Plan Review Details - Permit 16041215
Plan Review Stops For Permit 16041215
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-02 Cont ID  
Sent By jwitmer Date 2016-06-02 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2016-06-02 Time 09:22 Sent To  
Notes
2016-06-02 13:45:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041215
 ADD: 2001 S. DIXIE HWY.
 CONT: MAC ENTERPRISES
 TEL: 561-236-3627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JUNE 02/ 2016
 ACTION: BUILDING PROVISO
  
 1) THE INTERIOR STAIRWAY WITH SHORT TREADS, PLEASE
 REVIEW THE BUILDING OFFICIAL ROBERT BROWNS REQUIREMENTS
 TO CREATE A CODE COMPLIANT SET OF STAIRS. 1009.7.2
 RISER HEIGHT AND TREAD DEPTH.
 STAIR RISER HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM
 AND 4 INCHES (102 MM) MINIMUM. THE RISER HEIGHT SHALL
 BE MEASURED VERTICALLY BETWEEN THE NOSINGS OF ADJACENT
 TREADS. RECTANGULAR TREAD DEPTHS SHALL BE 11 INCHES
 (279 MM) MINIMUM MEASURED HORIZONTALLY BETWEEN THE
 VERTICAL PLANES OF THE FOREMOST PROJECTION OF ADJACENT
 TREADS AND AT A RIGHT ANGLE TO THE TREAD?S NOSING.
  
 2A) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 2B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By jwitmer Date 2016-05-06 Time 14:08 Rev Time  
Received By jwitmer Date 2016-05-06 Time 07:30 Sent To  
Notes
2016-05-06 14:07:49BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041215
 ADD: 2001 S. DIXIE HWY.
 CONT: MAC ENTERPRISES
 TEL: 561-236-3627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 06/ 2016
 ACTION: DENIED
  
 1) SHEET A050 LIFE SAFETY PLAN:
  
 1A) NO FIRE SPRINKLER PLANS WERE SUBMITTED! BUILDING
 CODE DATA LIST THIS BUILDING AS A BLDG. TYPE III-B/
 SPRINKLERED. UNDER THE HEADING OF THE EXISTING BUILDING
 CODE A. IV(A) FIRE SPRINKLERS ARE TO BE INSTALLED UNDER
 A SEPARATE PERMIT.
 PLEASE NOTE THIS IS A CHANGE OF OCCUPANCY AND UNDER
 THE:
 EXIST. BLDG. CODE 1001.3 WHERE THE OCCUPANCY
 CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF
 SECTIONS 1002 THROUGH 1012 SHALL APPLY. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS
 WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE
 GROUP TO A DIFFERENT GROUP.
 EXIST. BUILD. CODE 1004.1 FIRE PROTECTION REQUIREMENTS
 OF SECTION 1012 SHALL APPLY WHERE A BUILDING OR
 PORTIONS THEREOF UNDERGO A CHANGE OF OCCUPANCY
 CLASSIFICATION.
 EXIST. BLDG. CODE 1012.2.1 FIRE SPRINKLER SYSTEM. WHERE
 A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
 2014 FBC-B 903.2.3 GROUP E. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE PROVIDED FOR GROUP E OCCUPANCIES AS
 FOLLOWS: (1.) THROUGHOUT ALL GROUP E FIRE AREAS GREATER
 THAN 12,000 SQUARE FEET (1115 M2) IN AREA.
 SEE FLORIDA ADMINISTRATIVE CODE 61G15-32.004 FIRE
 PROTECTION ENGINEERING DOCUMENTS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1.1. COMMERCIAL BUILDINGS:
 (5.) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 1B) IT APPEARS THERE MAY BE A DISCREPANCY IN PLANS.
 SHEET A050 LIFE SAFETY PLAN , THE BUILDING CODE DATA
 INDICATES THE AGE OR GRADES OF THE SCHOOL TO BE 9TH
 THRU THE 12TH GRADE. THE LIFE SAFETY SHEET DOES NOT
 LIST THE GRADES JUST CLASSROOM WHICH IT SHOULD SINCE
 THIS IS THE LIFE SAFETY SHEET. SHEET A101 LIST
 CLASSROOMS STARTING AT PRE-K. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED, DISCREPANCY IN PLANS.
  
 1C) IT APPEARS THERE IS A DISCREPANCY IN PLANS. SHEET
 A050 LIFE SAFETY PLAN AND SHEET A101. LIFE SAFETY PLAN
 INDICATES A CLASSROOM WITH 1315 SQ. FT. WHEREAS THE
 SAME ROOM ON SHEET A101 IS LABELED AS A MULTI- PURPOSE
 ROOM WHERE THE OCCUPANT LOAD SHOULD BE FIGURED AT 15
 SQ. FT. PER OCCUPANT. 2014 FBC-B TABLE 1004.1.2.
 DISCREPANCY IN PLANS 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 1D) SHEET A050 LIFE SAFETY PLAN AND SHEET A101 NEITHER
 SHEET LIST THE USAGE OF ROOMS 201, 202 NOR 203.
 ADDITIONAL INFORMATION REQUIRED 107.2.1.3. / 2014 FBC-B
 TABLE 1004.1.2.
  
 1E) PRE-CONSTRUCTION MEETING THAT WAS HELD AT THE
 BUILDING DEPARTMENT SHOWED THE USE OF A PORTION OF THE
 1ST FLOOR ROOF AS ACCESSIBLE AND USED AS A PLAYGROUND,
 HAS THIS AREA BEEN DELETED FROM THE PLANS? THERE IS AN
 EXTERIOR DOOR LEADING OUT ONTO WHAT APPEARS TO BE A
 BALCONY? 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. IS
 THE 1ST FLOOR ROOF STRUCTURAL MEMBERS SIZED FOR THE
 ADDITIONAL LIVE LOAD THAT WOULD BE PUT ON THESE FRAMING
 MEMBERS? 2014 FBC-B TABLE 1607.1 (26) OCCUPIABLE ROOFS?
  
 1F) THE PRE-CONSTRUCTION MEETING THAT WAS HELD AT THE
 BUILDING DEPARTMENT THERE WAS DISCUSSION ABOUT THE
 LOCATION OF PROPERTY LINES TO THE WEST AND SOUTH OF THE
 BUILDING. TO THE WEST THERE IS AN ALLEYWAY WHERE THE
 ALLOWABLE OPENINGS PER SECTION TABLE 705.8 OF THE FBC-B
 ARE EXCEEDED.
  
 1G) THE DOORS FACING THE WEST PROPERTY LINE APPEAR TO
 SWING OUT OVER THE PROPERTY LINE. FBC-B 3202.2
 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN HEIGHT.
 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE
 PUBLIC RIGHT-OF-WAY.
  
 1H) THE EXISTING BUILDING APPEARS TO HAVE SECTIONS OF
 THE BUILDING THAT TRANSGRESS THE PROPERTY LINE AS WELL
 AS NEW CONSTRUCTION THAT TRANSGRESS THE PROPERTY LINE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
  
 2) SHEET A101:
 2A) PLEASE NOTE DOOR 114B IS WITHIN 10 FEET OF THE OPEN
 SECOND FLOOR EXTERIOR LANDING AND STAIRWAY. THE DOOR
 SCHEDULE ON SHEET A601 DOES NOT SHOW COMPLIANCE WITH A
 FIRE RATED DOOR AND SIDE LITE.
 SEE 1026.6 EXTERIOR STAIRWAY AND RAMP PROTECTION.
 EXTERIOR EXIT STAIRWAYS AND RAMPS SHALL BE SEPARATED
 FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN
 SECTION 1022.2. OPENINGS SHALL BE LIMITED TO THOSE
 NECESSARY FOR EGRESS FROM NORMALLY OCCUPIED SPACES.
 DOOR 114B AND SIDE LIGHT TO BE 45 MINUTE FIRE RATED.
  
 2B) DOOR # 110 B DOES NOT COMPLY WITH THE 2014
 FBC-ACCESSIBILITY CODE 404.2.4.3 RECESSED DOORS, SEE
 FIGURE 404.2.4.3(A).
  
 3) SHEET A102;
 3A) DOOR 204 AND SIDE LIGHT ARE TO COMPLY WITH SEE
 1026.6 EXTERIOR STAIRWAY AND RAMP PROTECTION. 1HOUR
 FIRE PROTECTED AND NO GLAZING, NO SIDELIGHT. EXTERIOR
 EXIT STAIRWAYS AND RAMPS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING AS REQUIRED IN SECTION 1022.2.
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EGRESS
 FROM NORMALLY OCCUPIED SPACES.
  
 ALSO SEE 2012 IBC-B 1026.6 COMMENTARY THE BASE CODE,
 AND FIGURE 1026.6.1 FOR CROSS HATCHED SECTION OPENINGS
 LIMITED BY SECTIONS 1022.4 & 1022.5.
  
 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND RAMP
 OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 716. OPENINGS IN INTERIOR EXIT
 STAIRWAYS AND RAMPS OTHER THAN UNPROTECTED EXTERIOR
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT
 ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES
 AND FOR EGRESS FROM THE ENCLOSURE. ELEVATORS SHALL NOT
 OPEN INTO INTERIOR EXIT STAIRWAYS AND RAMPS.
  
 1022.5 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS AND RAMPS.
  
 EXCEPTION: MEMBRANE PENETRATIONS SHALL BE PERMITTED ON
 THE OUTSIDE OF THE INTERIOR EXIT STAIRWAY AND RAMP.
 SUCH PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714.3.2.
  
 4) SHEET A311 THIS SHEET HAS NOTES 501 AND 502
 INDICATING THE STAIR TREAD IS TO BE A CONCRETE FILED
 PAN SYSTEM. THERE IS NO MENTION OF THE STAIR RISER.
 PLEASE SHOW COMPLIANCE WITH 2014 ACCESS. CODE 210.1.
 INTERIOR AND EXTERIOR STAIRS THAT ARE PART OF A MEANS
 OF EGRESS SHALL COMPLY WITH 504. 504.3 OPEN RISERS.
 OPEN RISERS ARE NOT PERMITTED.
  
 5) SHEET A400; THE VARIOUS GRAB BARS FOE WATER CLOSETS
 ARE DIMENSIONED FOR HEIGHT FROM THE CENTERLINE. THE
 2014 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BAR IS DIMENSIONED FROM THE TOP OF THE GRASPING
 SURFACE.
  
 6) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
  
 7) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 8) FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. , 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 9) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. IF SO RAS 117 CALCULATIONS ARE REQUIRED BY
 EITHER A FLORIDA ARCHITECT OR ENGINEER.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 10) ROOFING: NOTICE: EFFECTIVE APRIL 1/2016 THE
 REFERENCED MIAMI-DADE COUNTY ELECTROGALVANIZED
 FASTENERS LISTINGS ARE SUSPENDED:
 11--1019.02 & 11-1019.03 BLUELINX CORP.
 12-0423.06 CONTINENAL MATERIALS, INC.
 15-1123.04 PRIME SOURCE BUILDING PRODUCTS, INC.
 13-0530.01 SPECIALTY FASTENING SYSTEM
 12-0423.03 & 12-0423.04 SUMMIT CONGLOMERATE, LLC
 12-1205.11, 12-1205.13 & 13-05 & 13-0514.05 WEATHERPRO,
 LLC
  
 11) SHEET M-103 SHOWS THE A/C CONDENSING UNITS ON THE
 TOP OF THE 2ND STORY ROOF. PLEASE PROVIDE COMPLIANCE
 WITH 2014 FBC-B 1509.6.4. WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877
 MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT
 APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE
 FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) HIGH OR WALKING ON ROOFS HAVING A SLOPE
 GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE). PERMANENT LADDERS INSTALLED TO
 PROVIDE THE REQUIRED ACCESS.
  
 12) DEPENDING ON THE FINAL LOCATION OF THE ROOF TOP A/C
 CONDENSERS COMPLIANCE WITH FBC-B 1013.6MAY BE A ISSUE.
 1013.6 MECHANICAL EQUIPMENT.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 13) IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-20 Cont ID  
Sent By vperez Date 2016-05-20 Time 14:55 Rev Time 0.00
Received By vperez Date 2016-05-20 Time 14:55 Sent To  
Notes
2016-05-20 14:55:29INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO- PLEASE PROVIDE FPL UTILITY LETTERHEAD
 REFLECTING THE AVAILABLE FAULT CURRENT AT THE
 TRANSFORMER.
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By vperez Date 2016-05-04 Time 14:42 Rev Time 0.00
Received By vperez Date 2016-05-04 Time 08:17 Sent To  
Notes
2016-05-04 14:43:01INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE UPDATE ALL REFERENCES TO OLD FBC EC 505 TO
 REFLECT NEW FBC ENERGY CONSERVATION C405.1 REQUIREMENTS
 AND C405.7.4 COMPLETION REQUIREMENTS-(DRAWINGS AND
 MANUALS. SEE VERBIAGE IN THE CODE.
 2. PROVIDE A SHOW ON PLANS THE VOLTAGE DROP
 CALCULATIONS FOR FEEDER AND BRANCH CIRCUITS PER FBC EC
 C405.7 ELECTRICAL POWER MANDATORY
 3. NOTE REGARDING SEPARATE PERMIT FOR UTILITY
 TRANSFORMER WILL NOT SUFFICE FOR REVIEW APPROVAL AS WE
 NEED TO DETERMINE THAT THE AVAILABLE FAULT CURRENT AT
 TRANSFORMER FROM THE UTILITY TO CERTIFY OUT THAT THE
 EQUIPMENT AIC RATINGS SHOWN IS WITHIN COMPLIANCE.
 4. ADDRESS ALL AND ANY FIRE DEPARTMENT COMMENTS RELATED
 TO THE ELECTRICAL SCOPE.
 5. LABEL THE ONE-LINE SERVICE RISER MAINS TO BE RATED
 FOR SERVICE ENTRANCE. A NOTE WILL SUFFICE.
 6. PROVIDE A GENERAL NOTE TO INDICATE NEC 110.16 ARC
 FLASH HAZARD WARNINGS- A NOTE WILL SUFFICE.
 7. PER NEC 110.24 A AND B. INDICATE ON PLANS REQUIRED
 FIELD MARKING OF THE AVAILABLE FAULT CURRENT DUE TO
 MODIFICATIONS.
 8. SEPARATE PERMITS REQUIRED FOR ALL LOW VOLTAGE
 SYSTEMS AND FIRE ALARM. PROVIDE A NOTE
 9. LABEL ALL RECEPTACLES WITHIN 6FT OF SINKS TO BE GFCI
 PROTECTED. SEE POWER SHEET. NEC 210.8B7
 10. PLEASE CLARIFY THE LOCATION OF THE ELECTRICAL PANEL
 BOARDS, PER NEC 110.26 CLEARANCE REQUIREMENTS TO BE
 MAINTAINED
 11. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL.
 PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By Mgonzale Date 2016-06-01 Time   Rev Time 1.00
Received By mgonzale Date 2016-06-01 Time   Sent To B
Notes
2016-06-01 08:50:51PROVISOS:
  
 1. CIVIL PLANS ARE UNDER REVIEW THRU ENGINEERING
 SERVICES, A SEPARATE PERMIT IS REQUIRED FOR FIRELINE
 ON-SITE.
 THIS SHALL INCLUDE SUBMISSION OF CIVIL PLANS SHEET C-1
 THRU C-9 TO OBTAIN A UG FIRELINE, FA OR FS PERMIT.
 INCLUDE ON PLANS THE FIRE HYDRANT PRESSURE TEST, TIME,
 LOCATION, WHO PERFORMED THE TEST AND RESULTS.
  
 2. CIVIL PLANS REQUIRE PALM BEACH COUNTY HEALTH
 DEPARTMENT REVIEW AND APPROVAL.
  
 3. A RIGHT-OF-WAY PERMIT THRU ENGINEERING WILL ALSO BE
 REQUIRED FOR CITY UTILITY WORK.
  
 4. CONTRACTOR SHALL USE THE CITY'S ENGINEERING STANDARD
 DETAILS AVAILABLE.
 HTTP://WPBFL.US/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FO
 RMS,-PERMITS-APPLICATIONS
 INCLUDING "PRESSURE PIPE" SERIES.
  
 5. A PRE-CONSTRUCTION MEETING WILL BE REQUIRED WITH THE
 CITY OF WPB ENGIEERING DEPARTMENT PRIOR TO ANY PUBLIC
 UTILITY EXCAVATIONS.
  
 6. SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
 (A) GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION
 90-205, AND EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR
 INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY
 OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER
 SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT
 COMPOSED ENTIRELY OF STORMWATER.
 (B) SITE OF INDUSTRIAL ACTIVITY. EXCEPT AS PROVIDED IN
 SECTION 90-205, ANY DIRECT OR INDIRECT DISCHARGE FROM A
 SITE OF INDUSTRIAL ACTIVITY TO THE SEPARATE STORM SEWER
 SYSTEM OWNED BY THE CITY WHICH DOES NOT COMPLY WITH, OR
 IS NOT PURSUANT TO, A VALID NPDES PERMIT IS PROHIBITED.
 (C) ILLICIT CONNECTIONS. NO PERSON MAY MAINTAIN, USE OR
 ESTABLISH ANY DIRECT OR INDIRECT CONNECTION TO THE
 STORMWATER SYSTEM THAT RESULTS IN ANY DISCHARGE IN
 VIOLATION OF THIS ARTICLE. THIS PROHIBITION IS
 RETROACTIVE AND APPLIES TO CONNECTIONS MADE IN THE
 PAST, REGARDLESS OF WHETHER MADE UNDER A PERMIT, OR
 OTHER AUTHORIZATION, OR WHETHER PERMISSIBLE UNDER LAWS
 OR PRACTICES APPLICABLE OR PREVAILING AT THE TIME THE
 CONNECTION WAS MADE. (CODE 1979, 32-18)
  
 7. NOTIFY - PERVIOUS AND IMPERVIOUS AREAS CALCULATIONS
 TO CITY OF WEST PALM BEACH ENGINEERING DEPARTMENT.
  
 8. ANY SIDEWALKS OR ADA PATHS NEAR AND ALONG THE
 PERIMETER OF THE PROPERTY SHALL CONFORM TO ADAAG
 STANDARDS FOR MINIMUM SLOPE AND WIDTH ACCESS.
  
 9. ANY EXISTING PUBLIC UTILITY CONNECTION NOT NEEDED
 FOR USE OF THE DEVELOPMENT SHALL BE CUT AND CAPPED AT
 THE MAIN. ANY DEVIATION OR HARDSHIP MAY BE EXPRESSED IN
 WRITING TO THE CITY OF WEST PALM BEACH PUBLIC UTILITY
 DIRECTOR IN WRITING. PLAN SHOWS WATER AND SEWER
 SERVICES THAT WILL NOT BE USED.
  
 10. CALL 811 BEFORE DIG, SHALL BE IN ALL UTILITY PLANS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-05-09 Cont ID  
Sent By Mgonzale Date 2016-05-09 Time   Rev Time 1.00
Received By mgonzale Date 2016-05-09 Time   Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-06-02 Cont ID  
Sent By wjolin Date 2016-06-02 Time 14:16 Rev Time 0.00
Received By wjolin Date 2016-06-02 Time 14:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-06-02 Cont ID  
Sent By wjolin Date 2016-06-01 Time 09:46 Rev Time 0.00
Received By wjolin Date 2016-06-01 Time 09:31 Sent To  
Notes
2016-06-01 09:46:222001 SOUTH DIXIE HIGHWAY
 PERMIT #16041215
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - FIRE SPRINKLER: ENGINEERED FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By wjolin Date 2016-05-05 Time 12:48 Rev Time 0.00
Received By wjolin Date 2016-05-05 Time 10:27 Sent To  
Notes
2016-05-05 11:41:592001 SOUTH DIXIE HIGHWAY
 PERMIT #16041215
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM
  
 GENERAL: PROVIDE PANIC HARDWARE FOR ALL EGRESS DOORS
 SUBJECT TO 50 OR MORE PERSONS. SEVERAL DOORS MISSING
 PANIC HARDWARE INCLUDING DOORS 114, 114A, 114B, 119,
 121, 200 AND 204.
  
 SHEET A050 & SHEET A101: THESE SHEETS ARE IN CONFLICT
 WITH EACHOTHER. ONE SHEET INDICATES CLASSROOM AND THE
 OTHER SHEET INDICATES MULTI-PURPOSE USE. MULTI-PURPOSE
 ROOM #114 IS SHOWN UTILIZING AN OCCUPANT LOAD FACTOR 20
 SQUARE FEET PER PERSON IN LIEU OF 15 SQUARE FEET PER
 PERSON.
  
 SHEET A101: 2ND GRADE CLASSROOM #107 EGRESS DOOR
 APPEARS TO OBSTRUCT THE CORRIDOR. PER SECTION 7.2.1.4.3
 DOOR LEAF ENCROACHMENT - DURING ITS SWING, ANY DOOR
 LEAF IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN
 ONE-HALF OF THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL
 PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH
 OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING,
 WHEN FULLY OPEN.
  
 SHEET A101: CORRIDOR EGRESS HAS THE POTENTIAL TO BE
 RESTRICTED WITH SECURITY DOOR/GRILL #100A. THIS IS NOT
 PERMITTED EVEN WITH FIRE ALARM INTEGRATION.
  
 SHEET A102: WHAT AGE GROUPS ARE INTENDED TO OCCUPY
 CLASSROOMS #202 AND #203.
  
 SHEET E101: CARD READER SHOWN ON EGRESS SIDE OF MAIN
 EXIT DOOR #100.
  
 SHEET E202: COULD NOT LOCATE EXTERIOR EMERGENCY
 LIGHTING FOR STAIR #2.
  
 GENERAL: IS ANY COMMERCIAL COOKING PROPSED AT THE
 SCHOOL?
  
 FIRE SPRINKLER: ENGINEERED FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-02 Cont ID  
Sent By jwitmer Date 2016-06-02 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2016-05-19 Time 14:38 Sent To  
Notes
2016-05-19 14:39:41C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-10 Cont ID  
Sent By cpuell Date 2016-05-10 Time 12:41 Rev Time 0.00
Received By cpuell Date 2016-04-27 Time 13:48 Sent To  
Notes
2016-04-28 13:48:40C32

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2016-06-06 Cont ID  
Sent By jwitmer Date 2016-06-06 Time 09:10 Rev Time 0.00
Received By jwitmer Date 2016-06-06 Time 09:10 Sent To  
Notes
2016-06-06 09:11:4506/06/16 PLANS BACK FROM P. B. C. IMPACT FEE OFFICE,
 PLANS STAMPED NO FEES DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-06-02 Cont ID  
Sent By jwitmer Date 2016-06-02 Time 11:38 Rev Time 0.00
Received By jwitmer Date 2016-06-02 Time 09:22 Sent To  
Notes
2016-06-02 11:38:29GOOD MORNING MR. SWOOPE,
  
 SINCE SPEAKING WITH YOU THIS MORNING I'VE SPOKEN WITH
 MS. LOUIE THE PLANNER FOR THIS PROJECT. THE CITY OF
 WEST PALM BEACH PLANNING & ZONING HAS APPROVED THIS
 SCHOOL FOR 125 STUDENTS. PALM BEACH COUNTY TRAFFIC
 CONCURRENCY APPROVAL IS FOR 150 STUDENTS, WE WILL BE
 SENDING THE CONTRACTOR WITH PLANS TO BE REVIEWED BY
 YOUR DEPARTMENT FOR ASSESSMENT OF IMPACT FEES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION15110652
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By jwitmer Date 2016-05-06 Time 14:08 Rev Time  
Received By jwitmer Date 2016-05-06 Time 07:30 Sent To  
Notes
2016-05-06 14:08:12IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-31 Cont ID  
Sent By ccole Date 2016-05-31 Time 08:44 Rev Time 0.00
Received By ccole Date 2016-05-25 Time 15:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-02 Cont ID  
Sent By ccole Date 2016-05-02 Time 15:54 Rev Time 0.00
Received By ccole Date 2016-05-02 Time 15:54 Sent To  
Notes
2016-05-02 16:24:351ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041215
 5/2/16
  
 1) THE IAQ PROCEDURE FOR OUTDOOR AIR INTAKE REQUIRES
 SUBMITTAL OF DESIGN DOCUMENTATION AS INDICATED IN
 SECTION 6.3.6 ASHRAE 62.1-2010:
 6.3.6 DOCUMENTATION. WHEN THE IAQ PROCEDURE IS USED,
 THE FOLLOWING INFORMATION SHALL BE INCLUDED IN THE
 DESIGN DOCUMENTATION: THE CONTAMINANTS OF CONCERN
 CONSIDERED IN THE DESIGN PROCESS, THE SOURCES AND
 EMISSION RATES OF THE CONTAMINANTS OF CONCERN, THE
 CONCENTRATION LIMITS AND EXPOSURE PERIODS AND THE
 REFERENCES FOR THESE LIMITS, AND THE ANALYTICAL
 APPROACH USED TO DETERMINE VENTILATION RATES AND AIR
 CLEANING REQUIREMENTS. THE CONTAMINANT MONITORING AND
 OCCUPANT AND/OR VISITOR EVALUATION PLANS SHALL ALSO BE
 INCLUDED IN THE DOCUMENTATION.
 PLEASE REVIEW ALL SUB-SECTIONS LISTED UNDER 6.3 AND
 SHOW COMPLIANCE.
  
 2) SHEET M-001: PLEASE UPDATE THE ASHRAE 62.1-2007
 REFERENCE SHOWN IN THE O/A TABLE TO THE CURRENT 2010
 EDITION.
  
 3) M-001: IT APPEARS THAT THE SYSTEM DATA IN THE AC
 SCHEDULE FOR AHU-11 IS LISTED UNDER AHU-12 AND VICE
 VERSA. PLEASE REFER TO THE SUBMITTED AC SUMMARY
 CALCULATIONS, AND THE AC LAYOUT PLAN ON SHEET M-101
 WHERE THE SYSTEMS APPEAR TO BE MISLABELED.
  
 4) M-001: EDUCATIONAL SCIENCE LABORATORIES REQUIRE
 EXHAUST SYSTEMS AT A RATE OF 50CFM'S PER SF. PLEASE
 CLARIFY WHAT TYPE OF ACTIVITIES WILL BE CONDUCTED IN
 THE SCIENCE ROOM, AND ALSO INDICATE IF THERE WILL BE AN
 ART CLASSROOM WHICH ALSO REQUIRES AND INDEPENDENT
 EXHAUST SYSTEM. REVISE THE PLANS TO SHOW COMPLIANCE.
  
 5) M-001: THE O/A SCHEDULE LISTS #122 AS "LARGE SPACE
 IN THE CENTER". PLEASE BE MORE SPECIFIC REGARDING THE
 USE OF THIS AREA. WHY WOULD THE O/A RATE FOR THIS AREA
 BE ANY LESS THAN THE PIAZZA?
  
 6) M-003: PLEASE CORRECT THE HVAC DESIGN TABLE
 INDICATING NO DUCT SMOKE DETECTORS.
  
 7) M-101: THE PLAN INDICATES 2360 CFM'S OF SUPPLY AIR
 FOR THE 4-TON SYSTEM WHICH IS CAPABLE OF PRODUCING
 MAXIMUM 1600 CFM'S ACCORDING TO THE AC SCHEDULE.
  
 8) M-101: THE EXHAUST IN ROOM 112A NEEDS TO BE
 INCREASED TO ACCOMODATE THE LOCKERS OR DRESSING AREA-
 TABLE 6-4 ASHRAE 62.1-10.
  
 9) M-102: PLEASE CLARIFY THE USE OF THE MOTORIZED
 DAMPER IN THE COMMON WALL BETWEEN CLASSROOMS 202 & 203.
  
 10) A050: REFER TO SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION. THE BUILDING CODE DATA INDICATES THE
 PROJECT IS A "CHANGE OF OCCUPANCY". PLEASE PROVIDE
 ENERGY CALCULATIONS.
  
 11) PROVIDE AC CALCULATIONS FOR THE WAC-1 SYSTEM.
  
 12) REFER TO SECTIONS C403.2.7.2 AND C403.2.7.3 FBC
 ENERGY CONSERVATION AND REPLACE THE WOOD DOORS ON THE
 MECHANICAL CLOSETS WITH NON-COMBUSTIBLE DOORS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-25 Cont ID  
Sent By gjohnson Date 2016-05-25 Time 17:26 Rev Time 0.00
Received By gjohnson Date 2016-05-25 Time 16:35 Sent To  
Notes
2016-05-25 17:26:43 
 PLUMBING PROVISO
 4 OF THE 9 DRINKING FOUNTAINS SHALL COMPLY WITH FBC
 ACC. SEC. 602.7 DRINKING FOUNTAINS FOR STANDING
 PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 TO MEET THE REQUIREMENTS OF FBC ACC. SEC.
 211.3 MORE THAN MINIMUM NUMBER.
 WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING
 FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.7.
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-03 Cont ID  
Sent By gjohnson Date 2016-05-03 Time 12:59 Rev Time 0.00
Received By gjohnson Date 2016-05-03 Time 08:50 Sent To  
Notes
2016-05-03 13:57:571ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1. A TOTAL OF 6 DRINKING FOUNTAINS ARE REQUIRED PER FBC
 PL TABLE 403.1. THEY SHALL COMPLY WITH FBC ACC. SEC.
 211.3 MORE THAN MINIMUM NUMBER.
 WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING
 FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.7.
  
 2. SHT. A050 THE BUILDING CODE DATA HAS A NOTE THAT
 STATES GRADES 9 THRU 12 MY UNDERSTANDING WAS THIS
 SCHOOL WAS TO BE PREK THRU 4TH GRADE PLEASE CLARIFY PER
 WPB AMEND. TO FBC SEC. 107.2.1
  
 3. WHAT GRADES ARE CLASSROOM S 202 AND 203. PER WPB
 AMEND. TO FBC 107.2.1
  
 4. SEPARATE FACILITIES ARE REQUIRED FOR MALE AND FEMALE
 4TH GRADE AND ABOVE PER FBC PL 403.2 AND FBC 468.3.5
  
 5. SHT. A400 NOTE # 1 PROVIDE MIN AND MAXIMUM FOR ALL
 DIMENSIONS WHEN PROVIDED IN CODE. PER WPB AMEND. TO FBC
 107.2.1
  
 6. GRAB BARS TO BE MEASURED TO THE TOP OF THE GRIPING
 SURFACE . PER FBC ACC SEC. 609.4
  
 7. SHT. P-201 THE RISER DIAGRAM IS SHOWING WALL MOUNTED
 WATER CLOSETS BUT THE PLUMBING SCHEDULE ON SHT A-400
 HAS FLOOR MOUNTED PLEASE CLARIFY PER WPB AMEND. TO FBC
 107.2.1
  
 8. ALL LAVATORY'S AND SINKS SHALL HAVE TEMPERED WATER.
 PER FBC PL SEC. 607.1 AND SHALL COMPLY WITH FBC PL SEC.
 416.5
  
 9. HOT WATER SYSTEM SHALL COMPLY WITH FBC PL SEC. 607.2
 HOT OR TEMPERED WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
  
 10. A BACK FLO IS REQUIRED FOR THE 1/2IN. LINE TO
 PLANTER AREA PER FBC PL SEC. 608
  
 11. THERMAL EXPANSION CONTROL IS REQUIRED FOR WATER
 HEATER PER FBC PL SEC. 607.3
  
 12. PROVIDE MANUFACTURE SPECS FOR SUMP PUMP WITH OIL
 MINDER, WATER HEATERS . PER WPB AMEND. TO FBC 107.2.1
  
 13. PROVIDE GREASE CALCULATIONS FROM SCHIER YOU CAN
 CONTACT LEE SCHNEEWEISS FOR THOSE AT PH# 800-538-4792
 PER WPB AMEND. TO FBC 107.2.1
  
 14. SAMPLING PORT FROM GREASE SHALL BE MIN OF 6IN. AND
 SHALL NOT BE MADE WITH A SANITARY CROSS PER WPB
 UTILITIES.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-06-02 Cont ID  
Sent By llouie Date 2016-06-02 Time   Rev Time 0.00
Received By llouie Date 2016-06-02 Time   Sent To  
Notes
2016-06-02 15:51:18ZONING APPROVED WITH PROVISOS:
  
 1.) SUBJECT TO THE CONDITIONS OUTLINED IN THE SITE PLAN
 APPROVAL LETTER, DATED 6/2/16, FOR CASE NO. ISPR 16-02.
  
 2.) SEPARATE PERMIT REQUIRED FOR LANDSCAPING AND
 SIGNAGE.
  
 CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2016-05-24 Cont ID  
Sent By llouie Date 2016-05-24 Time   Rev Time 0.00
Received By llouie Date 2016-05-24 Time   Sent To  
Notes
2016-05-24 17:14:06** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) 5/9/16 REPEAT COMMENT: ALL ROOF TOP MECHANICAL
 EQUIPMENT SHALL BE SCREEN FROM VIEW WITH PARAPETS.
 PLEASE ILLUSTRATE/NOTATE FOR COMPLIANCE.
  
 2.) SITE PLAN (ISPR 16-01) IS PENDING REVIEW BY THE
 PLANS AND PLATS REVIEW COMMITTEE (PPRC). PLEASE NOTE
 THAT ZONING WILL NOT APPROVE THE BUILDING PERMIT UNTIL
 THE SITE PLAN IS APPROVED.
  
 3.) PLEASE NOTE THAT ANY CHANGES TO ISPR 16-01 OR ON
 THE RESUBMITTED PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU
 HAVE QUESTIONS.
  
 NOTE:
 * SEPARATE PERMIT AND REVIEW REQUIRED FOR EXTERIOR
 IMPROVEMENTS, LANDSCAPING, SIGNAGE, EXTERIOR LIGHTING,
 ETC.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-05-09 Cont ID  
Sent By llouie Date 2016-05-09 Time 15:05 Rev Time  
Received By llouie Date 2016-05-09 Time   Sent To  
Notes
2016-05-09 15:07:18** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ALL ROOF TOP MECHANICAL EQUIPMENT SHALL BE SCREEN
 FROM VIEW WITH PARAPETS. PLEASE ILLUSTRATE/NOTATE FOR
 COMPLIANCE.
  
 2.) PLEASE PROVIDE SCALE AND DIMENSIONS TO THE
 ARCHITECTURAL ELEVATIONS.
  
 3.) EXTERIOR CHANGES DETECTED; SITE PLAN SHOWING
 BUILDING SETBACK DISTANCE FROM PROPERTY LINES REQUIRED.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
 NOTE:
  
 * SITE PLAN (ISPR 16-01) PENDING REVIEW BY THE PLANS
 AND PLATS REVIEW COMMITTEE (PPRC).
  
 * SEPARATE PERMIT AND REVIEW REQUIRED FOR EXTERIOR
 IMPROVEMENTS, LANDSCAPING, SIGNAGE, EXTERIOR LIGHTING,
 ETC.
  
  
  