Plan Review Details - Permit 16050024
Plan Review Stops For Permit 16050024
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-07 Cont ID  
Sent By jwitmer Date 2016-05-07 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2016-05-07 Time 08:33 Sent To  
Notes
2016-05-07 10:08:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050024
 ADD: 550 QUADRILLE BLVD. SUITE # 100
 CONT: DURHAM BROTHERS
 TEL: 561-662-0736
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 07/2016
 ACTION: DENIED
  
 2014 FBC-BUILDING .
  
 1) PLEASE SUBMIT THE PRELIMINARY PLAN APPROVAL BY THE
 AGENCY FOR HEALTH CARE ADMINISTRATION (THE AGENCY) OR
 AT THE FIRST CONSTRUCTION DOCUMENT REVIEW IF THERE HAS
 BEEN NO PREVIOUS PRELIMINARY PLAN APPROVAL FOR THAT
 PROJECT FOR STATE LICENSURE PURPOSES, THESE CODES AND
 STANDARDS SHALL BE APPLICABLE TO THE PROJECT ON THE
 EFFECTIVE DATE OF THIS CODE.
  
 2) 451.2 ADDITIONAL CODES AND STANDARDS FOR THE DESIGN
 AND CONSTRUCTION OF AMBULATORY SURGICAL CENTERS AND,
 UNLESS EXEMPTED BY CHAPTER 395.0163, FLORIDA STATUTES,
 ALL AMBULATORY SURGICAL CENTER OUTPATIENT FACILITIES
 AND AMBULATORY SURGICAL CENTER MOBILE AND TRANSPORTABLE
 UNITS.
 IN ADDITION TO THE MINIMUM STANDARDS REQUIRED BY
 SECTION 451 OF THIS CODE, CHAPTER 59A-5, FLORIDA
 ADMINISTRATIVE CODE OR BY CHAPTER 395, FLORIDA
 STATUTES, ALL NEW AMBULATORY SURGICAL CENTERS AND ALL
 ADDITIONS, ALTERATIONS OR RENOVATIONS TO EXISTING
 AMBULATORY SURGICAL CENTERS SHALL ALSO BE IN COMPLIANCE
 WITH THE FOLLOWING CODES AND STANDARDS ON THE EFFECTIVE
 DATE OF THIS CODE AS DESCRIBED IN SECTION 451.1.5 OF
 THIS CODE.
  
 FBC-B 451.2.1 THE FIRE CODES DESCRIBED IN CHAPTER
 69A-3.012, STANDARDS OF THE NATIONAL FIRE PROTECTION
 ASSOCIATION ADOPTED, FLORIDA ADMINISTRATIVE CODE.
  
 FBC-B 451.2.2 GUIDELINES FOR DESIGN AND CONSTRUCTION OF
 HEALTH CARE FACILITIES (THE GUIDELINES), AS REFERENCE
 IN CHAPTER 35 OF THIS CODE. PLEASE REFER TO 2010
 EDITION SECTION 3.7SPECIFIC REQUIREMENTS FOR OUTPATIENT
 SURGICAL FACILITIES.
  
  
 3)2014 FBC-B 451.3.1 IN ADDITION TO THE CODES AND
 STANDARDS REFERENCED IN SECTION 451.2, THE MINIMUM
 STANDARDS OF CONSTRUCTION AND SPECIFIED MINIMUM
 ESSENTIAL FACILITIES DESCRIBED IN SECTION 451.3 SHALL
 APPLY TO ALL AMBULATORY SURGICAL CENTERS AS DESCRIBED
 IN SECTION 451.1. AND TO ALL NEW ADDITIONS, ALTERATIONS
 OR RENOVATIONS TO EXISTING AMBULATORY SURGICAL CENTER
 ON THE EFFECTIVE DATE OF THE CODE.
  
 3A) 451.3.2 OPERATING ROOMS. (REFERENCE THE GUIDELINES
 FOR OTHER REQUIREMENTS.)
  
