Plan Review Details - Permit 16050249
Plan Review Stops For Permit 16050249
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-09-19 Cont ID  
Sent By shill Date 2016-09-19 Time 11:44 Rev Time 0.00
Received By shill Date 2016-09-19 Time 11:44 Sent To  
Notes
2016-09-19 12:20:15PROVISOS:
  
 COMPONENT AND CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMTTED AS A REVISION
 PRIOR TO INSTALLATION.
  
 ROOF PERMIT REQUIRED. PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED AS A REVISION
 PRIOR TO INSTALLATION. CONTRACTOR TO INDICATE ASSEMBLY
 OR INSTALLATION METHOD PROPOSED. INCLUDE ENGINEERING IF
 REQUIRED.
  
  
  
  
  
  
  
 VERIFIED PLANS ARE THE SAME WITH THE FOLLOWING
 EXCEPTION:
  
 SHEET E0.01 HAS A VERSION/DATE OF V3, 7/22/16 FOR SETS
 1 AND 3
 SHEET E0.01 HAS A VERSION/DATE OF V2, 6/03/16 FOR SET 2
  
 THE SHEET APPEAR THE SAME WITH THE EXCEPTION OF THE
 REVISION NUMBER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-09-16 Cont ID  
Sent By shill Date 2016-09-16 Time 09:42 Rev Time 0.00
Received By shill Date 2016-09-16 Time 07:41 Sent To  
Notes
2016-09-16 10:07:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. BUILDING REVIEW IS PASSED PENDING RECEIPT OF 3RD SET
 (SEE ITEM #2).
  
 2. THE THIRD SET PROVIDED IS NOT THE SAME AS THE OTHER
 TWO SETS SUBMITTED.
  
 CIVIL SHEETS ARE NOT INCLUDED
 AE311 IS NOT THE SAME VERSION
 AE312 MISSING
  
 THE PROCESS OF CONFIRMING THAT THE THIRD SET MATCHES
 THE OTHER SETS WAS STOPPED AT THIS POINT. HAVE
 CONTRACTOR PROVIDE A THIRD SET WHICH MATCHES THE OTHER
 SETS (AS SOON AS POSSIBLE - NO ADDITIONAL REVIEWS WILL
 BE DONE UNTIL THIS IS COMPLETED). I'VE WRITTEN "SET #3"
 ON THE OUTSIDE OF THE NEW SET. PLEASE LET ME KNOW WHEN
 THIS IS COMPLETE.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-08-16 Cont ID  
Sent By shill Date 2016-08-16 Time 08:11 Rev Time 0.00
Received By shill Date 2016-08-16 Time 08:11 Sent To  
Notes
2016-08-16 08:11:36****CORRECTIONS****
 REVISED 9/7 (ITEM 34)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
  
 1. FLORIDA STATUTE 553.71, IT APPEARS THAT THIS
 BUILDING MAY QUALIFY AS A THRESHOLD BUILDING; ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SF IN AREA AND AN OCCUPANT CONTENT
 OF GREATER THAN 500 PERSONS.
  
 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED:
  
 A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY
 THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED
 TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT
 ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL
 INFORMATION.
 FORMS WERE SENT TO: [email protected]
 ON 5/28/16.
  
 C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW
 BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE
 RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY
 SAMANTHA HILL), 561-805-6666, [email protected],
 [email protected]
  
 ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE
 CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN
 THE SPECIAL INSPECTOR AGREEMENT.
  
 D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL
 ([email protected], [email protected]).
  
 E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE
 SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL
 DOCUMENTS.
  
 F. THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633.
  
 (ARCHITECT OK - REVISED PLAN)
  
 THE ENGINEER HAS A SIMILAR STATEMENT BUT LACKS SOME OF
 THE STATUTORY LANGUAGE; PLEASE REVISE.
  
 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE
 ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD
 AND THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE
 SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE
 ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO
 INSPECTION. THE CITY APPROVED (CITY STAMPED)
 SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE
 JOB AT THE TIME OF INSPECTION.
  
 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL
 DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD
 BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING.
  
 5. SEE IMPACT FEE REVIEW.
  
 6. ADVISORY ONLY; SEE ROOF (R STOP) REVIEW. NO ROOFING
 INFORMATION PROVIDED IF ROOFING INFORMATION (PRODUCT
 APPROVAL REVIEWED BY DESIGNER OF RECORD, ASSEMBLY
 PROPOSED, ENHANCED FASTENING CALCULATIONS IF REQUIRED)
 IS NOT SUBMITTED PRIOR TO PERMIT ISSUANCE, THIS PERMIT
 WILL BE ISSUED WITH PROVISO. ROOF INFORMATION WILL BE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED PRIOR
 TO INSTALLATION.
  
 9. THREE COMPLETE SETS OF PLANS REQUIRED FOR ALL
 THRESHOLD JOBS (CITY, CONTRACTOR, THRESHOLD INSPECTOR).
  
 11 TO 18. OK
  
 19. LS101, ACADEMICS TEAM ROOM OCCUPANT LOAD IS SHOWN
 AS 20 SF PER PERSON, CLARIFY, APPEARS TO BE A TYPO AS
 THIS SHOULD BE 15 SF (AND OCC LOAD CALCULATED USING 15
 SF). REVISE PLAN TO CLARIFY USE OF THE SPACE. 15SF IS
 FOR AREAS WITH TABLES AND CHAIRS, AREAS WITH CHAIRS
 ONLY SHOULD USE 7 SF, AND STANDING AREAS SHOULD USE
 5SF.
  
 2ND REVIEW, ARCHITECT?S RESPONSE IS ACCEPTABLE. PLEASE
 REVISE PLAN TO NOTE THAT ACADEMICS TEAM ROOM IS A
 CLASSROOM, ACCESSORY USE.
  
 20. LS101, THE ACADEMICS TEAM ROOM MEANS OF EGRESS
 FORCES THE OCCUPANT TO TRAVEL THROUGH A SPACE WHICH IS
 A WORK AREA, WHICH APPEARS TO BE PROHIBITED BY FBC
 1014.2. REVISE PLAN TO EITHER MODIFY EXITING STRATEGY
 OR REVISE PLAN TO SHOW COMPLIANCE (I.E., SHOW HOW THE
 TWO SPACES ARE ACCESSORY TO ONE ANOTHER).
  
 2ND REVIEW, RESPONSE STATES THAT DIRECT ACCESS TO THE
 CORRIDOR WAS PROVIDED. PLEASE SEE LS101; THE NEW ACCESS
 TO CORRIDOR APPEARS TO BE LABELED STORAGE ON ALL
 SHEETS. PLEASE REVISE THE LIFE SAFETY AND FLOOR PLAN.
 IT APPEARS THAT THE STORAGE ROOM MAY BE THE ADJACENT
 ROOM. ALSO PLEASE INCLUDE THE DIMENSION BETWEEN THE TWO
 DOORS TO SHOW COMPLIANCE WITH FBC 5TH EDITION
 ACCESSIBILITY FIGURE 404.2.6.
  
 24 - 27. OK
  
 30. OK
  
 31 TO 33. OK
  
 34. REVISED 9/7 - RECEIVED LETTER FROM ENGINEER
 REGARDING RATIONALE FOR RISK CATEGORY II. LETTER IS
 ACCEPTABLE; PLEASE INCLUDE THE SIGNED, SEALED ORGINAL
 WITH THE RESUBMITTAL.
  
 35. OK
  
 36. FBC 1008.1.10, REVISE DOOR SCHEDULE AE701 TO
 INCLUDE DOOR HARDWARE; IT IS NOT CLEAR WHERE PANIC
 HARDWARE IS PROPOSED.
  
 FBC TABLE 716.5, EXIT ENCLOSURES REQUIRE 1 HOUR DOORS;
 DOOR 101 PROPOSES 20 MIN, PLEASE REVISE.
  
 ALSO, REGARDING THIS EXIT STAIR WHICH DISCHARGES INTO
 THE FIRST FLOOR, SEE FBC 1027.1 EXCEPTION 1.1, THE EXIT
 IS TO BE READILY VISIBLE AND IDENTIFIABLE FROM THE
 POINT OF TERMINATION OF THE ENCLOSURE. PLEASE SEE
 CLARIFICATION IN THE COMMENTARY, WHICH SPECIFICALLY
 STATES THAT THE OCCUPANT SHOULD NOT BE REQUIRED TO TURN
 COMPLETELY AROUND OR AROUND A CORNER. IT APPEARS THAT
 EITHER THE DOOR SHOULD OPEN DIRECTLY INTO THE DIRECTION
 OF THE EXIT DISCHARGE OR THE WALL AT THE END OF THE
 FIRST FLOOR STAIR SHOULD BE RATED THE SAME AS THE STAIR
 IF THIS IS TO BE CONSIDERED A CONTINUATION OF THE STAIR
 EXIT.
  
 37. FROM PREVIOUS LIST: A SPOT CHECK OF THE ENERGY
 CALCS WAS DONE; PLEASE CLARIFY THE FOLLOWING OR REVISE
 PLAN:
 ROOF INSULATION IS R20 ON ENERGY CALCS, R19 ON PLAN
  
 2ND REVIEW, THIS WAS CORRECTED BUT STILL SPECS R19 IN
 SOME LOCATIONS (SEE AE320, AE321). PLEASE REVISE AND
 CHECK ALL.
  
 38. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 COMPONENTS AND CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED, REVIEWED AND
 APPROVED PRIOR TO INSTALLATION
  
 SEPARATE PERMITS, PLANS, REVIEWS, AND FEES WILL BE
 REQUIRED FOR SIGNS, AWNINGS, PARKING
  
 NEW COMMENT:
  
 39. PLAN REVIEW NOTE: THIS PLAN WAS RESUBMITTED PRIOR
 TO BUILDING PLAN REVIEW #2.
  
 PLEASE SEE FS553.80 (NOTE LANGUAGE "SHALL IMPOSE"
 RATHER THAN "MAY"):
 (B)"WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS'
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 FOR THIS PROJECT, PLAN REVIEW FEE IS $22,637 (4X FEE =
 $90,548). IF DESIGN PROFESSIONAL DISAGREES WITH A
 SIGNIFICANT PLAN REVIEW COMMENT FOR ANY PROJECT, IT IS
 RESPECTFULLY SUGGESTED THAT THE APPROPRIATE REVIEWER BE
 CONTACTED AND RESOLVE PRIOR TO RESUBMITTING. ALTHOUGH
 LANGUAGE REQUIRES THAT THE FEE BE IMPOSED, IT IS NOT
 BEING IMPOSED AT THIS TIME DUE TO THE FACT THAT SINCE
 PLANS WERE RESUBMITTED WITHOUT ADDRESSING BUILDING
 COMMENTS FROM REVIEW 1, THIS IS BUILDING REVIEW 2
 RATHER THAN BUILDING REVIEW 3. PLEASE ALLOW ALL TRADES
 TO COMPLETE REVIEWS PRIOR TO RESUBMITTAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-25 Cont ID  
Sent By shill Date 2016-07-25 Time 07:28 Rev Time 0.00
Received By shill Date 2016-07-25 Time 07:03 Sent To  
Notes
2016-07-25 08:08:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
  
 1. FLORIDA STATUTE 553.71, IT APPEARS THAT THIS
 BUILDING MAY QUALIFY AS A THRESHOLD BUILDING; ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SF IN AREA AND AN OCCUPANT CONTENT
 OF GREATER THAN 500 PERSONS.
  
 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED:
  
 A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY
 THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED
 TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT
 ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL
 INFORMATION.
 FORMS WERE SENT TO: [email protected]
 ON 5/28/16.
  
 C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW
 BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE
 RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY
 SAMANTHA HILL), 561-805-6666, [email protected],
 [email protected]
  
 ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE
 CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN
 THE SPECIAL INSPECTOR AGREEMENT.
  
 D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL
 ([email protected], [email protected]).
  
 E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE
 SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL
 DOCUMENTS.
  
 F. THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633.
  
 I WAS UNABLE TO LOCATE THIS STATEMENT ON THE
 ARCHITECT'S PLANS.
  
 THE ENGINEER HAS A SIMILAR STATEMENT BUT LACKS SOME OF
 THE STATUTORY LANGUAGE; PLEASE REVISE.
  
 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE
 ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD
 AND THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE
 SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE
 ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO
 INSPECTION. THE CITY APPROVED (CITY STAMPED)
 SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE
 JOB AT THE TIME OF INSPECTION.
  
 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL
 DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD
 BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING.
  
