Plan Review Details - Permit 16050318
Plan Review Stops For Permit 16050318
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-31 Cont ID  
Sent By shill Date 2016-05-31 Time 12:59 Rev Time 0.00
Received By shill Date 2016-05-31 Time 12:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-20 Cont ID  
Sent By shill Date 2016-05-20 Time 12:11 Rev Time 0.00
Received By shill Date 2016-05-19 Time 17:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 10:59 Rev Time 0.00
Received By mvaldes Date 2016-06-15 Time 10:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-18 Cont ID  
Sent By vperez Date 2016-05-18 Time 13:37 Rev Time 0.00
Received By vperez Date 2016-05-18 Time 13:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-31 Cont ID  
Sent By pleduc Date 2016-05-31 Time   Rev Time 0.00
Received By pleduc Date 2016-05-31 Time 14:22 Sent To  
Notes
2016-05-31 15:12:37THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PREVIOUS FIRE COMMENTS WERE NOT ADDRESSED.
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET CS 1 - THERE IS AN INCORRECT REFERENCE TO THE
 FIRE CODE. THOUGH IT MAY NOT NEGATIVELY AFFECT THE
 SUBMITTAL, IT MAY REQUIRE FURTHER REVIEW FOR
 COMPLIANCE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
  
 2) SHEET A 1 - THERE IS A NOTE INDICATING THE
 RELOCATION OF A SD AND FA DEVICE. PLEASE PROVIDE A NOTE
 AND ENSURE THE FOLLOWING:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 3) SHEET A 1 - THERE ARE NEW WALLS INDCATED. ANY
 REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR CEILINGS
 IN A SPRINKLERED BUILDING REQUIRES AN EVALUATION OF THE
 SPRINKLER PROTECTION. A CERTIFIED FIRE SPRINKLER
 CONTRACTOR SHALL REVIEW THE PROPOSED AND IF REQUIRED,
 PROVIDE SHOP DRAWINGS FOR ANY WORK.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 LIFE SAFETY CONTRACTOR.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-23 Cont ID  
Sent By pleduc Date 2016-05-24 Time   Rev Time 0.00
Received By pleduc Date 2016-05-23 Time 14:08 Sent To  
Notes
2016-05-23 14:20:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET CS 1 - THERE IS AN INCORRECT REFERENCE TO THE
 FIRE CODE. THOUGH IT MAY NOT NEGATIVELY AFFECT THE
 SUBMITTAL, IT MAY REQUIRE FURTHER REVIEW FOR
 COMPLIANCE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
  
 2) SHEET A 1 - THERE IS A NOTE INDICATING THE
 RELOCATION OF A SD AND FA DEVICE. PLEASE PROVIDE A NOTE
 AND ENSURE THE FOLLOWING:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 3) SHEET A 1 - THERE ARE NEW WALLS INDCATED. ANY
 REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR CEILINGS
 IN A SPRINKLERED BUILDING REQUIRES AN EVALUATION OF THE
 SPRINKLER PROTECTION. A CERTIFIED FIRE SPRINKLER
 CONTRACTOR SHALL REVIEW THE PROPOSED AND IF REQUIRED,
 PROVIDE SHOP DRAWINGS FOR ANY WORK.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 LIFE SAFETY CONTRACTOR.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 11:01 Rev Time 0.00
Received By mvaldes Date 2016-05-25 Time 10:48 Sent To  
Notes
2016-05-26 10:48:36B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-26 Cont ID  
Sent By lmarchan Date 2016-05-26 Time 10:45 Rev Time 0.00
Received By lmarchan Date 2016-05-09 Time 10:49 Sent To  
Notes
2016-05-09 10:47:51B05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-02 Cont ID  
Sent By ccole Date 2016-06-02 Time 12:31 Rev Time 0.00
Received By ccole Date 2016-06-02 Time 12:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-18 Cont ID  
Sent By ccole Date 2016-05-18 Time 15:57 Rev Time 0.00
Received By ccole Date 2016-05-18 Time 15:57 Sent To  
Notes
2016-05-18 16:00:51 
 1ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050318
 5/18/16
  
 1) PROVIDE HVAC PLANS SHOWING ALL ALTERATIONS REQUIRED
 TO ACCOMODATE THE NEW DEN ROOM- SECTION 107 WPB
 AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2016-05-13 Cont ID  
Sent By gjohnson Date 2016-05-13 Time 10:55 Rev Time 0.00
Received By gjohnson Date 2016-05-13 Time 10:55 Sent To  
Notes
2016-05-13 10:56:36NO PLUMBING UNDER THIS PERMIT
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  