2016-05-10 07:02:41 | 1) THIS PERMIT APPLICATION IS FOR THE INSTALLATION OF |
| GAS PIPING TO A WATER HEATER, DRYER AND RANGE YET A GAS |
| PLAN HAS NOT BEEN SUBMITTED, ONLY AN ELECTRICAL PLAN |
| SHOWING THESE APPLIANCES AS ELECTRIC.. SUBMIT TWO |
| COPIES OF A GAS PLAN THAT CLEARLY REFLECTS THE ENTIRE |
| SCOPE OF WORK TO BE DONE. FBC 107.2.1. |
| 2) THE FOLLOWING INFORMATION, AT A MINIMUM, SHALL BE |
| SUBMITTED FOR REVIEW: |
| |
| GAS PERMIT APPLICATION REQUIREMENTS |
| 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. |
| G2413. |
| |
| 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING |
| (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO |
| FBC SEC.107.2.1. |
| |
| 5. TYPE OF GAS (LP OR NATURAL). |
| |
| 6 BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8 |
| THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR |
| 2014 FBC-RES. SEC. G2413. |
| |
| 7. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER |
| OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS |
| SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| |
| 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL |
| APPLIANCES PER THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR |
| 2014 FBC-RES. SEC. G 2407. |
| |
| 9. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| SEC. G2413.2. . |
| |
| 10. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426. |
| |
| 12. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. |
| |
| 13. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF |
| THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| 14 CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE |
| GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED |
| PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA |
| 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED |
| PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK |
| SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT |
| WIND LOAD PER THE FLORIDA BUILDING CODE. |
| |
| 15. SHOW THE LOCATION OF ALL MEDIUM PRESSURE REGULATORS |
| ( IF APPLICABLE ). A LISTED SHUTOFF VALVE SHALL BE |
| INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR PER |
| 2014 FGC SEC.409.4. |
| |
| 17) SEDIMENT TRAPS SHALL BE INSTALLED IN ACCORDANCE |
| WITH THE 2014 FGC SEC.408.4. |
| |
| 18) SUBMIT TWO COPIES OF THE APPROPRIATE SIZING TABLE |
| FROM THE 2014 FUEL GAS CODE FOR THE SIZING OF THIS |
| SYSTEM. FBC 107.2.1. |
| |