREA TO BE LABELED GFCI ALSO. NEC 210.8B5
 7. ADDRESS ALL FIRE COMMENTS RELATED TO ELECTRICAL
 SHEETS, EXIT LIGHTING, HOOD AND FIRE ALARM DRAWINGS.
 8. PROVIDE A GENERAL NOTE TO INDICATE THE REQUIREMENTS
 OF NEC 410.130G1- DISCONNECTING MEANS FOR ALL DOUBLE
 ENDED LAMPS.
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-08 Cont ID  
Sent By pleduc Date 2016-08-08 Time   Rev Time 0.00
Received By pleduc Date 2016-08-08 Time 12:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-16 Cont ID  
Sent By pleduc Date 2016-05-16 Time   Rev Time 0.00
Received By pleduc Date 2016-05-16 Time 15:50 Sent To  
Notes
2016-05-16 16:41:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET CVR - THERE IS NO INDICATION OR REFERENCE TO
 REVIEW OR COMPLIANCE WITH THE FLRODA FIRE PREVENTION
 CODE. PLEASE ENSURE REVIEW AND COMPLIANCE AND PROVIDE A
 NOTE UNDER DESIGN STANDARDS.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) SHEET A 1 - THERE IS AN INDICATION IN THE KITCHEN
 AREA OF A WARMING OVEN. PLEASE PROVIDE THE
 MANUFACTURER'S EQUIPMENT SPEC AND INSTALLATION GUIDE AS
 TO REVIEW FOR PROPER VENTING AND/OR A FIRE SUPPRESSION
 SYSTEM IN COMPLAINCE WITH NFPA 96.
  
 IN ADDITION, PLEASE PROVIDE PROPOSED MENU AND OR FOOD
 ITEMS.
  
 CHAPTER 9 BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTS OF THIS STANDARD.
  
  
 3) SHEET A 1 - A HANDRAIL IS INDICATED BY DOOR 101B;
 HOWEVER, THERE IS NO HANDRAIL DETAIL OR REFERENCE SHEET
 CALL OUT.
  
 PLEASE PROVIDE HANDRAIL DETAIL IN COMPLIANCE WITH NFPA
 101, CHAPTER 7, 7.2.2.4.4 HANDRAIL DETAILS; INCLUDING
 BUT NOT LIMITED TO,
  
 7.2.2.4.4.1 NEW HANDRAILS ON STAIRS SHALL NOT BE LESS
 THAN 34 IN. AND NOT MORE THAN 38 IN. ABOVE THE SURFACE
 OF THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE
 RAIL FROM THE LEADING EDGE OF THE TREAD.
  
 AND REMAINING HANDRAIL DETAILS.
  
  
 4) SHEET E 4 - PROVIDE A NOTE INDICATING THAT FIRE
 ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF NFPA
 72, 2010 EDITION.
  
  
 5) SHEET E 2 - PROVIDE AND EXIT SIGN AT EACH EXIT IN
 EACH MEETING ROOM PER NFPA 101, CHAPTER 12, 12.2.10
 MARKING OF MEANS OF EGRESS.
 12.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS
 IN ACCORDANCE WITH SECTION 7.10.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS,
 SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS.
  
  
 6) SHEET E 2 - PROVIDE AN EXIT SIGN AT THE HALLWAY /
 MULTI PURPOSE ROOM CONNECTION BOTH, VISIBLE FROM EACH
 DIRECTION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-15 Cont ID  
Sent By jwitmer Date 2016-09-15 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2016-08-26 Time 10:37 Sent To  
Notes
2016-08-29 10:37:58C06

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-24 Cont ID  
Sent By gjohnson Date 2016-08-18 Time 08:55 Rev Time 0.00
Received By gjohnson Date 2016-07-22 Time 10:16 Sent To  
Notes
2016-07-25 10:17:13C05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-13 Cont ID  
Sent By jroach Date 2016-06-13 Time 15:01 Rev Time 0.00
Received By jroach Date 2016-05-10 Time 10:57 Sent To  
Notes
2016-05-11 10:57:24C06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-06-01 Cont ID  
Sent By jwitmer Date 2016-06-01 Time 13:25 Rev Time 0.00
Received By jwitmer Date 2016-06-01 Time 13:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-09-07 Cont ID  
Sent By ccole Date 2016-09-07 Time 10:44 Rev Time 0.00
Received By ccole Date 2016-09-07 Time 10:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-27 Cont ID  
Sent By ccole Date 2016-07-27 Time 10:41 Rev Time 0.00
Received By ccole Date 2016-07-27 Time 10:40 Sent To  
Notes
2016-07-27 10:54:562ND REVIEW MECHANICAL
 PERMIT #16050413
 7/26/16
  
 1) SHEET M-1 & M-3: PROVIDE AN O/A CALCULATION FOR
 STORAGE ROOM 110 AND INDICATE HOW THE AIR WILL BE
 PROVIDED.
  
 2) M-1: INDICATE CONTROLS OPERATION FOR EF-4. THE
 ELECTRICAL PLANS DO NOT SHOW ANY CIRCUIT OR CIRCUIT
 CONNECTION TO THE FAN.
  
 3) M-1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 WARMING OVEN.
  
 4) M-1: INDICATE HOW CONDENSATE FROM AHU-1 IS BEING
 DRAINED AND DISCHARGED
  
 5) PROVIDE A DETAIL FOR INSTALLATION OF THE ERV.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-19 Cont ID  
Sent By ccole Date 2016-05-19 Time 07:13 Rev Time 0.00
Received By ccole Date 2016-05-19 Time 07:13 Sent To  
Notes
2016-05-19 07:18:341ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050413
 5/19/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS- SECTION
 C403.2.1 FBC-14 ENERGY CALCULATION.
 2) PROVIDE ENERGY CALCULATIONS- C101.4.3 FBC-14 ENERGY
 CONSERVATION.
 3) SHEET M-3: THE OUTSIDE AIR HAS BEEN CALCULATED USING
 OFFICES AS THE BASIS OF DESIGN, HOWEVER THIS IS AN
 ASSEMBLY OCCUPANCY PER THE ARCHITECT. IT APPEARS THAT
 THE OCCUPANCY DENSITIES AND AIRFLOW RATES IN THE
 CALCULATIONS DO NOT MATCH THE INTENDED USE OF THE ROOMS
 AND SPACES.
 4) M3: THE EXHAUST RATE FOR TOILETS OR URINALS IS 70
 CFM PER FIXTURE FOR INTERMITTENT USE- TABLE 403.3
 FOOTNOTE E. EF 1 & 2 SHALL BE MINIMUM 210 CFM'S EACH.
 5) M-1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE RETURN
 AIR SYSTEM OF AHU-1 PER SECTION 606.2.1
 6) M-1: REFER TO SECTION 507.2.2 AND PROVIDE A TYPE II
 HOOD FOR THE WARMING OVEN OR PROVIDE EXHAUST
 VENTILATION AT A RATE OF 0.70 CFM'S PER SF.
 7) M-5: PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR
 THE RTU'S PER SECTION 301.15. PROVIDE ON THE PLAN A
 SECTION CUT THAT SHOWS THE ROOF OPENING REINFORCEMENTS,
 CURB CONSTRUCTION AND ANCHORAGE, CURB HEIGHT, AND RT&U
 MOUNTING DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2019-10-23 Cont ID  
Sent By shill Date 2019-10-23 Time 18:02 Rev Time 0.00
Received By shill Date 2019-10-23 Time 18:02 Sent To  
Notes
2019-10-23 18:03:07SUBSTANTIAL IMPROVEMENT
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-08-18 Cont ID  
Sent By gjohnson Date 2016-08-18 Time 12:49 Rev Time 0.00
Received By gjohnson Date 2016-08-18 Time 09:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-18 Cont ID  
Sent By gjohnson Date 2016-05-18 Time 09:16 Rev Time 0.00
Received By gjohnson Date 2016-05-18 Time 09:16 Sent To  
Notes
2016-05-18 09:34:121ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. DRINKING FOUNTAIN SHALL COMPLY WITH FBC ACC SEC.
 602.4- 306 - 307 SHOW ON PLAN.
 PER WPB AMEND. TO FBC 107.2.1
  
 2. MIRROR SHALL BE 40IN. MAX ABOVE FLOOR PER FBC ACC
 SEC. 603.3
  
 3. SHOW WATER CLOSET 16IN MIN AND 18IN MAX FROM SIDE
 WALL PER FBC ACC SEC. 604.2
  
 4. SHOW GRAB BARS TO COMPLY WITH FBC ACC SEC.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 5. TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC
 SEC. 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 5. KITCHEN SINKS SHALL COMPLY WITH FBC ACC SEC. 606.2
 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.

Review Stop Z ZONING
Rev No 3 Status P Date 2016-09-14 Cont ID  
Sent By jroach Date 2016-09-14 Time 10:59 Rev Time 0.00
Received By jroach Date 2016-09-14 Time 10:58 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2016-08-16 Cont ID  
Sent By jroach Date 2016-08-16 Time 08:38 Rev Time 0.00
Received By jroach Date 2016-08-16 Time 08:38 Sent To  
Notes
2016-08-16 08:38:29ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.16.2016
 PERMIT NO.: 16050413
 ADDRESS: 4800 DREHER TRAIL NORTH
 CONTRACTOR/CONTACT: ALLEN GAST
 TELEPHONE NO.: 561.281.1001
 SCOPE OF REVIEW: INTERIOR AND EXTERIOR IMPROVEMENTS
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO RESOLUTION NO. 223-16, WHICH APPROVED
 THE RENOVATIONS, BEFORE COMMENCING THE IMPROVEMENTS,
 THE SCIENCE CENTER SHALL PROVIDE THE CITY?S RISK
 MANAGER WITH CERTIFICATES OF INSURANCE EVIDENCING THAT
 ANY CONTRACTOR(S) PERFORMING THE IMPROVEMENTS CARRIES
 THE APPROPRIATE LEVELS OF INSURANCE, AS REQUIRED BY THE
 LEASE AGREEMENT. PLEASE PROVIDE THE CERTIFICATES OF
 INSURANCE TO BE REVIEWED / APPROVED BY THE CITY?S RISK
 MANAGER.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-13 Cont ID  
Sent By jroach Date 2016-06-13 Time 15:01 Rev Time 0.00
Received By jroach Date 2016-06-06 Time 16:28 Sent To  
Notes
2016-06-13 15:01:32ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.13.2016
 PERMIT NO.: 16050413
 ADDRESS: 4800 DREHER TRAIL NORTH
 CONTRACTOR/CONTACT: ALLEN GAST
 TELEPHONE NO.: 561.281.1001
 SCOPE OF REVIEW: INTERIOR AND EXTERIOR IMPROVEMENTS
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO THE LEASE BETWEEN THE CITY AND THE SOUTH
 FLORIDA SCIENCE CENTER FOR THE GARDEN CLUB BUILDING,
 ONLY MINOR ALTERATIONS WERE PERMITTED; EXTERIOR
 IMPROVEMENTS AND SIGNIFICANT ALTERATIONS TO THE
 BUILDING REQUIRE THE APPROVAL BY THE CITY COMMISSION
 PRIOR TO THE ISSUANCE OF A BUILDING PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved