2016-05-31 15:12:37 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| THE PREVIOUS FIRE COMMENTS WERE NOT ADDRESSED. |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| 1) SHEET CS 1 - THERE IS AN INCORRECT REFERENCE TO THE |
| FIRE CODE. THOUGH IT MAY NOT NEGATIVELY AFFECT THE |
| SUBMITTAL, IT MAY REQUIRE FURTHER REVIEW FOR |
| COMPLIANCE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| |
| |
| 2) SHEET A 1 - THERE IS A NOTE INDICATING THE |
| RELOCATION OF A SD AND FA DEVICE. PLEASE PROVIDE A NOTE |
| AND ENSURE THE FOLLOWING: |
| |
| THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| CONSTRUCTION PERIOD. |
| ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE |
| UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE |
| SAFETY CONTRACTORS. |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| |
| 3) SHEET A 1 - THERE ARE NEW WALLS INDCATED. ANY |
| REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR CEILINGS |
| IN A SPRINKLERED BUILDING REQUIRES AN EVALUATION OF THE |
| SPRINKLER PROTECTION. A CERTIFIED FIRE SPRINKLER |
| CONTRACTOR SHALL REVIEW THE PROPOSED AND IF REQUIRED, |
| PROVIDE SHOP DRAWINGS FOR ANY WORK. |
| |
| ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE |
| DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED |
| LIFE SAFETY CONTRACTOR. |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |