Plan Review Details - Permit 16050012
Plan Review Stops For Permit 16050012
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-05-12 Cont ID  
Sent By tklarge Date 2016-05-12 Time 11:25 Rev Time 0.00
Received By tklarge Date 2016-05-12 Time 11:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By tklarge Date 2016-05-04 Time 06:32 Rev Time 0.00
Received By tklarge Date 2016-05-04 Time 06:09 Sent To  
Notes
2016-05-04 06:32:081) THERE ARE OTHER GAS APPLIANCES CONNECTED TO THIS GAS
 SYSTEM (SEE PLAN IN POOL HEATER APPLICATION FOLDER).
 THE CONSUMER LINE FROM THE METER WILL BE UNDER SIZED AT
 1 1/4 INCHES AS PRESENTLY SHOWN. THE CONSUMER LINE
 SHALL BE INCREASED TO 1 1/2 INCHES PER TABLE 402.4 (2)
 OF 2014 FGC. SHOW THIS ON YOUR DRAWING AND LIST THE
 EXISTING APPLIANCES AND THEIR BTU LOAD ON THE PLANS AND
 ALSO THE ENTIRE BBTU LOAD ON THE SYSTEM AND THE PSI OF
 THE SYSTEM.2014 FGC SEC.402.2.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATER.FBC 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-04 Cont ID  
Sent By tklarge Date 2016-05-04 Time 06:32 Rev Time 0.00
Received By tklarge Date 2016-05-02 Time 11:26 Sent To  
Notes
2016-05-02 11:26:31PLUMB -$5000