Plan Review Details - Permit 16050174
Plan Review Stops For Permit 16050174
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-05-16 Cont ID  
Sent By tklarge Date 2016-05-16 Time 11:49 Rev Time 0.00
Received By tklarge Date 2016-05-16 Time 11:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-05-12 Cont ID  
Sent By tklarge Date 2016-05-12 Time 03:44 Rev Time 0.00
Received By tklarge Date 2016-05-12 Time 03:03 Sent To  
Notes
2016-05-12 03:29:211) THIS PERMIT APPLICATION IS FOR THE INSTALLATION OF
 GAS PIPING TO A WATER HEATER, DRYER AND RANGE. THE PLAN
 THAT WAS SUBMITTED IS SEVERELY LACKING THE PREVIOUSLY
 REQUESTED INFORMATION. SUBMIT TWO COPIES OF A GAS PLAN
 THAT CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK TO BE
 DONE. FBC 107.2.1. 2ND REQUEST.
  
 2) THE FOLLOWING INFORMATION, AT A MINIMUM, SHALL BE
 SUBMITTED FOR REVIEW:
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 3) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 4.) SHOW THE TYPE (S) OF ALL PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD
 NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 5) TYPE OF GAS (LP OR NATURAL).
  
 6) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
  
 7.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN
 THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 8.) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL
 APPLIANCES PER THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR
 2014 FBC-RES. SEC. G 2407.
  
 9.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 10) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
  
 11). SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
  
 12.) SHOW THE LOCATION OF ALL MEDIUM PRESSURE
 REGULATORS ( IF APPLICABLE ). A LISTED SHUTOFF VALVE
 SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP
 REGULATOR PER 2014 FGC SEC.409.4.
  
 13) SEDIMENT TRAPS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE 2014 FGC SEC.408.4.
  
 14) SUBMIT TWO COPIES OF THE APPROPRIATE SIZING TABLE
 FROM THE 2014 FUEL GAS CODE FOR THE SIZING OF THIS
 SYSTEM. FBC 107.2.1.
  
 NOTE: IT IS OBVIOUS THAT MY REVIEW COMMENTS HAVE NOT
 BEEN ADDRESSED OR EVEN READ. IF THE GAS PLAN GETS
 TURNED DOWN AGAIN, 4 TIMES THE PLAN REVIEW FEE SHALL BE
 PAID AT THE TIME OF RESUBMITTAL IN ACCORDANCE WITH FLA.
 STATUTE 553.80 (2) ( B).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-05-10 Cont ID  
Sent By tklarge Date 2016-05-10 Time 08:29 Rev Time 0.00
Received By tklarge Date 2016-05-10 Time 06:22 Sent To  
Notes
2016-05-10 07:02:411) THIS PERMIT APPLICATION IS FOR THE INSTALLATION OF
 GAS PIPING TO A WATER HEATER, DRYER AND RANGE YET A GAS
 PLAN HAS NOT BEEN SUBMITTED, ONLY AN ELECTRICAL PLAN
 SHOWING THESE APPLIANCES AS ELECTRIC.. SUBMIT TWO
 COPIES OF A GAS PLAN THAT CLEARLY REFLECTS THE ENTIRE
 SCOPE OF WORK TO BE DONE. FBC 107.2.1.
 2) THE FOLLOWING INFORMATION, AT A MINIMUM, SHALL BE
 SUBMITTED FOR REVIEW:
  
 GAS PERMIT APPLICATION REQUIREMENTS
 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 5. TYPE OF GAS (LP OR NATURAL).
  
 6 BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
  
 7. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL
 APPLIANCES PER THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR
 2014 FBC-RES. SEC. G 2407.
  
 9. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 10. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
  
 12. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
  
 13. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
  
 14 CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE
 GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED
 PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA
 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED
 PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK
 SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT
 WIND LOAD PER THE FLORIDA BUILDING CODE.
  
 15. SHOW THE LOCATION OF ALL MEDIUM PRESSURE REGULATORS
 ( IF APPLICABLE ). A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR PER
 2014 FGC SEC.409.4.
  
 17) SEDIMENT TRAPS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE 2014 FGC SEC.408.4.
  
 18) SUBMIT TWO COPIES OF THE APPROPRIATE SIZING TABLE
 FROM THE 2014 FUEL GAS CODE FOR THE SIZING OF THIS
 SYSTEM. FBC 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-16 Cont ID  
Sent By tklarge Date 2016-05-16 Time 11:49 Rev Time 0.00
Received By tklarge Date 2016-05-16 Time 11:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-12 Cont ID  
Sent By tklarge Date 2016-05-12 Time 03:45 Rev Time 0.00
Received By tklarge Date 2016-05-10 Time 13:42 Sent To  
Notes
2016-05-11 13:42:26RESUB OF REVISION ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-10 Cont ID  
Sent By tklarge Date 2016-05-10 Time 08:29 Rev Time 0.00
Received By tklarge Date 2016-05-04 Time 06:40 Sent To  
Notes
2016-05-05 06:40:59PLUMB -$5000