 5. SEE IMPACT FEE REVIEW.
  
 6. ADVISORY ONLY; SEE ROOF (R STOP) REVIEW. NO ROOFING
 INFORMATION PROVIDED IF ROOFING INFORMATION (PRODUCT
 APPROVAL REVIEWED BY DESIGNER OF RECORD, ASSEMBLY
 PROPOSED, ENHANCED FASTENING CALCULATIONS IF REQUIRED)
 IS NOT SUBMITTED PRIOR TO PERMIT ISSUANCE, THIS PERMIT
 WILL BE ISSUED WITH PROVISO. ROOF INFORMATION WILL BE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED PRIOR
 TO INSTALLATION.
  
 7, 8. OK
  
 9 ? 12. REVISE SHEETS TO ADDRESS COMMENTS 9 THROUGH 12
 FROM REVIEW 1 AS DISCUSSED PER EMAILS AND ATTACHED PDF.
  
 13. FBC 107, FS 553.71, SHEET LS101, PROVIDE A TOTAL
 OCCUPANT LOAD FOR THE BUILDING, BROKEN DOWN BY FLOOR
 AND OCCUPANCY CLASSIFICATION.
  
 14. LS101, ROOM 145 SHOWS OCCUPANT LOAD CALCULATED AT
 100 SF PER PERSON. FBC TABLE 1004.1.2, 50 SF GROSS
 REQUIRED, PLEASE REVISE.
  
 15, 16. OK
  
 17. LS101, SOME ROOMS AND SPACES DO NOT INCLUDE AN
 OCCUPANT LOAD (137, 138, 139, 140, CORRIDORS, ALL
 OTHERS AS APPLICABLE). PLEASE REVISE TO INCLUDE, FBC
 1004. NOTE THAT DEFINITION (CHAPTER 2) OF FLOOR AREA
 GROSS INCLUDES ALL AREAS, BUT FLOOR AREA NET EXCLUDES
 UNOCCUPIED SPACE. ALTHOUGH THIS IS ASSEMBLY OCCUPANCY,
 TABLE 1004.1.2 UTILIZES GROSS SF FOR THE MAJORITY OF
 THE SPACES ON THIS FLOOR. PLEASE NOTE THAT THIS
 RATIONALE IS SUBSTANTIATED BY THE IBC, BUILDING 2012
 COMMENTARY.
  
 FBC 107, IT IS ACKNOWLEDGED THAT THE ISSUES OF ROUNDING
 AND MISSING OCCUPANT LOAD WILL LIKELY NOT AFFECT THE
 LIFE SAFETY DESIGN. HOWEVER, A TOTAL OCCUPANT LOAD IS
 REQUIRED FOR INFORMATION REQUIRED TO BE ON THE
 CERTIFICATE OF OCCUPANCY.
  
 2ND REVIEW, PLEASE REVISE LIFE SAFETY PLAN AND OCCUPANT
 LOAD AS DISCUSSED VIA EMAIL.
  
 18. BREAK ROOM 110 OCCUPANT LOAD APPEARS TO HAVE A TYPO
 (16 SF RATHER THAN 15 SF), ALSO PLEASE ROUND UP, SEE
 OTHER COMMENTS, FBC TABLE 1004.1.2.
  
 19. LS101, ACADEMICS TEAM ROOM OCCUPANT LOAD IS SHOWN
 AS 20 SF PER PERSON, CLARIFY, APPEARS TO BE A TYPO AS
 THIS SHOULD BE 15 SF (AND OCC LOAD CALCULATED USING 15
 SF). REVISE PLAN TO CLARIFY USE OF THE SPACE. 15SF IS
 FOR AREAS WITH TABLES AND CHAIRS, AREAS WITH CHAIRS
 ONLY SHOULD USE 7 SF, AND STANDING AREAS SHOULD USE
 5SF.
  
 20. LS101, THE ACADEMICS TEAM ROOM MEANS OF EGRESS
 FORCES THE OCCUPANT TO TRAVEL THROUGH A SPACE WHICH IS
 A WORK AREA, WHICH APPEARS TO BE PROHIBITED BY FBC
 1014.2. REVISE PLAN TO EITHER MODIFY EXITING STRATEGY
 OR REVISE PLAN TO SHOW COMPLIANCE (I.E., SHOW HOW THE
 TWO SPACES ARE ACCESSORY TO ONE ANOTHER).
  
 IF THE RESUBMITTAL PROPOSES TO MAINTAIN EGRESS FROM AN
 A2 AREA THROUGH A WORK AREA, PLEASE GET THIS ITEM
 REVIEWED PRIOR TO RESUBMITTAL VIA EMAIL.
  
 21. LS 101 AND LS 102, NO DIMENSIONS WERE INCLUDED ON
 THE PLAN, OR ON THE OTHER A SHEETS. ADD OVERALL
 DIMENSIONS. REVISE PLAN TO SHOW COMMON PATH IN ROOM
 145, FBC 1014.3.
  
 22. TRAVEL DISTANCE REQUIREMENTS NOTES ARE INCLUDED IN
 CODE REVIEW SECTION OF THE LIFE SAFETY PLAN, BUT NO
 TRAVEL DISTANCES SHOWN. PLEASE REVISE TO INCLUDE WORST
 CASE, FBC 107.
  
 23. OK
  
 24. LS 101, EXITING STRATEGY VESTIBULE 128 IS NOT
 CLEAR, SEE FBC 1005.7.1, REVISE PLAN TO SHOW COMPLIANCE
 OR CLARIFY MEANS OF EGRESS PATH. LS101 SHOWS AN ARROW
 THROUGH THE VESTIBULE, BUT WHEN BOTH DOORS ARE IN THE
 OPEN POSITION, THE CORRIDOR APPEARS TO BE ALMOST
 ENTIRELY BLOCKED.
  
 25. FBC 1011.1, REVISE PLAN TO INCLUDE ALL REQUIRED
 EXIT SIGNS.
  
 LS101, PLEASE ADD AN EXIT SIGN AT CORRIDOR 164, BETWEEN
 ICE AND WET ROOM, OR REVISE EXIT ACCESS.
  
 26. 2ND REVIEW, PLEASE REVISE PLAN AS DISCUSSED VIA
 EMAIL.
  
 26. FBC 1007, REVISE PLAN TO INDICATE METHOD OF
 ACCESSIBLE MEANS OF EGRESS SELECTED, REVISE PLAN TO
 SHOW COMPLIANCE WITH METHOD SELECTED.
  
 27. OK
  
 28. ACCESSIBILITY NOT ADDRESSED ON THIS PLAN:
  
 206.2.13, EXERCISE MACHINES AND EQUIPMENT
 241, SAUNAS AND STEAM ROOMS
 222, LOCKER ROOMS
 226, DINING SURFACES (TERRACES)
  
 THESE ITEMS CAN BE ADDRESSED WITH NOTES ON THE PLAN,
 SHOP DRAWINGS TO BE SUBMITTED PRIOR TO INSTALLATION.
  
 29. AE 112, PROVIDE DIMENSION OF CLEARANCE, 18IN
 MINIMUM, PULL SIDE, FOR DOOR A121, FBC 5TH ED
 ACCESSIBILITY FIGURE 404.2.4.1(A).
  
 30. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 404.6,
 ENCLOSURE OF ATRIUMS (FP SHEETS, LS SHEETS). THE NOTE
 ON LS SHEETS REFERS TO THE SMOKE PARTITION, BUT I WAS
 UNABLE TO LOCATE THE REFERENCE TO WINDOW SPRINKLERS.
  
 31. LS101 AND 102, REVISE INTERIOR FINISH NOTES TO
 INCLUDE ATRIUM REQUIREMENT, FBC 404.8.
  
 32. FBC 107, 703.1, PROVIDE DETAILS (ASSEMBLIES) FOR
 THE FIRE RATED ELEMENTS.
  
 33. AE801 RATED STUD PARTITION DOES NOT SPECIFY THE UL
 NUMBER, PLEASE REVISE TO INCLUDE, FBC 703.
  
 34. NOTE CD 01 STATES THIS WAS DESIGNED PER FBC. FBC
 TABLE 1604.5, RISK CATEGORY III INCLUDES BUILDINGS OF
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OVER 300,
 SHEET S0.01 INDICATES THIS BUILDING WAS DESIGNED AS
 RISK CATEGORY II, PLEASE REVISE.
  
 35. PLEASE REVISE FLOOR PLAN TO INCLUDE THE GATE SHOWN
 ON DETAIL AE712. IF THIS GATE IS IN THE EXIT DISCHARGE,
 REVISE THE DETAIL TO DEPICT THE REQUIRED PANIC
 HARDWARE, FBC 1008.2.
  
 36. FBC 1008.1.10, REVISE DOOR SCHEDULE AE701 TO
 INCLUDE DOOR HARDWARE; IT IS NOT CLEAR WHERE PANIC
 HARDWARE IS PROPOSED.
  
 37. A SPOT CHECK OF THE ENERGY CALCS WAS DONE; PLEASE
 CLARIFY THE FOLLOWING OR REVISE PLAN:
 ROOF INSULATION IS R20 ON ENERGY CALCS, R19 ON PLAN
 WALL INSULATION IS R3.9 ON ENERGY CALCS, UNABLE TO
 LOCATE ON PLAN
 WATER HEATER SECTION IS BLANK
 EXTERIOR LIGHTING IS BLANK
 FLOOR R VALUE 3.73, CLARIFY
  
 38. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 COMPONENTS AND CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED, REVIEWED AND
 APPROVED PRIOR TO INSTALLATION
  
 SEPARATE PERMITS, PLANS, REVIEWS, AND FEES WILL BE
 REQUIRED FOR SIGNS, AWNINGS, PARKING
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By shill Date 2016-06-06 Time 11:34 Rev Time 0.00
Received By shill Date 2016-06-06 Time 11:34 Sent To  
Notes
2016-06-06 11:34:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
  
 1. FLORIDA STATUTE 553.71, IT APPEARS THAT THIS
 BUILDING MAY QUALIFY AS A THRESHOLD BUILDING; ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SF IN AREA AND AN OCCUPANT CONTENT
 OF GREATER THAN 500 PERSONS.
  
 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED:
  
 A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY
 THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED
 TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT
 ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL
 INFORMATION.
 FORMS WERE SENT TO: [email protected]
 ON 5/28/16.
  
 C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW
 BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE
 RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY
 SAMANTHA HILL), 561-805-6666, [email protected],
 [email protected]
  
 ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE
 CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN
 THE SPECIAL INSPECTOR AGREEMENT.
  
 D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL
 ([email protected], [email protected]).
  
 E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE
 SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL
 DOCUMENTS.
  
 F. THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633.
  
 I WAS UNABLE TO LOCATE THIS STATEMENT ON THE
 ARCHITECT'S PLANS.
  
 THE ENGINEER HAS A SIMILAR STATEMENT BUT LACKS SOME OF
 THE STATUTORY LANGUAGE; PLEASE REVISE.
  
 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE
 ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD
 AND THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE
 SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE
 ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO
 INSPECTION. THE CITY APPROVED (CITY STAMPED)
 SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE
 JOB AT THE TIME OF INSPECTION.
  
 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL
 DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD
 BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING.
  
 5. SEE IMPACT FEE REVIEW.
  
 6. ADVISORY ONLY; SEE ROOF (R STOP) REVIEW. NO ROOFING
 INFORMATION PROVIDED IF ROOFING INFORMATION (PRODUCT
 APPROVAL REVIEWED BY DESIGNER OF RECORD, ASSEMBLY
 PROPOSED, ENHANCED FASTENING CALCULATIONS IF REQUIRED)
 IS NOT SUBMITTED PRIOR TO PERMIT ISSUANCE, THIS PERMIT
 WILL BE ISSUED WITH PROVISO. ROOF INFORMATION WILL BE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED PRIOR
 TO INSTALLATION.
  
 7. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. SHEETS C1 THROUGH C4 PREPARED BY RICHARD
 REIKENIS, PE ARE COPIES. THESE PAGES LACK THE
 CERTIFICATE OF AUTHORIZATION, REFERENCE AN OUTDATED
 BUILDING CODE, AND THE SEAL LACKS A DATE. ALSO, PLEASE
 NOTE THAT THIS ENGINEER HAS NOT YET COMPLIED WITH FS
 471.0195, FAC 61G15-22.01 (MANDATORY BY JUNE 30, 2016).
 NOTE THAT THIS ENGINEER, ALTHOUGH RESPONSIBLE FOR CIVIL
 SHEETS, HAS REFERENCED ACCESSIBILITY ON HIS PLAN. SEE
 PAGE 4 OF THE APRIL EDITION OF THE FBPE NEWSLETTER FOR
 MORE INFORMATION:
  
  HTTPS://WWW.FBPE.ORG/INDEX.PHP/FILE-DOWNLOADS/SEND/56-
 2015-2016-FBPE-NEWSLETTERS/377-APRIL-2016-FBPE-NEWSLET
 TER
  
 8. GENERAL ADVISORY TO ALL ENGINEERS WHO DESIGN
 BUILDINGS, STRUCTURES, FACILITIES OR SYSTEMS COVERED BY
 THE FLORIDA BUILDING CODE, ALL ENGINEERS ARE REQUIRED
 TO COMPLETE THE ADVANCED BUILDING CODE COURSE BY JUNE
 30, 2016, FS471.0195 AND FAC61G15-22.001. UPON
 COMPLETION OF THE COURSE, FBPE IS TO BE PROVIDED WITH A
 COPY OF THE COMPLETION CERTIFICATE SO THAT THE
 ENGINEER?S LICENSE RECORD ON WWW.MYFLORIDALICENSE.COM
 WEBSITE WILL BE BEEN UPDATED.
  
 CURRENTLY, MORE INFORMATION REGARDING THIS COURSE CAN
 BE FOUND ON THE FBPE HOME PAGE, LATEST NEWS:
  
 WWW.FBPE.ORG
  
 AND ALSO ON PAGE 4 OF THE FBPE NEWSLETTER:
  
 HTTPS://WWW.FBPE.ORG/INDEX.PHP/FILE-DOWNLOADS/SEND/56-2
 015-2016-FBPE-NEWSLETTERS/377-APRIL-2016-FBPE-NEWSLETT
 ER
  
 9. THREE COMPLETE SETS OF PLANS REQUIRED FOR ALL
 THRESHOLD (AND RESIDENT INSPECTOR) JOBS, FBC 107.
  
 10. FBC 506, REVISE PLAN TO SHOW THE DISTANCE BETWEEN
 THE PROPOSED STRUCTURE AND THE EXISTING BLEACHERS, AND
 PROVIDE DIMENSIONS FOR THE EXISTING BLEACHERS.
  
 11. FBC 506, PROVIDE DIMENSIONS AND IDENTIFICATION FOR
 THE LARGE UNIDENTIFIED RECTANGLE, NORTHWEST SIDE.
  
 12. FBC 506.2.2, SHOW DISTANCE FROM THE WEST SIDE OF
 THE BUILDING TO THE FIRE LANE.
  
 13. FBC 107, FS 553.71, SHEET LS101, PROVIDE A TOTAL
 OCCUPANT LOAD FOR THE BUILDING, BROKEN DOWN BY FLOOR
 AND OCCUPANCY CLASSIFICATION.
  
 14. LS101, ROOM 145 SHOWS OCCUPANT LOAD CALCULATED AT
 100 SF PER PERSON. FBC TABLE 1004.1.2, 50 SF GROSS
 REQUIRED, PLEASE REVISE.
  
 15. LS101, ROOM 165 APPEARS TO HAVE A TYPO (230
 OCCUPANT LOAD). EITHER CORRECT OR PROVIDE ADDITIONAL
 MEANS OF EGRESS, FBC 1015.
  
 16. LS101, ROOMS 148, 149 152, 159, ANY OTHER ROOMS AS
 APPLICABLE, PLEASE ROUND UP FOR OCCUPANT LOAD, FBC
 TABLE 1004.1.2.
  
 17. LS101, SOME ROOMS AND SPACES DO NOT INCLUDE AN
 OCCUPANT LOAD (137, 138, 139, 140, CORRIDORS, ALL
 OTHERS AS APPLICABLE). PLEASE REVISE TO INCLUDE, FBC
 1004. NOTE THAT DEFINITION (CHAPTER 2) OF FLOOR AREA
 GROSS INCLUDES ALL AREAS, BUT FLOOR AREA NET EXCLUDES
 UNOCCUPIED SPACE. ALTHOUGH THIS IS ASSEMBLY OCCUPANCY,
 TABLE 1004.1.2 UTILIZES GROSS SF FOR THE MAJORITY OF
 THE SPACES ON THIS FLOOR. PLEASE NOTE THAT THIS
 RATIONALE IS SUBSTANTIATED BY THE IBC, BUILDING 2012
 COMMENTARY.
  
 FBC 107, IT IS ACKNOWLEDGED THAT THE ISSUES OF ROUNDING
 AND MISSING OCCUPANT LOAD WILL LIKELY NOT AFFECT THE
 LIFE SAFETY DESIGN. HOWEVER, A TOTAL OCCUPANT LOAD IS
 REQUIRED FOR INFORMATION REQUIRED TO BE ON THE
 CERTIFICATE OF OCCUPANCY.
  
 18. BREAK ROOM 110 OCCUPANT LOAD APPEARS TO HAVE A TYPO
 (16 SF RATHER THAN 15 SF), ALSO PLEASE ROUND UP, SEE
 OTHER COMMENTS, FBC TABLE 1004.1.2.
  
 19. LS101, ACADEMICS TEAM ROOM OCCUPANT LOAD IS SHOWN
 AS 20 SF PER PERSON, CLARIFY, APPEARS TO BE A TYPO AS
 THIS SHOULD BE 15 SF (AND OCC LOAD CALCULATED USING 15
 SF). REVISE PLAN TO CLARIFY USE OF THE SPACE. 15SF IS
 FOR AREAS WITH TABLES AND CHAIRS, AREAS WITH CHAIRS
 ONLY SHOULD USE 7 SF, AND STANDING AREAS SHOULD USE
 5SF.
  
 20. LS101, THE ACADEMICS TEAM ROOM MEANS OF EGRESS
 FORCES THE OCCUPANT TO TRAVEL THROUGH A SPACE WHICH IS
 A WORK AREA, WHICH APPEARS TO BE PROHIBITED BY FBC
 1014.2. REVISE PLAN TO EITHER MODIFY EXITING STRATEGY
 OR REVISE PLAN TO SHOW COMPLIANCE (I.E., SHOW HOW THE
 TWO SPACES ARE ACCESSORY TO ONE ANOTHER).
  
 IF THE RESUBMITTAL PROPOSES TO MAINTAIN EGRESS FROM AN
 A2 AREA THROUGH A WORK AREA, PLEASE GET THIS ITEM
 REVIEWED PRIOR TO RESUBMITTAL VIA EMAIL.
  
 21. LS 101 AND LS 102, NO DIMENSIONS WERE INCLUDED ON
 THE PLAN, OR ON THE OTHER A SHEETS. ADD OVERALL
 DIMENSIONS. REVISE PLAN TO SHOW COMMON PATH IN ROOM
 145, FBC 1014.3.
  
 22. TRAVEL DISTANCE REQUIREMENTS NOTES ARE INCLUDED IN
 CODE REVIEW SECTION OF THE LIFE SAFETY PLAN, BUT NO
 TRAVEL DISTANCES SHOWN. PLEASE REVISE TO INCLUDE WORST
 CASE, FBC 107.
  
 23. FBC 1022.5 AND .6, MECHANICAL SHEETS APPEAR TO SHOW
 A DUCT INTO THE EXIT STAIR, PLEASE REMOVE.
  
 24. LS 101, EXITING STRATEGY VESTIBULE 128 IS NOT
 CLEAR, SEE FBC 1005.7.1, REVISE PLAN TO SHOW COMPLIANCE
 OR CLARIFY MEANS OF EGRESS PATH. LS101 SHOWS AN ARROW
 THROUGH THE VESTIBULE, BUT WHEN BOTH DOORS ARE IN THE
 OPEN POSITION, THE CORRIDOR APPEARS TO BE ALMOST
 ENTIRELY BLOCKED.
  
 25. FBC 1011.1, REVISE PLAN TO INCLUDE ALL REQUIRED
 EXIT SIGNS.
  
 26. FBC 107, 1004, 1008, USE OF THE HOSPITALITY SPACES
 ON THE SECOND FLOOR AND HOW OCCUPANT LOAD WAS
 DETERMINED IS NOT CLEAR. A TABLE AND CHAIR OCCUPANT
 LOAD (15SF) WAS USED FOR TERRACES, AND STANDING (5SF)
 FOR INDOORS. WILL OCCUPANTS NEVER BE ALLOWED TO STAND
 OUTDOORS IN THE TERRACES? IT IS NOT CLEAR WHY DIFFERENT
 METHODS WERE USED WHEN IT APPEARS THAT THE TERRACES ARE
 EXTENSIONS OF THE HOSPITALITY SPACE. IT APPEARS
 POSSIBLE THAT 5SF PER PERSON SHOULD BE USED FOR THE
 TERRACES. PROVIDE MORE INFORMATION OR REVISE OCCUPANT
 LOAD, NUMBER OF EXITS, DOOR SWING. PLEASE CONTACT ME IF
 YOU WISH TO DISCUSS.
  
 26. FBC 1007, REVISE PLAN TO INDICATE METHOD OF
 ACCESSIBLE MEANS OF EGRESS SELECTED, REVISE PLAN TO
 SHOW COMPLIANCE WITH METHOD SELECTED.
  
 27. PROVIDE A DETAIL FOR THE ACCESSIBLE SHOWER, FBC 5TH
 EDITION ACCESSIBILITY 608.
  
 28. ACCESSIBILITY NOT ADDRESSED ON THIS PLAN:
  
 206.2.13, EXERCISE MACHINES AND EQUIPMENT
 241, SAUNAS AND STEAM ROOMS
 222, LOCKER ROOMS
 226, DINING SURFACES (TERRACES)
  
 THESE ITEMS CAN BE ADDRESSED WITH NOTES ON THE PLAN,
 SHOP DRAWINGS TO BE SUBMITTED PRIOR TO INSTALLATION.
  
 29. AE 112, PROVIDE DIMENSION OF CLEARANCE, 18IN
 MINIMUM, PULL SIDE, FOR DOOR A121, FBC 5TH ED
 ACCESSIBILITY FIGURE 404.2.4.1(A).
  
 30. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 404.6,
 ENCLOSURE OF ATRIUMS (FP SHEETS, LS SHEETS). THE NOTE
 ON LS SHEETS REFERS TO THE SMOKE PARTITION, BUT I WAS
 UNABLE TO LOCATE THE REFERENCE TO WINDOW SPRINKLERS.
  
 31. LS101 AND 102, REVISE INTERIOR FINISH NOTES TO
 INCLUDE ATRIUM REQUIREMENT, FBC 404.8.
  
 32. FBC 107, 703.1, PROVIDE DETAILS (ASSEMBLIES) FOR
 THE FIRE RATED ELEMENTS.
  
 33. AE801 RATED STUD PARTITION DOES NOT SPECIFY THE UL
 NUMBER, PLEASE REVISE TO INCLUDE, FBC 703.
  
 34. NOTE CD 01 STATES THIS WAS DESIGNED PER FBC. FBC
 TABLE 1604.5, RISK CATEGORY III INCLUDES BUILDINGS OF
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OVER 300,
 SHEET S0.01 INDICATES THIS BUILDING WAS DESIGNED AS
 RISK CATEGORY II, PLEASE REVISE.
  
 35. PLEASE REVISE FLOOR PLAN TO INCLUDE THE GATE SHOWN
 ON DETAIL AE712. IF THIS GATE IS IN THE EXIT DISCHARGE,
 REVISE THE DETAIL TO DEPICT THE REQUIRED PANIC
 HARDWARE, FBC 1008.2.
  
 36. FBC 1008.1.10, REVISE DOOR SCHEDULE AE701 TO
 INCLUDE DOOR HARDWARE; IT IS NOT CLEAR WHERE PANIC
 HARDWARE IS PROPOSED.
  
 37. A SPOT CHECK OF THE ENERGY CALCS WAS DONE; PLEASE
 CLARIFY THE FOLLOWING OR REVISE PLAN:
 ROOF INSULATION IS R20 ON ENERGY CALCS, R19 ON PLAN
 WALL INSULATION IS R3.9 ON ENERGY CALCS, UNABLE TO
 LOCATE ON PLAN
 WATER HEATER SECTION IS BLANK
 EXTERIOR LIGHTING IS BLANK
 FLOOR R VALUE 3.73, CLARIFY
  
 38. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 COMPONENTS AND CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED, REVIEWED AND
 APPROVED PRIOR TO INSTALLATION
  
 SEPARATE PERMITS, PLANS, REVIEWS, AND FEES WILL BE
 REQUIRED FOR SIGNS, AWNINGS, PARKING
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-09-19 Cont ID  
Sent By vperez Date 2016-09-19 Time 07:56 Rev Time 0.00
Received By vperez Date 2016-09-19 Time 07:56 Sent To  
Notes
2016-09-19 08:13:06PLANS APPROVED PENDING SET #2 LABELED CONTRACTOR SET
 MISSING 3 SHEETS E 2.01-2.02-2.03 PROVIDE FOR STAMPS

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-08-13 Cont ID  
Sent By vperez Date 2016-08-13 Time 14:09 Rev Time 0.00
Received By vperez Date 2016-08-13 Time 14:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-11 Cont ID  
Sent By vperez Date 2016-07-11 Time 14:05 Rev Time 0.00
Received By vperez Date 2016-07-11 Time 09:13 Sent To  
Notes
2016-07-11 14:06:532ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS:
  
 NO COMMENTS FOR ELECTRICAL ADDRESSED SEE BELOW PREVIOUS
 COMMENTS.
  
 1. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED
 TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA,
 SIGNAGE, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC
 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS
 AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS
 REQUIRED.
 3. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS.
 4. PER FBC EC 405.7- 50% OF ALL RECEPTACLES 125V, 15
 AND 20A MUST BE AUTOMATICALLY CONTROLLED WHERE
 INSTALLED IN PRIVATE OFFICES, OPEN OFFICES, AND
 COMPUTER CLASSROOMS. THIS INCLUDES THOSE INSTALLED IN
 MODULAR PARTITIONS. SHOW COMPLIANCE.
 5. PLEASE ADDRESS FIRE COMMENTS RELATED TO THE
 ELECTRICAL DESIGN.
 6. LABEL GFCI ALL RECEPTACLES IN THE MEN?S AND WOMEN?S
 LOCKER ROOMS PER NEC 210.8B7
 7. LABEL GFCI ALL RECEPTACLES WITHIN 6FT OF SINKS, SEE
 SERVING PANTRY?S AREA. NEC 210.8B5
 8. LABEL GFCI CIRCUIT LB-40 ELEVATOR SUMP PUMP SHOWS A
 DUPLEX RECEPTACLE. IF IT?S A SINGLE RECEPTACLE SHOW
 CORRECT SYMBOL. NEC 620.85
 9. SHOW THE AIC RATING PER UTILITY COMPANY LETTERHEAD
 AT THE TRANSFORMER. FBC 107.3.5
 10. PROVIDE AIC CALCULATION FOR THE NEW SERVICE.
 11. REFLECT ON PANEL SCHEDULE THE CONDUCTORS SIZE
 SELECTED FOR ALL BRANCH CICUITS. FBC 107.3.5
 12. CLARIFY THE LOCATION OF THE ELEVATOR MACHINE ROOM.
 13. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-23 Cont ID  
Sent By vperez Date 2016-06-23 Time 14:04 Rev Time 0.00
Received By vperez Date 2016-06-23 Time 14:04 Sent To ENG
Notes
2016-06-23 14:15:28INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED
 TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA,
 SIGNAGE, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC
 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS
 AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS
 REQUIRED.
 3. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS.
 4. PER FBC EC 405.7- 50% OF ALL RECEPTACLES 125V, 15
 AND 20A MUST BE AUTOMATICALLY CONTROLLED WHERE
 INSTALLED IN PRIVATE OFFICES, OPEN OFFICES, AND
 COMPUTER CLASSROOMS. THIS INCLUDES THOSE INSTALLED IN
 MODULAR PARTITIONS. SHOW COMPLIANCE.
 5. PLEASE ADDRESS FIRE COMMENTS RELATED TO THE
 ELECTRICAL DESIGN.
 6. LABEL GFCI ALL RECEPTACLES IN THE MEN?S AND WOMEN?S
 LOCKER ROOMS PER NEC 210.8B7
 7. LABEL GFCI ALL RECEPTACLES WITHIN 6FT OF SINKS, SEE
 SERVING PANTRY?S AREA. NEC 210.8B5
 8. LABEL GFCI CIRCUIT LB-40 ELEVATOR SUMP PUMP SHOWS A
 DUPLEX RECEPTACLE. IF IT?S A SINGLE RECEPTACLE SHOW
 CORRECT SYMBOL. NEC 620.85
 9. SHOW THE AIC RATING PER UTILITY COMPANY LETTERHEAD
 AT THE TRANSFORMER. FBC 107.3.5
 10. PROVIDE AIC CALCULATION FOR THE NEW SERVICE.
 11. REFLECT ON PANEL SCHEDULE THE CONDUCTORS SIZE
 SELECTED FOR ALL BRANCH CICUITS. FBC 107.3.5
 12. CLARIFY THE LOCATION OF THE ELEVATOR MACHINE ROOM.
 13. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2016-09-19 Cont ID  
Sent By Mgonzale Date 2016-09-19 Time   Rev Time 1.00
Received By mgonzale Date 2016-09-19 Time   Sent To I
Notes
2016-09-19 19:20:01PROVISOS:
  
 #1 OBTAIN UG FIRELINE PERMIT FOR FIRELINE AND PLUMBING
 PERMIT FOR WATER SERVICE CONNECTION/BACKFLOW.
  
 #2 SUBMIT THE DCDA AND RPPA BACKFLOWS MUST BE LEAD
 FREE,
  
 #3 CUSTOMER SERVICE MUST APPROVE SERVICE LOCATIONS. ANY
 OBSTRUCTIONS MUST BE ADDRESSED.
 SERVICE LOCATIONS SHALL BE LANDSCAPED LEAVING ADEQUATE
 CLEARANCE FOR MAINTENANCE TO BACKFLOWS.
  
 #4 TAPPS TO WATER LINES WILL REQUIRE PRESENCE OF CITY
 OF WPB ENGINEERING PERSONNEL. OBTAIN ENGINEERING
 DEVELOPMENT APPROVAL
 FOR PUBLIC UTILITIE SERVICES.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-06-29 Cont ID  
Sent By Mgonzale Date 2016-06-29 Time   Rev Time 1.00
Received By mgonzale Date 2016-06-29 Time   Sent To I
Notes
2016-06-29 13:09:36PLEASE ADDRESS FIRE AND PLUMBING COMMENTS.
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 EMAIL SPECIFICATIONS SHEETS FOR "LEAD FREE" DCDA AND
 RPPA DEVICES. TO [email protected]
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-09-20 Cont ID  
Sent By pleduc Date 2016-09-20 Time   Rev Time 0.00
Received By pleduc Date 2016-09-20 Time 11:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-08-17 Cont ID  
Sent By pleduc Date 2016-08-17 Time   Rev Time 0.00
Received By pleduc Date 2016-08-16 Time 16:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-15 Cont ID  
Sent By pleduc Date 2016-07-15 Time   Rev Time 0.00
Received By pleduc Date 2016-07-14 Time 16:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-10 Cont ID  
Sent By pleduc Date 2016-05-10 Time   Rev Time 0.00
Received By pleduc Date 2016-05-09 Time 12:37 Sent To  
Notes
2016-05-09 15:25:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET LS 101 - STAIR 1 INDICATES ITS EXIT TO THE
 INTERIOR OB THE BUILDING. THE EXIT DOES NOT MEET THE
 REQUIREMENTS BELOW # 1, 136 OCCUPANTS VS 105 FOR STAIR
 # 2. AND # 3 THE EXIT PATH IS READILY VISIBLE AND
 IDENTIFIABLE.
  
 AN EXTERIOR EXIT DOOR IS REQUIRED IN STAIR # 1.
  
 PER NFPA 101, CHAPTER 12, NEW ASSEMBLY OCCUPANCIES,
 12.2.7 DISCHARGE FROM EXITS.
 12.2.7.1 EXIT DISCHARGE SHALL COMPLY WITH SECTION 7.7.
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT
 DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH
 7.7.1.4.
 7.7.2 EXIT DISCHARGE THROUGH INTERIOR BUILDING AREAS.
 EXITS SHALL BE PERMITTED TO DISCHARGE THROUGH INTERIOR
 BUILDING AREAS, PROVIDED THAT ALL OF THE FOLLOWING ARE
 MET:
 (1) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER OF
 EXITS, AND NOT MORE THAN 50 PERCENT OF THE REQUIRED
 EGRESS CAPACITY, SHALL DISCHARGE THROUGH AREAS ON ANY
 LEVEL OF DISCHARGE, EXCEPT AS OTHERWISE PERMITTED BY
 ONE OF THE FOLLOWING:
 (A) ONE HUNDRED PERCENT OF THE EXITS SHALL BE PERMITTED
 TO DISCHARGE THROUGH AREAS ON ANY LEVEL OF DISCHARGE IN
 DETENTION AND CORRECTIONAL OCCUPANCIES AS OTHERWISE
 PROVIDED IN CHAPTERS 22 AND 23.
 (B) IN EXISTING BUILDINGS, THE 50 PERCENT LIMIT ON
 EGRESS CAPACITY SHALL NOT APPLY IF THE 50 PERCENT LIMIT
 ON THE REQUIRED NUMBER OF EXITS IS MET.
 (2) EACH LEVEL OF DISCHARGE SHALL DISCHARGE DIRECTLY
 OUTSIDE AT THE FINISHED GROUND LEVEL OR DISCHARGE
 DIRECTLY OUTSIDE AND PROVIDE ACCESS TO THE FINISHED
 GROUND LEVEL BY OUTSIDE STAIRS OR OUTSIDE RAMPS.
 (3) THE INTERIOR EXIT DISCHARGE SHALL LEAD TO A FREE
 AND UNOBSTRUCTED WAY TO THE EXTERIOR OF THE BUILDING,
 AND SUCHWAY SHALL BE READILY VISIBLE AND IDENTIFIABLE
 FROM THE POINT OF DISCHARGE FROM THE EXIT.
 (4) THE INTERIOR EXIT DISCHARGE SHALL BE PROTECTED BY
 ONE OF THE FOLLOWING METHODS:
 (A) THE LEVEL OF DISCHARGE SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7, OR THE PORTION OF THE
 LEVEL OF DISCHARGE USED FOR INTERIOR EXIT DISCHARGE
 SHALL BE PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION 9.7 AND SHALL BE
 SEPARATED FROM THE NONSPRINKLERED PORTION OF THE FLOOR
 BY FIRE BARRIERS WITH A FIRE RESISTANCE RATING MEETING
 THE REQUIREMENTS FOR THE ENCLOSURE OF EXITS. (SEE
 7.1.3.2.1.)
 (B) THE INTERIOR EXIT DISCHARGE AREA SHALL BE IN A
 VESTIBULE OR FOYER THAT MEETS ALL OF THE FOLLOWING
 CRITERIA:
 I. THE DEPTH FROM THE EXTERIOR OF THE BUILDING SHALL BE
 NOT MORE THAN 10 FT (3050 MM), AND THE LENGTH SHALL BE
 NOT MORE THAN 30 FT (9.1 M).
 II. THE FOYER SHALL BE SEPARATED FROM THE REMAINDER OF
 THE LEVEL OF DISCHARGE BY CONSTRUCTION PROVIDING
 PROTECTION NOT LESS THAN THE EQUIVALENT OF WIRED GLASS
 IN STEEL FRAMES OR 45 MINUTES FIRERESISTIVE
 CONSTRUCTION.
 III. THE FOYER SHALL SERVE ONLY AS MEANS OF EGRESS AND
 SHALL INCLUDE AN EXIT DIRECTLY TO THE OUTSIDE.
 (5) THE ENTIRE AREA ON THE LEVEL OF DISCHARGE SHALL BE
 SEPARATED FROM AREAS BELOW BY CONSTRUCTION HAVING A
 FIRE RESISTANCE RATING NOT LESS THAN THAT REQUIRED FOR
 THE EXIT ENCLOSURE, UNLESS OTHERWISE PROVIDED IN
 7.7.2(6).
 (6) LEVELS BELOW THE LEVEL OF DISCHARGE IN AN ATRIUM
 SHALL BE PERMITTED TO BE OPEN TO THE LEVEL OF DISCHARGE
 WHERE SUCH LEVEL OF DISCHARGE IS PROTECTED IN
 ACCORDANCE WITH 8.6.7.
  
 2) SHEET FA 1.01 - PLEASE PROVIDE A NOTE INDICATING
 THAT THE FIRE ALARM WORK SHALL BE SUBMITTED AND
 COMPLETED UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED
 LIFE SAFETY CONTRACTOR.
  
 3) SHEET M 0.02 - DUCT DETECTORS ARE NOT CLEARLY
 INDICATED OR COULD BE EASILY LOCATED. PER NFPA CHAPTER
 12, 12.5 BUILDING SERVICES.
 12.5.1 UTILITIES. UTILITIES SHALL COMPLY WITH THE
 PROVISIONS OF SECTION 9.1.
 12.5.2 HEATING, VENTILATING, AND AIR-CONDITIONING
 EQUIPMENT. HEATING, VENTILATING, AND AIR-CONDITIONING
 EQUIPMENT SHALL COMPLY WITH THE PROVISIONS OF SECTION
 9.2.
  
 9.2 HEATING, VENTILATING, AND AIR-CONDITIONING.
 9.2.1 AIR-CONDITIONING, HEATING, VENTILATING DUCTWORK,
 AND RELATED EQUIPMENT. AIR-CONDITIONING, HEATING,
 VENTILATING DUCTWORK, AND RELATED EQUIPMENT SHALL BE IN
 ACCORDANCE WITH NFPA 90A, STANDARD FOR THE INSTALLATION
 OF AIR-CONDITIONING AND
 VENTILATING SYSTEMS, OR NFPA 90B, STANDARD FOR THE
 INSTALLATION OF WARM AIR HEATING AND AIR-CONDITIONING
 SYSTEMS, AS APPLICABLE, UNLESS SUCH INSTALLATIONS ARE
 APPROVED EXISTING INSTALLATIONS, WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 PER NFPA 90 A , CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTEDAT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
 3) SHEET AE701 - THE DOOR & FRAME SCHEDULE DOES NOT
 INDICATE ANY DOOR HARDWARE SPECIFCALLY, EXIT DOOR
 HARDWARE AND PANIC DEVICES. PLEASE PROVIDE DETAIL
 HARDWARE DEVICES FOR EACH DOOR PER NFPA 101 CHAPTER 12,
 12.2.2.2 DOORS
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE
 EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS AS PERMITTED IN
 12.2.2.2.6.
  
 4) SHEET AE 210 - THERE IS NO INDICATION OF A LIGHT
 WEIGHT ROOF AND/OR FLOOR SIGN PLEASE PROVIDE FOR A
 LIGHTWEIGHT SIGN PER FLORIDA 69A-60.0081; NOTICE
 SIGNAGE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 5) SHEET AE 112 - THERE IS NO INDICATION OF THE
 DIMENSIONS OF CORRIDORS 130 AND 133. PLEASE PROVIE THE
 DIMENSIONS COMPLY WITH NFPA 101, CHAPTER 12, 12.2.3.8
 MINIMUM CORRIDOR WIDTH. THE WIDTH OF ANY EXIT ACCESS
 CORRIDOR SERVING 50 OR MORE PERSONS SHALL BE NOT LESS
 THAN 44 IN. (1120 MM).
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-09-23 Cont ID  
Sent By jroach Date 2016-09-23 Time 13:55 Rev Time 0.00
Received By jroach Date 2016-09-22 Time 14:44 Sent To  
Notes
2016-09-22 14:45:03C39

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-09-20 Cont ID  
Sent By lmarchan Date 2016-09-20 Time 15:35 Rev Time 0.00
Received By lmarchan Date 2016-09-07 Time 14:09 Sent To  
Notes
2016-09-07 17:06:33C39

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-07 Cont ID  
Sent By skennedy Date 2016-09-07 Time 14:09 Rev Time 0.00
Received By skennedy Date 2016-08-03 Time 14:34 Sent To  
Notes
2016-08-03 14:35:15C39

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-03 Cont ID  
Sent By skennedy Date 2016-08-03 Time 14:33 Rev Time 0.00
Received By skennedy Date 2016-06-30 Time 10:10 Sent To  
Notes
2016-07-01 10:10:25C39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-29 Cont ID  
Sent By vperez Date 2016-06-29 Time 16:32 Rev Time 0.00
Received By cpuell Date 2016-06-23 Time 14:15 Sent To  
Notes
2016-05-05 15:32:55C39

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2016-09-22 Cont ID  
Sent By shill Date 2016-09-22 Time 17:35 Rev Time 0.00
Received By shill Date 2016-09-22 Time 17:35 Sent To  
Notes
2016-09-22 17:36:08MU 2016 023888 0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-08-16 Cont ID  
Sent By shill Date 2016-08-16 Time 08:12 Rev Time 0.00
Received By shill Date 2016-08-16 Time 08:12 Sent To  
Notes
2016-08-16 08:14:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS
 REQUIRED PRIOR TO PERMIT ISSUANCE. THE PLANS ARE TO BE
 STAMPED AND THE RECEIPT SHOWING THAT ALL FEES DUE HAVE
 BEEN PAID IS TO BE PROVIDED. 561-233-5025 FOR MORE
 INFORMATION.
  
 THIS MAY BE DONE AT THE END OF PLAN REVIEW, BUT IS
 REQUIRED PRIOR TO BUILDING PERMIT ISSUANCE. AFTER PALM
 BEACH COUNTY IMPACT FEE IS COMPLETE, THE STAMPED PLANS
 AND RECEIPT ARE TO BE RESUBMITTED AT THE BUILDING
 DIVISION COUNTER. THIS IS A PLAN REVIEW WHICH MAY TAKE
 UP TO THREE BUSINESS DAYS. IF PROJECT IS TIME
 SENSITIVE, PLEASE CONSIDER HAVING IMPACT FEE ASSESSMENT
 AND PAYMENT COMPLETE PRIOR TO RESUBMITTING TO AVOID THE
 ADDITIONAL WEEK DELAY AT THE END OF PLAN REVIEW.
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-07-25 Cont ID  
Sent By shill Date 2016-07-25 Time 08:08 Rev Time 0.00
Received By shill Date 2016-07-25 Time 08:08 Sent To  
Notes
2016-07-25 08:09:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS
 REQUIRED PRIOR TO PERMIT ISSUANCE. THE PLANS ARE TO BE
 STAMPED AND THE RECEIPT SHOWING THAT ALL FEES DUE HAVE
 BEEN PAID IS TO BE PROVIDED. 561-233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-05-27 Cont ID  
Sent By shill Date 2016-05-27 Time 10:53 Rev Time 0.00
Received By shill Date 2016-05-27 Time 10:53 Sent To  
Notes
2016-05-27 10:54:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS
 REQUIRED PRIOR TO PERMIT ISSUANCE. THE PLANS ARE TO BE
 STAMPED AND THE RECEIPT SHOWING THAT ALL FEES DUE HAVE
 BEEN PAID IS TO BE PROVIDED. 561-233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-09-19 Cont ID  
Sent By ccole Date 2016-09-19 Time 10:10 Rev Time 0.00
Received By ccole Date 2016-09-19 Time 10:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-08-15 Cont ID  
Sent By ccole Date 2016-08-15 Time 11:21 Rev Time 0.00
Received By ccole Date 2016-08-15 Time 08:28 Sent To  
Notes
2016-08-15 11:57:033RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16050249
 8/15/16
  
 1) THE ENERGY/GAUGE SUBMITTAL INDICATES AHU-5 TO HAVE A
 CAPACITY OF 284 MBH HOWEVER THE AC SCHEDULE INDICATES
 316 MBH- PLEASE CORRECT ONE OR THE OTHER.
  
 2) THE AC SYSTEMS APPEAR TO BE OVERSIZED AND NOT IN
 COMPLIANCE WITH SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION. THE AC CALCULATIONS INDICATE A TOTAL HEAT
 LOAD OF 62.8 TON HOWEVER THE SCHEDULE INDICATES 75 TONS
 OF COOLING. THE CALCULATIONS INDICATE A HEATING COIL
 REQUIREMENT OF 76 KW, HOWEVER THE SCHEDULE INDICATES 95
 KW ELECTRIC HEAT SELECTED- SEE SECTION C403.2.2 FBC-14
 ENERGY CONSERVATION.
  
 3) THE ZONE LOCATIONS INDICATED IN THE AC CALCULATIONS-
 EAST, WEST, CENTRAL, LOCKERS, STR COND DO NOT MATCH THE
 AHU LOCATIONS SHOW IN THE SCHEDULE- SOUTH, STRENGTH,
 NORTH, HOSPITALITY, & SOUTH O/A. PLEASE CORRELATE THE
 CALCS WITH THE SYSTEMS AND THE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-12 Cont ID  
Sent By ccole Date 2016-07-12 Time 09:15 Rev Time 0.00
Received By ccole Date 2016-07-11 Time 16:56 Sent To  
Notes
2016-07-12 09:17:252ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050249
 7/12/16
  
 1) SHEETS M0.02 & M1.01: EF-1 HAS A CAPACITY OF 1075
 CFMS, HOWEVER THE PLAN INDICATES A TOTAL OF 1150 CFMS
 REQUIRED.
  
 2) M0.02 & M1.01: EF-10 HAS A CAPACITY OF 100 CFRMS,
 HOWEVER THE PLAN INDICATES A TOTAL OF 200 CFMS
 REQUIRED.
  
 3) M0.02 & M1.01: AHU-5 HAS A TOTAL SUPPLY AND O/A
 CAPACITY OF 3100 CFMS, HOWEVER THE PLAN IS INDICATING A
 LESSER AMOUNT OF 2815 CFMS OF AIR BEING SUPPLIED. AS
 THIS UNIT IS PROVIDING 100 % AIR FOR EXHAUST, PLEASE
 REVIEW THE PLAN FOR ANY POSSIBLE SUPPLY DIFFUSER
 OMISSIONS.
  
 4) M0.02 & M1.01, AHU-5 O/A SCHEDULE SHOWS 520 CFMS OF
 EXHAUST AIR FOR THE WOMEN'S LOCKER/SHOWER ROOM, HOWEVER
 THE PLAN IS INDICATING A LESSER AMOUNT OF 450 CFMS.
  
 5) THE AC COOLING AND HEATING CALCULATIONS, AND THE
 ENERGY CALCULATIONS WERE NOT RESUBMITTED WITH THE
 CORRECTED PLANS.
  
 6) AS PREVIOUSLY REQUESTED IN 1ST REVIEW COMMENT #4B,
 PLEASE PROVIDE DETAILS OR NOTES ON THE PLAN INDICATING
 COMPLIANCE FOR O/A INTAKE AND EXHAUST TERMINATION
 LOCATION CLEARANCES- SEE SECTIONS 401.4 & 501.3.1.
  
 7) IN REFERENCE TO 1ST REVIEW COMMENT #5, CLARIFY IF
 THE AIR HANDLERS WILL BE LINKED TOGETHER FOR FAN
 SHUTDOWN IF ANY SINGLE DUCT SMOKE DETECTOR ACTIVATES.
  
 8) AS PREVIOUSLY REQUESTRED IN 1ST REVIEW COMMENT #8B,
 PROVIDE MAKEUP AIR FOR THE DRYERS. THE RESPONSE FROM
 JLRD REFERENCES THE AHU-5 TABLE HOWEVER AHU-5 IS NOT
 SERVING THE LAUNDRY ROOM.
  
 9) ADVISORY: IN REFERENCE TO JLRD RESPONSE TO 1ST
 REVIEW COMMENT #10, A SPECIALTY ENGINEER WILL PROVIDE
 THE WIND DESIGN CRITERIA FOR THE EXTERIOR MECHANICAL
 EQUIPMENT INSTALLATIONS. PLEASE NOTE TRHAT A HOLD WILL
 BE PLACED ON MECHANICAL INSPECTIONS UNTIL THE
 ENGINEERING IS SUBMITTED AND APPROVED.
  
 10) M1.01, M1.02, & M1.03: PLEASE SHOW THE REQUIRED
 ACCESS PANELS ON THE PLANS FOR ALL ABOVE CEILING
 EXHAUST FANS- SECTION 306.1.
  
 11) M1.01, M1.02, & M1.03: SHOW THE REQUIRED SMOKE
 DAMPERS FOR DUCT PENETRATING SMOKE WALLS AT CORRIDORS
 132 & 200- SECTION 607.5.4.
  
 12) M3.03: PROVIDE A SMOKE DAMPER DETAIL AND INDICATE
 WHERE THE FIRE DAMPERS SHOWN ON THIS PLAN SHEET CAN BE
 FOUND ON THE HVAC FLOOR PLANS.
  
 13) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND PROVIDE NON-COMBUSTIBLE DOORS FOR ALL
 MECHANICAL CLOSETS, UNLESS THE RETURN DUCTS ARE
 DIRECTLY CONNECTED TO THE AIR HANDLERS.
  
 14) ADVISORY: JLRD HAS REQUESTED DEFFERRED SUBMITTALS
 FOR PRODUCTS INCLUDING O/A INTAKE AND EXHAUST LOUVERS,
 AND DUCT SMOKE DETECTORS. PLEASE REVIEW THE FOLLOWING
 SECTIONS FOR THE WPB AMENDMENTS TO THE FBC:
  
 DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-17 Cont ID  
Sent By ccole Date 2016-05-17 Time 06:51 Rev Time 0.00
Received By ccole Date 2016-05-17 Time 06:51 Sent To  
Notes
2016-05-17 08:08:411ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050249
 5/17/16
  
 1) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 LOCKER ROOMS AND BATH ROOMS, AND PROVIDE HVAC CONTROL
 SEQUENCING DETAILS- SEE TABLE 403.3 FBC-14 MECHANICAL
 AND ASHRAE 62.1-2010.
  
 2) SHEET M0.02: REFER TO TABLE D-1 ASHRAE 90.1 AND
 CORRECT THE DRY AND WET BULB TEMPERATURES FOR WEST PALM
 BEACH SHOWN ON THE PLAN AND IN THE AC CALCULATIONS.
  
 3) SUBMIT A 2ND SET OF ENERGY AND AC CALCULATIONS, AND
 COMPLETE THE MANDATORY REQUIREMENTS CHECKLIST ON PAGE
 11 OF THE ENERGY SUBMITTAL.
  
 4) SHEETS M1.01, M1.02, & M1.03: PLEASE LABEL THE O/A
 INTAKES A) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE O/A
 AND EXHAUST DUCTS.- SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION. B) VERIFY COMPLIANCE WITH SECTIONS 401.4
 AND 501.3.1 FBC-14 MECHANICAL - REQUIRED CLEARANCES FOR
 O/A INTAKES AND EXHAUST OUTLETS. C) INDICATE HOW THE
 O/A INLET AND EXHAUST OUTLET OPENINGS WILL PROTECTED IN
 COMPLIANCE WITH SECTIONS 401.5 AND 501.3.2 , AND
 PROVIDE SUBMITTALS APPROVED WITH SIGNATURE BY THE
 DESIGN PROFESSIONAL.
  
 5) M1.01, M1.02, M1.03: PROVIDE DUCT SMOKE DETECTORS IN
 THE RETURN AIR SYSTEMS OF ALL SYSTEMS RETURNING OVER
 2000 CFM'S- SECTION 606.2.1. INDICATE CONTROLS
 OPERATION AND SUPERVISION OF THE DETECTORS, AND PROVIDE
 A SUBMITTAL APPROVED WITH SIGNATURE BY THE DESIGN
 PROFESSIONAL,
  
 6) M1.01 & M1.02: AHU-4 SHALL NOT SUPPLY AIR TO STAIR
 #1- REFER TO SECTION 1022.6 FBC-14 BUILDING: THE
 INTERIOR EXIT STAIRWAY AND RAMP VENTILATION SYSTEMS
 SHALL BE INDEPENDENT OF OTHER BUILDING VENTILATION
 SYSTEMS.
  
 7) M1.01: PROVIDE AN INDEPENDENT EXHAUST SYSTEM FOR THE
 JANITOR ROOM- SECTION 501.2.
  
 8) M1.01, LAUNDRY ROOM: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE DRYERS WITH APPROVAL SIGNATURE
 BY THE DESIGN PROFESSIONAL- REFER TO SECTION 504.7 AND
 REVISE THE PLAN TO SHOW COMPLIANCE.
 504.7 COMMERCIAL CLOTHES DRYERS.
 THE INSTALLATION OF DRYER EXHAUST DUCTS SERVING
 COMMERCIAL CLOTHES DRYERS SHALL COMPLY WITH THE
 APPLIANCE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 EXHAUST FAN MOTORS INSTALLED IN EXHAUST SYSTEMS SHALL
 BE LOCATED OUTSIDE OF THE AIRSTREAM. IN MULTIPLE
 INSTALLATIONS, THE FAN SHALL OPERATE CONTINUOUSLY OR BE
 INTERLOCKED TO OPERATE WHEN ANY INDIVIDUAL UNIT IS
 OPERATING. DUCTS SHALL HAVE A MINIMUM CLEARANCE OF 6
 INCHES (152 MM) TO COMBUSTIBLE MATERIALS. CLOTHES DRYER
 TRANSITION DUCTS USED TO CONNECT THE APPLIANCE TO THE
 EXHAUST DUCT SYSTEM SHALL BE LIMITED TO SINGLE LENGTHS
 NOT TO EXCEED 8 FEET (2438 MM) IN LENGTH AND SHALL BE
 LISTED AND LABELED FOR THE APPLICATION. TRANSITION
 DUCTS SHALL NOT BE CONCEALED WITHIN CONSTRUCTION.
 A) INDICATE THE GAGE OF THE DRYER EXHAUST DUCT. B)
 INDICATE HOW MAKE-UP MAIR IS BEING RPOVIDE AND PROVIDE
 A CALCULATION.
  
 9) M1.03: THE LABEL FOR AHU-4 IS MISSING.
  
 10) M3.01: PROVIDE THE WIND LOAD DESIGN CRITERIA ON THE
 PLAN- SECTION 301.15 FBC-14 MECHANICAL.
  
 11) INDICATE HOW ACC/AHU-6 WAS SIZED- PROVIDE A
 CALCULATION.
  
 12) M0.02: A) PROVIDE THE CORRECT SPELLING FOR
 "CONDENSER" IN THE SCHEDULE. B) PROVIDE THE EFFICIENCY
 RATINGS FOR THE ACC SYSTEMS 1-5 IN THE SCHEDULE.
  
 13) PROVIDE CONDENSATE DISPOSAL PLANS FOR ALL SYSTEMS-
 SECTION 307.
  
 14) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND PROVIDE CONSTRUCTION DETAILS AND
 MATERIALS COMPLIANCE FOR THE MECHANICAL CLOSETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-09-08 Cont ID  
Sent By tklarge Date 2016-09-08 Time 05:35 Rev Time 0.00
Received By tklarge Date 2016-09-08 Time 04:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-08-29 Cont ID  
Sent By tklarge Date 2016-08-29 Time 06:41 Rev Time 0.00
Received By tklarge Date 2016-08-27 Time 09:50 Sent To  
Notes
2016-08-29 06:16:161) SUBMIT A CONDENSATE RISER FOR REVIEW.SHT. P3.03 HAS
 BEEN REVISED TO SHOW THE HUB DRAINS, NOT THE CONDENSATE
 DRAINS AS HAS BEEN REQUESTED 2 PREVIOUS TIMES.SUBMIT A
 CONDENSATE RISER SHOWING THE SIZE OF THE CONDENSATE
 DRAINS AND THE EQUIPMENT CAPACITY OF THE DRAINS IN
 ACCORDANCE WITH 2014 FPC TABLE 314.2.2.
 2) WHAT WILL THE SINK IN CONFERENCE ROOM #134 BE USED
 FOR THAT IT WOULD NOT HAVE TO COMPLY WITH FPC
 SEC.607.1?
 3) THE FAUCETS IN BREAKROOM #110 AND PANTRY #118 SHALL
 BE EQUIPPED WITH A WATER TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 AND SHALL LIMIT THE TEMPERED
 WATER TO A MAXIMUM OF 110 DEGREES FARRENHEIT.THIS WILL
 ALSO APPLY TO THE CONFERENCE ROOM SINK IF DETERMINED
 THAT IT NEEDS TEMPERED WATER.
 4) PLEASE IDENTIFY THE CONTINUATION LINES ON THE WATER
 RISER BY IDENTIFICATION TAGS EITHER BY LETTERS OR
 NUMBERS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-07-27 Cont ID  
Sent By gjohnson Date 2016-07-27 Time 11:18 Rev Time 0.00
Received By gjohnson Date 2016-07-27 Time 11:18 Sent To  
Notes
2016-07-27 11:30:112ND REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHOW DIMENSION OF WATER CLOSET OF SIDE WALL. PER FBC
 ACC 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 2. SHOW CLEARANCE AROUND WATER CLOSET TO COMPLY WITH
 FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
  
 3. PREVIOUS COMMENT 16) SHT. P0.03 - SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE OIL GUARD SUMP
 PUMP SYSTEM. FPC SEC.1003.4 - EXCEPTION. THE DETAIL YOU
 PROVIDED ON P0.03 IS NOT WHAT WE ARE LOOKING FOR. WE
 WANT THE SPECIFICATION SHEETS FROM THE SPECIFIC
 MANUFACTURE FOR THE PUMP AND OIL GUARD SYSTEM. PER WPB
 AMEND. TO FBC 107.2.1
  
 4. PREVIOUS COMMENT 17) SHT.P0.03 - CONDENSATE BOX
 DETAIL - HOW WILL THE POSSIBILITY OF WATER SPILLAGE BE
 CONTROLLED WITH THIS DEVICE? CLARIFY. THIS DETAIL DOES
 NOT SHOW US HOW SPILLAGE WILL BE CONTROLLED. PLEASE
 CLARIFY PER WPB AMEND. TO FBC 107.2.1
  
 5. PREVIOUS COMMENT 18) SUBMIT A CONDENSATE RISER FOR
 REVIEW. SHOW THE TERMINATION POINT OF THE CONDENSATE
 DRAINS. FBC 107.1. YOU RESPONDED THAT A RISER WAS ADDED
 BUT COULD NOT FIND IT PLEASE CLARIFY.
  
 6. SHT. P0.03 DETAIL FOR WATER HEATER. THE RETURN LINE
 OF THE RECIRCULATION SYSTEM SHALL SHOW THAT IT CONNECTS
 TO BOTH THE COLD INLET OF THE WATER HEATER AND THE COLD
 WATER INLET OF THE THERMOSTATIC MIXING VALVE . PER FBC
 PL SEC. 607.2.2
  
 7. SHT. P1.04+P3.03 SNK 1+2 SHALL BE PROVIDE WITH HOT
 OR TEMPERED WATER. PER FBC PL 607.1
  
 8. SHT. P3.02 SHOW WATER HAMMER ARRESTOR ON ICE
 MACHINE. PER FBC PL 604.9
  
 9. PLEASE SHOW FLOW ARROWS ON HOT WATER RETURN SYSTEM .
 PER WPB AMEND TO FBC 107.2.1
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-19 Cont ID  
Sent By tklarge Date 2016-05-19 Time 06:21 Rev Time 0.00
Received By tklarge Date 2016-05-17 Time 04:56 Sent To  
Notes
2016-05-17 15:20:151) SUBMIT THE OCCUPANT LOAD FOR THE A-3 OCCUPANCY AND
 ALSO FOR THE B OCCUPANCY.FBC 1004.1.
 2) SHT. AE 410 - SHOW THE REQUIRED CLEAR FLOOR SPACE
 FOR THE BREAK ROOM SINK. 2014 FBC-ACCESSIBILITY
 SEC.606.2.
 3) SHT. AE 401 - CLEARLY SHOW THE INSIDE CLEAR
 DIMENSIONS OF THE ACCESSIBLE SHOWERS. TRANSFER SHOWERS
 SHALL BE 36 INCHES BY 36 INCHES CLEAR INSIDE DIMENSIONS
 PER 2014 FAC SEC.608.2.1.
 4) SHT.AE 403 - TOILET ACCESSORY LEGEND - NOTE # 4
 REFERS TO CHAPTER 11 SEC. 4.1.3 OF ADA. REVISE NOTE TO
 READ 2014 FBC-ACCESSIBILITY. THERE IS NO CHAPTER 11
 SEC. 4.1.3. IN THE 2014 FL. ACCESS. CODE.
 5) SHT. AE 911 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE, NOT TO THE CENTER AS
 SHOWN. 2014 FAC SEC. 609.4.
 6) INDICATE THE ACCESSIBLE URINAL IN EACH MEN'S
 RESTROOM ON THE FLOOR PLANS AND ON THE ELEVATION
 DRAWINGS. SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE
 PLANS. COMPLY WITH 2014 FAC SEC.605.1 THRU 605.4.
 7) SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF ALL
 ACCESSIBLE TOILET COMPARTMENTS AND TOILET ROOMS ON THE
 PLAN. FBC 107.2.1.
 8) SHOW THE LENGTH AND WIDTH OF THE STANDARD TOILET
 STALLS ON THE PLAN. COMPLY WITH 2014 FPC SEC. 405.3.1.
 9) AT LEAST ONE LAVATORY LOCATED OUTSIDE OF THE TOILET
 COMPARTMENT IN THE RESTROOMS SHALL COMPLY WITH FAC
 SEC.213.3.4.
 10) SHT. AE 911 - THE TOP OF THE SHOWER SEAT SHALL BE A
 MAXIMUM OF 19 INCHES ABOVE THE FINISHED FLOOR.FAC
 SEC.610.3.
 11) SHT. AE 911 - THE MAXIMUM SPOUT HEIGHT OF THE
 DRINKING FOUNTAIN FOR PERSONS IN A WHEELCHAIR SHALL BE
 A MAXIMUM OF 36 INCHES. THE SPOUT HEIGHT OF THE
 DRINKING FOUNTAIN FOR STANDING PERSONS SHALL BE 38
 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. FAC SECS.602.5 AND 602.7.
 12) SHOW THE REQUIRED TURNING SPACE IN THE TOILET ROOMS
 & TOILET COMPARTMENTS.FAC SEC. 304.
 13) SHT. AE 801 - DETAIL #6 - SHOW THE REQUIRED KNEE
 AND TOE CLEARANCES PER THE FAC SEC.306.
 14) SHT. AE 911 - THE TOILET PAPER DISPENSER SHALL BE
 LOCATED 7"- 9" MAXIMUM IN FRONT OF THE WATER CLOEST TO
 THE CENTERLINE OF THE DISPENSER PER FAC SEC. 604.7.
 15) THE SHOWER CONTROLS SHALL BE LOCATED A MAXIMUM 15
 INCHES FROM THE CENTERLINE OF THE SEAT TOWARD THE
 SHOWER OPENING.INDICATE THIS ON THE PLAN. FAC
 SEC.608.5.1.
 16) SHT. P0.03 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE OIL GUARD SUMP PUMP SYSTEM. FPC SEC.1003.4 -
 EXCEPTION.
 17) SHT.P0.03 - CONDENSATE BOX DETAIL - HOW WILL THE
 POSSIBILITY OF WATER SPILLAGE BE CONTROLLED WITH THIS
 DEVICE? CLARIFY.
 18) SUBMIT A CONDENSATE RISER FOR REVIEW. SHOW THE
 TERMINATION POINT OF THE CONDENSATE DRAINS. FBC 107.1.
 19)SHT. P0.03 - WATER HEATER DETAIL SHOWS THE WATER
 HEATERS AS BEING BOTTOM FED & THE WATER RISER ON SHT.
 P3.03 SHOWS THE WATER HEATERS AS TOP FED. CLARIFY.
 BOTTOM FED WATER HEATERS SHALL BE EQUIPPED WITH A
 VACUUM RELIEF ON THE CCOLD WATER SUPPLY PER FPC
 SEC.504.2.
 20) SHT. P0.03 - WATER HEATER DETAIL - THE HOT WATER
 RETURN LINE SHALL ALSO CONNECT TO THE COLD WATER INLET
 TO THE WATER HEATERS. THE FLOW ARROW ON THE DETAIL DOES
 NOT SEEM TO MEET THE INTENT OF FPC 607.2.1.
 21) SHT.P3.04 - INDICATE THE SLOPE OF THE HORIZONTAL
 STORM DRAIN PIPING. SIZING SHALL COMPLY WITH FPC TABLE
 1106.3. THE DESIGN OF THE STORM DRAIN SYSTEM SHALL
 INCLUDE 1/2 THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF. SUBMIT CALCULATIONS.
 22) SHT. P3.04 - RISER 3 ST - SIZE THE HORIZONTAL LINE
 DRAINING 2480 SQ. FT., 6115 SQ. FT., & 1835 SQ. FT. THE
 STORM DRAIN SYSTEM SHALL BE SIZED ON A RAINFALL RATE OF
 5 INCHES PER HOUR.
 23) SHT. P3.04 - RISER 2 ST - THE 6" LINE DRAINING 5185
 SQ. FT. MAY BE UNDERSIZED.INDICATE THE PIPE SLOPE AND
 COMPLY WITH FPC TABLE 1106.3.
 24) A BACKFLOW PREVENTER IS REQUIRED ON THE WATER
 SUPPLY TO THE REFRIGERATOR FOR THE ICE MAKER AND A
 WATER HAMMER ARRESTOR IS REQUIRED BECAUSE IT IS A QUICK
 CLOSING VALVE. FPC SEC.608.3.
 25) SHT. P3.01 - SIZE ALL SECTIONS OF THE VENTS AND THE
 WASTE STACKS. THERE ARE NUMEROUS SECTIONS THAT ARE NOT
 SIZED. FBC 107.2.1.
 26) SHT. P3.01 - THE SH-2 SHOWERS IN MEN'S RESTROOM
 158B & 159B AS DRAWN ON THE RISER CREATE A PLUMBING
 CODE VIOLATION FOR FIXTURES PERMITTED ON A WET VENT.
 EITHER INDIVIDUALLY VENT EACH SHOWER OR CONNECT BOTH
 SHOWERS TO THE STACK.FPC SEC. 912.
 27) THE SHOWERS IN ROOMS 148B & 153B AS DRAWN ON THE
 RISER CREATE A PLUMBING CODE VIOLATION OF FPC SEC. 912
 FOR THE NUMBER AND TYPE OF FIXTURE PERMITTED ON A WET
 VENT.
 28) THE VENT FOR THE MOP SINK AND THE FLOOR DRAIN SHALL
 BE LOCATED BETWWEEN THE TWO FIXTURES. FPC SECS.901.2,
 901.2.1.
 29) SHT. P3.01 - THE VENT FOR THE STATIONARY WHIRLPOOLS
 SHALL BE LOCATED BETWEEN THE TWO DRAINS. FPC SECS.
 901.2, 901.2.1.
 30) CLEANOUTS ARE REQUIRED IN THE BASE OF EACH SOIL OR
 WASTE STACK. FPC SEC.708.3.4.
 31) INDICATE THE SLOPE OF THE BUILDING DRAIN AND
 BRANCHES ON THE PLANS. COMPLY WITH FPC SEC.710 AND
 TABLE 710.1 (1).
 32) THE WASHERS AND DRYERS SHALL COMPLY WITH
 FBC-ACCESSIBILITY SEC.611.
 33) SIZE ALL SECTIONS OF THE WATER RISER.FBC 107.2.1.
 34) SHOW THE HOT WATER RECIRCULATING LINE ON SHEET
 P3.02.
 35) SHT.P1.01 & P1.03 - RESTROOMS #155A & 156A - THE
 RESTROOMS ARE MISLABELED. THE MEN'S IS SHOWN AS THE
 WOMEN'S AND THE WOMEN'S IS SHOWN AS THE MEN'S. PLEASE
 CORRECT.
 36) INDICATE THE ACCESSIBLE URINAL IN EACH MEN'S
 RESTROOM ON THE FLOOR PLANS AND ON THE ELEVATION
 DRAWINGS. SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE
 PLANS. COMPLY WITH 2014 FAC SEC.605.1 THRU 605.4.
 37) URINAL PARTITIONS SHALL COMPLY WITH 2014 FBC
 SEC.1210.3.2.
 38) SUBMIT A DESIGN DETAIL FOR THE LINT TRAP /
 INTERCEPTOR. COMPLY WITH 2014 FPC SEC.1003.6.
 39) SUBMIT MANUFACTURER'S INSTALLATION SPECIFICATIONS
 FOR THE WHIRLPOOL TUBS. FBC 107.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status N Date 2016-09-16 Cont ID  
Sent By shill Date 2016-09-16 Time 10:16 Rev Time 0.00
Received By shill Date 2016-09-16 Time 10:16 Sent To  
Notes
2016-09-16 10:17:38NO ROOF INFORMATION SUBMITTED
 THIS IS TO BE SUBMITTED AS A REVISION PRIOR TO
 INSTALLATION. THE PRODUCT APPROVAL, REVIEWED BY
 DESIGNER OF RECORD, IS TO BE SUBMITTED WITH THE
 ASSEMBLY PROPOSED INDICATED. ENGINEERING FOR ENHANCED
 FASTENING TO BE SUBMITTED IF APPLICABLE.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2016-08-15 Cont ID  
Sent By shill Date 2016-08-15 Time 17:37 Rev Time 0.00
Received By shill Date 2016-08-15 Time 17:37 Sent To  
Notes
2016-08-15 17:37:33NO ROOFING INFORMATION PROVIDED IF ROOFING INFORMATION
 (PRODUCT APPROVAL REVIEWED BY DESIGNER OF RECORD,
 ASSEMBLY PROPOSED, ENHANCED FASTENING CALCULATIONS IF
 REQUIRED) IS NOT SUBMITTED PRIOR TO PERMIT ISSUANCE,
 THIS PERMIT WILL BE ISSUED WITH PROVISO. ROOF
 INFORMATION WILL BE REQUIRED TO BE SUBMITTED, REVIEWED
 AND APPROVED PRIOR TO INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-07-25 Cont ID  
Sent By shill Date 2016-07-25 Time 08:09 Rev Time 0.00
Received By shill Date 2016-07-25 Time 08:09 Sent To  
Notes
2016-07-25 08:09:47NO ROOFING INFORMATION PROVIDED
 IF ROOFING INFORMATION (PRODUCT APPROVAL REVIEWED BY
 DESIGNER OF RECORD, ASSEMBLY PROPOSED, ENHANCED
 FASTENING CALCULATIONS IF REQUIRED) IS NOT SUBMITTED
 PRIOR TO PERMIT ISSUANCE, THIS INFORMATION WILL BE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED PRIOR
 TO INSTALLATION
  
 MODIFIED
 METAL BARREL TILE
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-06-03 Cont ID  
Sent By shill Date 2016-06-03 Time 12:08 Rev Time 0.00
Received By shill Date 2016-06-03 Time 12:08 Sent To  
Notes
2016-06-03 12:10:38NO ROOFING INFORMATION PROVIDED
 IF ROOFING INFORMATION (PRODUCT APPROVAL REVIEWED BY
 DESIGNER OF RECORD, ASSEMBLY PROPOSED, ENHANCED
 FASTENING CALCULATIONS IF REQUIRED) IS NOT SUBMITTED
 PRIOR TO PERMIT ISSUANCE, THIS INFORMATION WILL BE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED PRIOR
 TO INSTALLATION
  
 MODIFIED
 METAL BARREL TILE
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 5 Status P Date 2016-09-19 Cont ID  
Sent By shill Date 2016-09-19 Time 16:39 Rev Time 0.00
Received By shill Date 2016-09-19 Time 16:39 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status F Date 2016-09-19 Cont ID  
Sent By shill Date 2016-09-19 Time 07:13 Rev Time 0.00
Received By shill Date 2016-09-16 Time 08:52 Sent To  
Notes
2016-09-16 08:59:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
 4TH SUBMITTAL, THRESHOLD DOCUMENTS FIRST REVIEW
 PLEASE NOTE THAT THRESHOLD DOCUMENTS REQUIRE A PLAN
 REVIEW AND THE PERMIT CANNOT BE ISSUED UNTIL APPROVED
 BY KEN CONRAD.
  
 YOU MAY PROVIDE ONLY THE CORRECTED PAGES (RATHER THAN
 THE ENTIRE AGREEMENT). THE DOCUMENTS MAY BE SENT VIA
 EMAIL TO [email protected] FOR PRELIMINARY REVIEW PRIOR TO
 PLAN RESUBMITTAL. IT IS MY UNDERSTANDING THAT THIS
 PROJECT IS TIME SENSITIVE. PLEASE SEND DOCUMENTS AS
 SOON AS POSSIBLE. ALTHOUGH IT IS PREFERABLE THAT THEY
 BE SUBMITTED ALL AT ONCE, TO AVOID FURTHER DELAYS
 PLEASE PROVIDE DOCUMENTS AS THEY ARE AVAILABLE.
  
 1. FLORIDA STATUTE 553.71
  
 A. NA
  
 B. CONTRACTOR (DALE HEDRICK, QUALIFIER) IS TO SIGN THE
 THRESHOLD AGREEMENT.
  
 C. PER KEN CONRAD, THE CONTRACTOR AND INSPECTOR HAS
 BEEN APPROVED. HOWEVER, IT IS RECOMMENDED TO ADD AN
 ADDITIONAL INSPECTOR TO THE AGREEMENT. ONLY LICENSED
 INSPECTORS WHO HAVE SUBMITTED A RESUME AND SIGNED THE
 SI AGREEMENT MAY PERFORM INSPECTIONS ON THIS THRESHOLD
 STRUCTURE. APPROVAL OF AN ADDITIONAL INSPECTOR WILL NOT
 DELAY PERMIT ISSUANCE.
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2016-08-16 Cont ID  
Sent By shill Date 2016-08-16 Time 08:21 Rev Time 0.00
Received By shill Date 2016-08-16 Time 08:21 Sent To  
Notes
2016-08-16 08:25:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
 3RD SUBMITTAL, THRESHOLD DOCUMENTS HAVE NOT BEEN
 PROVIDED.
 PLEASE NOTE THAT THRESHOLD DOCUMENTS REQUIRE A PLAN
 REVIEW AND THE PERMIT CANNOT BE ISSUED UNTIL APPROVED
 BY KEN CONRAD. THE DOCUMENTS MAY BE SENT VIA EMAIL TO
 [email protected] FOR PRELIMINARY REVIEW PRIOR TO PLAN
 RESUBMITTAL. IT IS MY UNDERSTANDING THAT THIS PROJECT
 IS TIME SENSITIVE. PLEASE SEND DOCUMENTS AS SOON AS
 POSSIBLE. ALTHOUGH IT IS PREFERABLE THAT THEY BE
 SUBMITTED ALL AT ONCE, TO AVOID FURTHER DELAYS PLEASE
 PROVIDE DOCUMENTS AS THEY ARE AVAILABLE.
  
 1. FLORIDA STATUTE 553.71, IT APPEARS THAT THIS
 BUILDING MAY QUALIFY AS A THRESHOLD BUILDING; ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SF IN AREA AND AN OCCUPANT CONTENT
 OF GREATER THAN 500 PERSONS.
  
 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED:
  
 A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY
 THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED
 TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT
 ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL
 INFORMATION.
 FORMS WERE SENT TO: [email protected]
 ON 5/28/16.
  
 C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW
 BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE
 RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY
 SAMANTHA HILL), 561-805-6666, [email protected],
 [email protected]
  
 ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE
 CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN
 THE SPECIAL INSPECTOR AGREEMENT.
  
 D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL
 ([email protected], [email protected]).
  
 E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE
 SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL
 DOCUMENTS.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2016-07-25 Cont ID  
Sent By shill Date 2016-07-25 Time 08:10 Rev Time 0.00
Received By shill Date 2016-07-25 Time 08:10 Sent To  
Notes
2016-07-25 08:24:59SEE BUILDING COMMENTS
 TOTAL OCCUPANT LOAD 761, A3 AND B OCCUPANCIES
 2 STORIES, 28,188 SF 1ST STORY, 4,164 SF 2ND STORY.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-05-28 Cont ID  
Sent By shill Date 2016-05-28 Time 16:17 Rev Time 0.00
Received By shill Date 2016-05-28 Time 16:17 Sent To  
Notes
2016-05-28 16:18:23SEE BUILDING COMMENTS
 A TOTAL OCCUPANT LOAD WAS NOT PROVIDED BUT IT APPEARS
 THAT IT EXCEEDS 500, A3 AND B OCCUPANCIES
 2 STORIES, 28,188 SF 1ST STORY, 4,164 SF 2ND STORY.

Review Stop Z ZONING
Rev No 5 Status P Date 2016-09-23 Cont ID  
Sent By jroach Date 2016-09-23 Time 13:55 Rev Time 0.00
Received By jroach Date 2016-09-23 Time 13:55 Sent To  
Notes
2016-09-23 13:55:33ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.23.2016
 PERMIT NO.: 16050249
 ADDRESS: 3501 PARKER AVENUE
 CONTRACTOR/CONTACT: BRETT
 TELEPHONE NO.: 561.324.1127
 SCOPE OF REVIEW: NEW RECREATION BUILDING.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO INSTALLATION, A REVISION SHALL BE SUBMITTED
 FOR APPROVAL OF THE BIKE RACK DETAIL.
  
 2. SEPARATE PERMITS SHALL BE OBTAINED FOR LANDSCAPING
 AND IRRIGATION. ALL LANDSCAPING SHALL BE PERMITTED,
 INSTALLED AND PASSED INSPECTION PRIOR TO THE ISSUANCE
 OF A CERTIFICATE OF OCCUPANCY (CO).
  
 3. ALL OUTSTANDING LANDSCAPING AND SCREENING ENCLOSURES
 FOR THE ENTIRE PBAU ATHLETIC COMPLEX WILL BE REQUIRED
 TO BE INSTALLED PRIOR TO ISSUANCE OF A CO FOR THE
 RECREATION BUILDING.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 4 Status F Date 2016-09-19 Cont ID  
Sent By jroach Date 2016-09-19 Time 11:09 Rev Time 0.00
Received By jroach Date 2016-09-19 Time 11:09 Sent To  
Notes
2016-09-19 11:10:41ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.19.2016
 PERMIT NO.: 16050249
 ADDRESS:
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW RECREATION BUILDING.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE FOLLOWING COMMENTS ISSUED DURING THE MAJOR
 AMENDMENT PROCESS STILL NEED TO BE INCORPORATED INTO
 THE BUILDING PERMIT APPLICATION:
  
  A. BIKE RACKS SHALL BE PROVIDED AT THE ENTRANCE (OR
 CLOSE TO) THE BUILDING.
  
 2. SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR
 LANDSCAPING AND IRRIGATION.
  
 3. THE TRAFFIC STATEMENT (PREPARED BY KIMLEY-HORN &
 ASSOCIATES) SHALL BE ACKNOWLEDGEMENT AND/OR ACCEPTED BY
 PALM BEACH COUNTY PRIOR TO ISSUANCE OF A BUILDING
 PERMIT.
  
 4. PLEASE NOTE THAT ALL OUTSTANDING LANDSCAPING AND
 SCREENING ENCLOSURES FOR THE PBAU ATHLETIC COMPLEX WILL
 BE REQUIRED TO BE INSTALLED PRIOR TO ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY FOR THE RECREATION BUILDING.
  
 5. PLEASE INCLUDE THE SITE/MASTER PLAN, PREPARED BY
 WINSTON LEE & ASSOCIATES (LYNN BENDER), AS THIS IS THE
 OFFICIAL SITE/MASTER PLAN FOR THE PBAU ATHLETIC CAMPUS
 AND IS AN ACCURATE REPRESENTATION OF ALL SITE
 IMPROVEMENTS THAT ARE TO OCCUR AROUND THE BUILDING.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 3 Status F Date 2016-09-02 Cont ID  
Sent By jroach Date 2016-09-02 Time 11:11 Rev Time 0.00
Received By jroach Date 2016-09-02 Time 11:07 Sent To  
Notes
2016-09-02 11:11:10ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.02.2016
 PERMIT NO.: 16050249
 ADDRESS:
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW RECREATION BUILDING.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A MAJOR
 AMENDMENT TO THE PALM BEACH ATLANTIC UNIVERSITY (PBAU)
 ATHLETIC COMPLEX COMMUNITY SERVICE PLANNED DEVELOPMENT
 (CSPD) SHALL BE APPROVED BY THE CITY COMMISSION. SUCH
 APPLICATION HAS BEEN SUBMITTED AND IS BEING REVIEWED AT
 THIS TIME. THE FOLLOWING COMMENTS ISSUED DURING THE
 MAJOR AMENDMENT PROCESS WILL NEED TO BE INCORPORATED
 INTO THE BUILDING PERMIT APPLICATION:
  
  A. BIKE RACKS SHALL BE PROVIDED AT THE ENTRANCE (OR
 CLOSE TO) THE BUILDING.
  
 2. SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR
 LANDSCAPING AND IRRIGATION.
  
 3. THE TRAFFIC STATEMENT (PREPARED BY KIMLEY-HORN &
 ASSOCIATES) SHALL BE ACKNOWLEDGEMENT AND/OR ACCEPTED BY
 PALM BEACH COUNTY PRIOR TO ISSUANCE OF A BUILDING
 PERMIT.
  
 4. PLEASE NOTE THAT ALL OUTSTANDING LANDSCAPING AND
 SCREENING ENCLOSURES FOR THE PBAU ATHLETIC COMPLEX WILL
 BE REQUIRED TO BE INSTALLED PRIOR TO ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY FOR THE RECREATION BUILDING.
  
 5. PLEASE INCLUDE THE SITE/MASTER PLAN, PREPARED BY
 WINSTON LEE & ASSOCIATES (LYNN BENDER), AS THIS IS THE
 OFFICIAL SITE/MASTER PLAN FOR THE PBAU ATHLETIC CAMPUS
 AND IS AN ACCURATE REPRESENTATION OF ALL SITE
 IMPROVEMENTS THAT ARE TO OCCUR AROUND THE BUILDING.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 2 Status F Date 2016-07-06 Cont ID  
Sent By jroach Date 2016-07-06 Time 09:19 Rev Time 0.00
Received By jroach Date 2016-07-06 Time 09:19 Sent To  
Notes
2016-07-06 09:28:15ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.06.2016
 PERMIT NO.: 16050249
 ADDRESS:
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW RECREATION BUILDING.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A MAJOR
 AMENDMENT TO THE PALM BEACH ATLANTIC UNIVERSITY (PBAU)
 ATHLETIC COMPLEX COMMUNITY SERVICE PLANNED DEVELOPMENT
 (CSPD) SHALL BE APPROVED BY THE CITY COMMISSION. SUCH
 APPLICATION HAS BEEN SUBMITTED AND IS BEING REVIEWED AT
 THIS TIME. THE FOLLOWING COMMENTS ISSUED DURING THE
 MAJOR AMENDMENT PROCESS WILL NEED TO BE INCORPORATED
 INTO THE BUILDING PERMIT APPLICATION:
  
  A. THE CORNER OF THE COVERED WALKWAY AT THE FAR NORTH
 END OF THE BUILDING ENCROACHES INTO AN EXISTING FPL
 EASEMENT. EASEMENT CONSENT SHALL BE PROVIDED, OR THE
 BUILDING SHALL BE ADJUSTED ACCORDINGLY.
  
  B. BIKE RACKS SHALL BE PROVIDED AT THE ENTRANCE (OR
 CLOSE TO) THE BUILDING.
  
 2. SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR
 LANDSCAPING AND IRRIGATION.
  
 3. THE TRAFFIC STATEMENT (PREPARED BY KIMLEY-HORN &
 ASSOCIATES) SHALL BE ACKNOWLEDGEMENT AND/OR ACCEPTED BY
 PALM BEACH COUNTY PRIOR TO ISSUANCE OF A BUILDING
 PERMIT.
  
 4. PLEASE NOTE THAT ALL OUTSTANDING LANDSCAPING AND
 SCREENING ENCLOSURES FOR THE PBAU ATHLETIC COMPLEX WILL
 BE REQUIRED TO BE INSTALLED PRIOR TO ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY FOR THE RECREATION BUILDING.
  
 5. PLEASE INCLUDE THE SITE/MASTER PLAN, PREPARED BY
 WINSTON LEE & ASSOCIATES (LYNN BENDER), AS THIS IS THE
 OFFICIAL SITE/MASTER PLAN FOR THE PBAU ATHLETIC CAMPUS
 AND IS AN ACCURATE REPRESENTATION OF ALL SITE
 IMPROVEMENTS THAT ARE TO OCCUR AROUND THE BUILDING.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By jroach Date 2016-06-06 Time 14:36 Rev Time 0.00
Received By jroach Date 2016-06-06 Time 14:36 Sent To  
Notes
2016-06-06 14:37:02ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.06.2016
 PERMIT NO.: 16050249
 ADDRESS:
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW RECREATION BUILDING.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A MAJOR
 AMENDMENT TO THE PALM BEACH ATLANTIC UNIVERSITY (PBAU)
 ATHLETIC COMPLEX COMMUNITY SERVICE PLANNED DEVELOPMENT
 (CSPD) SHALL BE APPROVED BY THE CITY COMMISSION. SUCH
 APPLICATION HAS BEEN SUBMITTED AND IS BEING REVIEWED AT
 THIS TIME. ANY COMMENTS ISSUED DURING THE MAJOR
 AMENDMENT PROCESS WILL NEED TO BE INCORPORATED INTO THE
 BUILDING PERMIT APPLICATION.
  
 2. SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR
 LANDSCAPING AND IRRIGATION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved