Plan Review Details - Permit 16050165
Plan Review Stops For Permit 16050165
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-07 Cont ID  
Sent By jwitmer Date 2016-05-07 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2016-05-07 Time 07:29 Sent To  
Notes
2016-05-07 08:32:24BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050165
 ADD: 1919 N. FLAGLER DR. SUITE# ____
 CONT: ANDERSON-MOORE
 TEL: 561-662-1819
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 07/2016
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION NOR THE TITLEBLOCK OF THE
 PLANS PROVIDES THE LOCATION OF THE TENANT SPACE JUST
 THE 3RD FLOOR. THIS PROJECT IS NOT IN THE COMMON
 CORRIDOR BUT A TENANT SPACE, PLEASE PROVIDE THE TENNANT
 SUITE NUMBER.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS..
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION OF TTHE PROJECT...
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004 TITLE BLOCK.
 (3) NAME OR IDENTIFICATION OF PROJECT. THE TENANT SPACE
 IS NOT IDENTIFIED.
  
 2) SHEET A3.2 DETAIL E8 SHOWS A MICROWAVE, PLEASE
 INDICATE HOW COMPLIANCE WITH 2014 FL. ACCESS. CODE308.1
 REACH RANGES & 309.3
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-10 Cont ID  
Sent By vperez Date 2016-05-10 Time 13:50 Rev Time 0.00
Received By vperez Date 2016-05-10 Time 10:47 Sent To  
Notes
2016-05-10 13:51:10INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY OR CORRECT CIRCUIT #8 SHOWN AS A
 2POLE 60 AMP BREAKER ON A #12 CONDUCTOR. FBC 107.3.5
 2. SHOW THAT THERE IS A WP/GFCI RECEPTACLE WITHIN 25FT
 OF THE ROOFTOP UNITS ON THE FLOOR PLAN. NEC 210.63
 3. PROVIDE A NOTE TO INDICATE REQUIRED LOW VOLTAGE
 SYSTEMS (ACCESS, DATA ETC.) SEPARATE PERMITS. A NOTE
 WILL SUFFICE.
 4. PLEASE LABEL GFCI PROTECTED ALL RECEPTACLES IN THE
 BREAK ROOM WITHIN 6FT OF SINK. NEC 210.8B7
 5. PROVIDE A NOTE TO INDICATE REQUIREMENTS OF NEC
 410.130G1-REQUIRED DISCONNECTING MEAN FOR ALL
 FLORESCENT LUMINAIRES THAT UTILIZE DOUBLE ENDED LAMPS,
 SEE VERBIAGE IN CODE.
 6. PROVIDE SIZE OF THE EXISTING 3RD FLA WEST MAIN
 BREAKER.
 7. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-10 Cont ID  
Sent By scaldero Date 2016-05-10 Time 14:28 Rev Time 0.00
Received By scaldero Date 2016-05-10 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-11 Time 15:37 Rev Time 0.00
Received By shill Date 2016-05-04 Time 07:52 Sent To  
Notes
2016-05-05 07:54:10B01

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-11 Cont ID  
Sent By ccole Date 2016-05-11 Time 16:22 Rev Time 0.00
Received By ccole Date 2016-05-11 Time 16:22 Sent To  
Notes
2016-05-11 16:46:561ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050165
 5/11/16
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 3-TON RTU- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
 2) PROVIDE EXHAUST VENTILATION FOR THE KITCHENETTE-
 TABLE 6-4 ASHRAE 62.1-2010.
 3) PROVIDE A MECHANICAL ROOF PLAN SHOWING LOCATION OF
 THE NEW RTU AND THE CONDENSATE PIPE DISPOSAL RUN AND
 DISCHARGE LOCATION.
 4) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE O/A- SECTION
 C403.2.4.4 FBC-14 ENERGY.
 5) THE RTU ANCHORING DETAIL IS INCOMPLETE: A) PROVIDE
 COMPLETE WIND LOAD DESIGN CRITERIA- INCLUDING THE
 EXPOSURE CATEGORY AND HEIGHT ADJUSTMENT COEFFICIENT,
 AND DESIGN PRESSURES. B) INDICATE HOW THE CURB WILL BE
 ATTACHED TO THE ROOF STRUCTURE
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-11 Cont ID  
Sent By gjohnson Date 2016-05-11 Time 17:10 Rev Time 0.00
Received By gjohnson Date 2016-05-11 Time 17:10 Sent To  
Notes
***NONE***