 3B) 451.3.2.1 ALL AMBULATORY SURGICAL CENTERS SHALL BE
 EQUIPPED WITH A MINIMUM OF ONE OPERATING ROOM THAT IS
 IN COMPLIANCE WITH THE REQUIREMENTS OF A CLASS C
 OPERATING ROOM AS DESCRIBED IN THE GUIDELINES. ONLY
 CLASS C OPERATING ROOMS WILL BE LISTED AS OPERATING
 ROOMS FOR PURPOSES OF LICENSURE.
  
 3C) 451.3.2.2 IF PROVIDED, ALL CLASS A OR CLASS B
 OPERATING ROOMS, AND ALL PROCEDURE, EXAMINATION, OR
 TREATMENT ROOMS SHALL MEET THE REQUIREMENTS FOR THESE
 ROOMS AS DESCRIBED IN THE GUIDELINES.
  
 3D) 451.3.3 RECOVERY AREA. (REFERENCE THE GUIDELINES
 FOR OTHER REQUIREMENTS.)
  
 3E) 451.3.3.1 ONLY THE POST-ANESTHESIA RECOVERY
 POSITIONS, AS DESCRIBED IN THE GUIDELINES, WILL BE
 LISTED AS RECOVERY POSITIONS FOR PURPOSES OF LICENSURE.
  
 3F) 451.3.3.1.1 WHERE IT IS NOT POSSIBLE TO INSPECT A
 FIRE RATED PARTITION, WALL OR BARRIER OR A SMOKE
 BARRIER THAT EXTENDS THROUGH THE ATTIC OR INTERSTITIAL
 SPACE TO THE ROOF OR FLOOR DECK ABOVE BECAUSE OF THE
 LOCATION OF A MONOLITHIC CEILING MEMBRANE, CEILING
 ACCESS PANEL(S) SHALL BE INSTALLED ADJACENT TO EACH
 SIDE OF THE PARTITION, WALL OR BARRIER AT INTERVALS NOT
 EXCEEDING 30 FEET (9.00 M) AND IN SUCH LOCATIONS AS
 NECESSARY TO VIEW ALL SURFACES OF THE PARTITION, WALL
 OR BARRIER. OTHER CEILING ACCESS PANELS SHALL ONLY BE
 INSTALLED AS REQUIRED BY OTHER SECTIONS OF THE CODE.
 PARTITIONS, WALLS AND BARRIERS REQUIRING PROTECTED
 OPENINGS OR PENETRATIONS SHALL BE IDENTIFIED IN
 ACCORDANCE WITH SECTION 703 OF THIS CODE.
  
 4) 451.3.6 AIR-CONDITIONING, HEATING AND VENTILATING
 SYSTEMS.
 (REFERENCE THE GUIDELINES FOR OTHER REQUIREMENTS.)
  
 4A) 451.3.6.1 AIR-HANDLING EQUIPMENT SHALL BE LOCATED
 EITHER ON THE ROOF OF THE BUILDING IT SERVES OR IN
 MECHANICAL EQUIPMENT ROOMS UNLESS IT SERVES ONLY ONE
 ROOM AND IS LOCATED IN THAT ROOM. IN BUILDINGS WITH
 MULTIPLE USES, TENANTS OR OCCUPANCIES, THE LICENSED
 HEALTH CARE AREAS REQUIRED BY THIS CODE TO MAINTAIN
 FILTER EFFICIENCIES AND RELATIVE AIR PRESSURE
 RELATIONSHIPS SHALL BE SERVED BY SEPARATE DUCTED
 MECHANICAL AIR SUPPLY, RETURN AND EXHAUST SYSTEMS. THIS
 EQUIPMENT MAY BE LOCATED IN OTHER AREAS OF THE BUILDING
 OR IN THE SAME ROOM AS THE BUILDING AIR-HANDLING
 EQUIPMENT IF ACCESS DURING NORMAL BUSINESS HOURS IS
 AVAILABLE.
  
 4B) 451.3.6.2 VARIABLE VOLUME SYSTEMS SHALL NOT BE
 PERMITTED IN SURGICAL PROCEDURES ROOMS AND RECOVERY
 ROOMS.
  
 4C) 451.3.6.3 FRIABLE DUCT LININGS EXPOSED TO AIR
 MOVEMENT SHALL NOT BE USED IN DUCTS, TERMINAL BOXES OR
 OTHER SYSTEMS SUPPLYING OPERATING ROOMS AND RECOVERY
 ROOMS, UNLESS TERMINAL FILTERS OF AT LEAST 90-PERCENT
 EFFICIENCY ARE INSTALLED DOWNSTREAM OF LININGS.
 FLEXIBLE DUCT WORK SHALL HAVE A CONTINUOUS METAL INNER
 LINER ENCASED BY INSULATING MATERIAL WITH AN OUTER
 VAPOR JACKET CONFORMING TO UL 181 UNLESS THE FLEXIBLE
 DUCT MEETS THE FOLLOWING CRITERIA.
  
 4D) 451.3.6.3.1 . THE DUCT CONFORMS TO UL CLASS 1 AIR
 DUCT, STANDARD 181 WITH MINIMUM RATED AIR VELOCITY OF
 4,000 FEET PER MINUTE, AND IS PRESSURE RATED FOR A
 MINIMUM OF 4-INCHES WATER GAGE POSITIVE PRESSURE AND
 1-INCH WATER GAGE NEGATIVE PRESSURE.
  
 4E) 451.3.6.3.2 THE INNER CORE OF THE DUCT IS
 CONSTRUCTED OF CHLORINATED POLYETHYLENE (CPE) MATERIAL
 ENCIRCLING A STEEL HELIX BONDED TO THE CPE.
  
 4F) 451.3.6.3.3 THE DUCT HAS A FIRE-RETARDANT METALIZED
 VAPOR BARRIER THAT IS REINFORCED WITH CROSSHATCHED
 FIBERGLASS SCRIM HAVING A PERMANENCE OF NOT GREATER
 THAN 0.05 PERMS WHEN TESTED IN ACCORDANCE WITH ASTM E
 96 PROCEDURE A.
  
 4G) 451.3.6.3.4 THE DUCT HAS PASSED AN IMPACT TEST
 SIMILAR TO THE UL 181 STANDARD, CONDUCTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) EXCEPT
 IT SHALL USE A 25-POUND (11 KG) WEIGHT DROPPED FROM A
 HEIGHT OF 10 FEET (3.048 M). AS A RESULT OF THE TEST,
 THE INNER AND OUTER SURFACES OF THE SAMPLE SHALL NOT
 HAVE RUPTURED, BROKEN, TORN, RIPPED, COLLAPSED OR
 SEPARATED IN ORDER FOR THE DUCT TO PASS THE TEST. IN
 ADDITION, THE HELIX SHALL REBOUND TO A CROSS-SECTIONAL
 ELLIPTICAL AREA NOT LESS THAN 80 PERCENT OF THE
 ORIGINAL TEST SAMPLE DIAMETER. THE USE OF FLEXIBLE DUCT
 SHALL BE LIMITED TO FLEXIBLE AIR CONNECTOR
 APPLICATIONS.
  
 4H) 451.3.6.4 FILTER HOUSING FRAME BLANK-OFF PANELS
 SHALL BE PERMANENTLY ATTACHED TO THE FRAME, CONSTRUCTED
 OF RIGID MATERIALS AND HAVE SEALING SURFACES EQUAL TO
 OR GREATER THAN THE FILTER MEDIA INSTALLED IN THE
 FILTER FRAME. ALL JOINTS BETWEEN THE BLANK-OFF PANELS,
 FILTER HOUSING FRAMES AND FILTER SUPPORT STRUCTURE
 SHALL BE CAULKED AIR TIGHT.
  
 4I) 451.3.7 FAN AND DAMPER CONTROL DURING FIRE ALARM.
  
 4J) 451.3.7.1 DURING AN AUTOMATIC FIRE ALARM
 ACTIVATION, FAN SYSTEMS AND FAN EQUIPMENT SERVING MORE
 THAN ONE ROOM SHALL BE STOPPED TO PREVENT THE MOVEMENT
 OF SMOKE BY MECHANICAL MEANS FROM THE ZONE IN ALARM TO
 ADJACENT SMOKE ZONES OR TO ADJACENT AREAS WITHIN THE
 SMOKE ZONE IF THERE IS ONLY ONE ZONE IN THE FACILITY.
  
 4K) 451.3.7.2 FAN CONTROL SHALL BE DESIGNED SO AS TO
 MINIMIZE THE INTERRUPTION OF HEATING, VENTILATING AND
 AIR CONDITIONING IN COMPARTMENTS REMOTE FROM THE
 COMPARTMENT IN ALARM.
  
 4L) 451.3.7.3 FAN CONTROL SHALL NOT INTERFERE WITH THE
 CONTINUOUS OPERATION OF EXHAUST SYSTEMS CONVEYING
 ETHYLENE OXIDE OR OTHER HAZARDOUS CHEMICALS AND FUMES
 OR SYSTEMS REQUIRED TO OPERATE CONTINUOUSLY FOR THE
 HEALTH AND SAFETY OF OCCUPANTS. AIR-HANDLING SYSTEMS
 SHALL BE DESIGNED TO ALLOW FOR CONTINUOUS OPERATION OF
 ALL SUCH SYSTEMS AND TO MINIMIZE MOVEMENT OF SMOKE BY
 MECHANICAL MEANS FROM THE ZONE IN ALARM.
  
 5) 451.3.9 FIRE PUMP.
  
 5A) 451.3.9.1 WHERE REQUIRED IN NEW CONSTRUCTION, FIRE
 PUMPS AND ANCILLARY EQUIPMENT SHALL BE SEPARATED FROM
 OTHER FUNCTIONS BY CONSTRUCTION HAVING A 2-HOUR
 FIRE-RESISTANCE RATING.
  
 5B) 451.3.9.2 THE FIRE PUMP NORMAL SERVICE DISCONNECT
 SHALL BE RATED TO HOLD LOCKED ROTOR CURRENT
 INDEFINITELY. IF THE APPROVED NORMAL SERVICE DISCONNECT
 IS LOCATED ON THE EXTERIOR, IT SHALL BE SUPERVISED BY
 CONNECTION TO THE FIRE PUMP REMOTE ANNUNCIATOR AND
 SHALL PROVIDE A SEPARATE FIRE ALARM SYSTEM TROUBLE
 INDICATION.
  
 5C) 451.3.9.3 WHEN THE FIRE PUMP IS PLACED ON THE
 EMERGENCY SYSTEM IN ADDITION TO THE NORMAL SUPPLY, THE
 EMERGENCY FEEDER PROTECTIVE DEVICE SHALL BE SIZED IN
 ACCORDANCE WITH MAXIMUM RATING OR SETTINGS OF CHAPTER
 27 OF THIS CODE.
  
 5D) 451.3.9.4 THE FIRE PUMP TRANSFER SWITCH MAY BE
 EITHER MANUAL OR AUTOMATIC. IF LOCATED ON THE LINE SIDE
 OF THE CONTROLLER AS A SEPARATE UNIT, THE SWITCH MUST
 BE RATED FOR THE PUMP MOTOR LOCKED ROTOR CURRENT
 INDEFINITELY AND MUST BE LOCATED IN THE PUMP ROOM.
  
 5E) 451.3.9.5 COMBINATION FIRE PUMP CONTROLLER AND
 TRANSFER SWITCH UNITS LISTED BY THE UNDERWRITER?S
 LABORATORIES, INC., AS PRESCRIBED BY CHAPTER 27 OF THIS
 CODE ARE ACCEPTABLE WHEN THE TRANSFER SWITCH HAS
 EXPOSABLE AND REPLACEABLE CONTACTS, NOT
 CIRCUIT-BREAKER-TYPES, RATED FOR THE AVAILABLE
 SHORT-CIRCUIT CURRENT.
  
 5F) 451.3.9.6 THE FIRE PUMP SHALL BE INSTALLED IN A
 READILY ACCESSIBLE LOCATION WHEN IT IS LOCATED ON THE
 GRADE LEVEL FLOOR, THERE SHALL BE DIRECT ACCESS FROM
 THE EXTERIOR.
  
 5G) 451.3.10 ELECTRICAL REQUIREMENTS. (REFERENCE THE
 GUIDELINES FOR OTHER REQUIREMENTS.)
  
 5H) 451.3.10.1 ALL MATERIAL, INCLUDING EQUIPMENT,
 CONDUCTORS, CONTROLS, AND SIGNALING DEVICES, SHALL BE
 INSTALLED TO PROVIDE A COMPLETE ELECTRICAL SYSTEM WITH
 THE NECESSARY CHARACTERISTICS AND CAPACITY TO SUPPLY
 THE ELECTRICAL FACILITIES SHOWN IN THE SPECIFICATIONS
 OR INDICATED ON THE PLANS.
  
 5I) 451.3.10.2 ALL MATERIALS AND EQUIPMENT SHALL BE
 FACTORY LISTED AS COMPLYING WITH APPLICABLE STANDARDS
 OF UNDERWRITER?S LABORATORIES, INC., OR OTHER SIMILARLY
 ESTABLISHED STANDARDS OF A NATIONALLY RECOGNIZED
 TESTING LABORATORY (NRTL) THAT HAS BEEN CERTIFIED BY
 THE OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
 (OSHA) FOR THAT REFERENCED STANDARD.
  
 5J) 451.3.10.3 FIELD LABELING OF EQUIPMENT AND
 MATERIALS SHALL BE PERMITTED ONLY WHEN PROVIDED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY THAT HAS BEEN
 CERTIFIED BY THE OCCUPATIONAL SAFETY AND HEALTH
 ADMINISTRATION (OSHA) FOR THAT REFERENCED STANDARD.
  
 5K) 451.3.10.4 THERE SHALL BE DOCUMENTATION FOR
 EQUIPOTENTIAL GROUNDING IN ALL PATIENT CARE AREAS,
 BUILDING SERVICE GROUND ELECTRODE SYSTEMS, AND SPECIAL
 SYSTEMS SUCH AS FIRE ALARM, NURSE CALL, PAGING,
 GENERATOR, EMERGENCY POWER AND BREAKER COORDINATION.
  
 5L) 451.3.10.5 ALL SPACES OCCUPIED BY PEOPLE, MACHINERY
 AND EQUIPMENT WITHIN BUILDINGS, AND THE APPROACHES
 THERETO, AND PARKING LOTS, SHALL HAVE ELECTRIC
 LIGHTING.
  
 5M) 451.3.10.6 PATIENTS? RECOVERY ROOMS SHALL HAVE
 GENERAL LIGHTING. FIXED LIGHTS NOT SWITCHED AT THE DOOR
 SHALL HAVE SWITCH CONTROLS CONVENIENT FOR USE AT THE
 LUMINARIES. ALL SWITCHES FOR CONTROL OF LIGHTING IN
 RECOVERY AREAS SHALL BE OF THE QUIET OPERATING TYPE.
  
 5N) 451.3.10.7 OPERATING ROOMS SHALL HAVE GENERAL
 LIGHTING FOR THE ROOM IN ADDITION TO LOCALIZED
 SPECIALIZED LIGHTING PROVIDED BY A SPECIAL LIGHTING
 UNIT REQUIRED AT THE SURGICAL TABLE. THE TYPE OF
 SPECIAL LIGHTING UNIT SHALL BE AS SPECIFIED BY THE
 FUNCTIONAL PROGRAM OF THE FACILITY. EACH SPECIAL
 LIGHTING UNIT FOR LOCALIZED LIGHTING AT THE SURGICAL
 TABLE SHALL BE PERMANENTLY INSTALLED AND PERMANENTLY
 CONNECTED TO AN INDEPENDENT CIRCUIT THAT SHALL BE
 POWERED FROM THE CRITICAL BRANCH. IN ADDITION, A
 MINIMUM OF ONE GENERAL PURPOSE LIGHTING FIXTURE SHALL
 BE POWERED FROM A NORMAL CIRCUIT IN ALL OPERATING
 ROOMS.
  
 5O) 451.3.10.8 THE NUMBER AND CIRCUITRY OF ALL DUPLEX
 RECEPTACLES IN OPERATING ROOMS, CARDIAC CATHETERIZATION
 LABORATORIES, AND POST-OPERATIVE RECOVERY ROOMS, SHALL
 BE PROVIDED AS FOLLOWS:
  
 5P) 451.3.10.8.1 A MINIMUM OF FOUR DUPLEX RECEPTACLES
 SHALL BE CONNECTED TO THE CRITICAL BRANCH OF THE
 ESSENTIAL ELECTRICAL SYSTEM.
  
 5Q) 451.3.10.8.2 A MINIMUM OF TWO DUPLEX RECEPTACLES
 SHALL BE CONNECTED TO A NORMAL POWER CIRCUIT OR TO A
 CRITICAL BRANCH CIRCUIT
  
 6) 451.3.13.1 A TYPE 1 ESSENTIAL ELECTRICAL SYSTEM
 SHALL BE PROVIDED IN AMBULATORY SURGICAL CENTERS AS
 DESCRIBED IN NFPA 99, HEALTH CARE FACILITIES CODE. THE
 EMERGENCY POWER FOR THIS SYSTEM SHALL MEET THE
 REQUIREMENTS OF A LEVEL 1, TYPE 10, CLASS 8 GENERATOR
 AS DESCRIBED IN NFPA 110, EMERGENCY STANDBY POWER
 SYSTEMS.
  
 6A) 451.3.13.2. IN NEW CONSTRUCTION, THE NORMAL MAIN
 SERVICE EQUIPMENT SHALL BE SEPARATED FROM THE EMERGENCY
 DISTRIBUTION EQUIPMENT BY LOCATING IT IN A SEPARATE
 ROOM. TRANSFER SWITCHES SHALL BE CONSIDERED EMERGENCY
 DISTRIBUTION EQUIPMENT FOR THIS PURPOSE.
  
 6B) 451.3.13.3 THE GENERATOR REMOTE ANNUNCIATOR SHALL
 BE LOCATED IN A LOCATION THAT IS STAFFED DURING THE
 HOURS OF OPERATION OF THE AMBULATORY SURGICAL CENTER.
  
 6C) 451.3.13.4 SWITCHES FOR CRITICAL BRANCH LIGHTING
 SHALL BE TOTALLY SEPARATE FROM NORMAL SWITCHING.
 CRITICAL BRANCH SWITCHES MAY BE ADJACENT TO NORMAL
 SWITCHES. SWITCHES FOR LIFE SAFETY LIGHTING ARE NOT
 PERMITTED EXCEPT AS REQUIRED FOR DUSK-TO-DAWN AUTOMATIC
 CONTROL OF EXTERIOR LIGHTING FIXTURES.
  
 6D) 451.3.13.5 THERE SHALL BE SELECTED LIFE SAFETY
 LIGHTING PROVIDED AT A MINIMUM OF 1 FOOTCANDLE (10 LUX)
 AND DESIGNED FOR AUTOMATIC DUSK-TO-DAWN OPERATION ALONG
 THE TRAVEL PATHS FROM THE EXITS TO THE PUBLIC WAY OR TO
 SAFE AREAS LOCATED A MINIMUM OF 30 FEET (9.144 M) FROM
 THE BUILDING.
  
 6E) 451.3.13.7 IF A DAY TANK IS PROVIDED, IT SHALL BE
 EQUIPPED WITH A DEDICATED LOW LEVEL FUEL ALARM AND A
 MANUAL PUMP. THE ALARM SHALL BE LOCATED AT THE
 GENERATOR DERANGEMENT PANEL.
  
 6F) 451.3.13.8 TRANSFER SWITCH CONTACTS SHALL BE OF THE
 OPEN TYPE AND SHALL BE ACCESSIBLE FOR INSPECTION AND
 REPLACEMENT.
  
 6G) 451.3.13.9 ELECTRIC LIGHTING REQUIRED TO PROVIDE
 CARE AND SERVICE TO THE PATIENT OCCUPIED AREAS AND THE
 NECESSARY PATIENT SUPPORT AREAS SHALL BE CONNECTED TO
 THE ESSENTIAL ELECTRICAL SYSTEM.
  
 7) 451.3.15 MEDICAL GAS. IF THERE IS A PIPED MEDICAL
 GAS INSTALLATION IN THE ASC, IT SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 99, HEALTH CARE FACILITIES CODE.
 SHEET A2.0 SHOWS 2 CYLINDER TANKS PLEASE PROVIDE WHAT
 TYPE OF GASSES ARE TO BE STORED IN THESE TANKS, THE
 QUANTITY OF GASSES TO BE STORED MSDS SHEETS FOR THE
 TYPE OF GAS AND IF THESE TYPE OF GASSES WILL REQUIRE
 FIRE RATED WALLS AND BE CONSIDERED CONTROL AREAS. 2014
 FBC-B TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITY PER
 CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL
 HAZARD.
  
 8) THE PLANS FAIL TO PROVIDE A SITE PLAN SHOWING THE
 LOCATION OF THE FIRE PUMP, GENERATOR AND THE REQUIRED
 PARKING SPACES. GUIDELINES FOR DESIGN AND CONSTRUCTION
 OF HEALTH CARE FACILITIES (THE GUIDELINES), AS
 REFERENCE IN CHAPTER 35 OF THIS CODE. PLEASE REFER TO
 2010 EDITION SECTION 3.7SPECIFIC REQUIREMENTS FOR
 OUTPATIENT SURGICAL FACILITIES. 3.7-1.3.2.1 FOUR SPACES
 SHALL BE PROVIDED FOR EACH ROOM ROUTINELY USED FOR
 SURGICAL PROCEDURES PLUS ONE SPACE FOR EACH STAFF
 MEMBER.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By albarran Date 2016-05-04 Time 14:42 Rev Time 0.00
Received By albarran Date 2016-05-04 Time 13:53 Sent To  
Notes
2016-05-04 16:16:191ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. NEC 422.31(B), A DISCONNECT IS MISSING FOR THE
 ELECTRIC WATER HEATER.
 2. LABEL FOR PANEL N ON THE SCHEDULE INDICATES EXISTING
 WHILE THE RISER SAYS IT IS NEW. CORRECT TO MATCH AND
 CLARIFY.
 3. NEC 110.16 ALL ELECTRICAL EQUIPMENT SHALL BE MARKED
 WITH THE ARC-FLASH HAZARD WARNING LABELS.
 4. NEC110.24 ALL ELECTRICAL APPARATUS SHALL BE DURABLY
 DATE MARKED WITH THE MAXIMUM AVAILABLE FAULT CURRENT.
 5. NEC 215.5 ALONG WITH THE RISER DIAGRAM YOU NEED TO
 SUBMIT LOAD CALCS FOR THE ADDED LOAD.
 6. FBC-EC405 MANDATORY LIGHTING CONTROLS ARE REQUIRED.
 LIGHTING CONTROL MISSING FOR ROOMS 1007, 108 & 109.
 7. FBC-EC405.5.2 PROVIDE A LIGHT DENSITY ALLOWANCE
 CHART SHOWING ENERGY CODE COMPLIANCE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-03 Cont ID  
Sent By wjolin Date 2016-05-03 Time 12:43 Rev Time 0.00
Received By wjolin Date 2016-05-03 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-18 Cont ID  
Sent By cpuell Date 2016-05-18 Time 10:30 Rev Time 0.00
Received By cpuell Date 2016-05-02 Time 17:05 Sent To  
Notes
2016-05-02 17:12:03B14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-09 Cont ID  
Sent By ccole Date 2016-05-09 Time 11:32 Rev Time 0.00
Received By ccole Date 2016-05-09 Time 11:31 Sent To  
Notes
2016-05-09 12:50:451ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050024
 5/9/16
  
 1) THE SUBMITTED PLANS FOR THE NEW SURGICAL CENTER DO
 NOT REFLECT APPLICABLE AND COMPLIANT CODE DESIGN, AND
 MUST BE REVISED TO PROVIDE ENOUGH INFORMATION FOR A
 COMPLETE MECHANICAL REVIEW.
 A) REFER TO SECTION 451 AMBULATORY SURGICAL CENTERS
 FBC-14 BUILDING AND PROVIDE DOCUMENTATION OF PLAN
 APPROVAL FROM AHCA- SECTION 451.1.5.
 B) IN ADDITION TO THE LIST OF APPLICABLE CODES ON SHEET
 CVR, THE PLANS SHALL ALSO BE DESIGNED IN ACCORDANCE
 WITH- SECTION 451.2.1: THE FIRE CODES DESCRIBED IN
 CHAPTER 69A-3.012, STANDARDS OF THE NATIONAL FIRE
 PROTECTION ASSOCIATION ADOPTED, FLORIDA ADMINISTRATIVE
 CODE & SECTION AND 451.2.2: GUIDELINES FOR DESIGN AND
 CONSTRUCTION OF HEALTH CARE FACILITIES AND ASHRAE
 170-2008.
 2) THE PLANS APPEAR TO INDICATE AN "OUTPATIENT"
 SURGICAL FACILITY. PLEASE REFER TO SECTION 3.1-8.2.1.1
 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE
 FACILTIES. REVIEW ALL SUB-SECTIONS AND ASHRAE 170-2008
 (PART 6 OF THE GUIDELINES) AND RE-DESIGN THE HVAC
 SYSTEMS ACCORDINGLY. PLEASE SEE TABLE 7-1 DESIGN
 PARAMETERS ASHRAE 170 FOR VENTILATION REQUIREMENTS.
 PROVIDE A VENTILATION TABLE ON THE PLAN FOR ALL ROOMS
 AND SPACES IN ACCORDANCRE WITH THE TABLE.
 3) THE CURRENT PLAN SHOWS A TRANSFER GRILL AT THE
 JANITOR/CORRIDOR, HOWEVER CORRIDORS SHALL NOT SERVE AS
 RETURN AIR DUCTS- SECTION 601.2 FBC-14 MECHANICAL.
 PLEASE CORRECT THE PLAN
 4) PLEASE INDICATE WHICH THE FRICTION RATE USED TO SIZE
 THE NEW SUPPLY AND RETURN DUCTS- THE MAIN DUCT TRUNKS
 APPEAR UNDERSIZED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-05 Cont ID  
Sent By gjohnson Date 2016-05-05 Time 10:07 Rev Time 0.00
Received By gjohnson Date 2016-05-05 Time 10:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-18 Cont ID  
Sent By aaponte Date 2016-05-18 Time 10:26 Rev Time 0.00
Received By aaponte Date 2016-05-18 Time 10:26 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved