Plan Review Details - Permit 16041147
Plan Review Stops For Permit 16041147
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-12-30 Cont ID  
Sent By jwitmer Date 2016-12-30 Time   Rev Time 0.00
Received By jwitmer Date 2016-12-30 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-11-17 Cont ID  
Sent By shill Date 2016-11-17 Time 17:01 Rev Time 0.00
Received By shill Date 2016-11-17 Time 17:01 Sent To  
Notes
2016-11-17 17:05:11BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041147
 ADD: 914 3RD ST.
 CONT: TREND WEST INC.
 TEL: 561-358-8817
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. OCT. 24 /2016
 ACTION: DENIED
  
 1) SHEET S1:
  
 1A)4TH REQUEST. THIS SHEET AND THE ELECTRICAL SHEETS
 SHOW 5 DWELLING UNITS, BUT THE DESIGNER OF RECORD MAKE
 NUMEROUS MENTION TO THE2014 RESIDENTIAL CODE. PLEASE
 NOTE THE FBC- RESIDENTIAL CODE IS FOR 1 & 2 FAMILY
 ONLY!!!!! PLEASE NOTE THIS 5 UNIT RESIDENTIAL STRUCTURE
 IS COVERED AND TO BE REVIEWED UNDER THE 2014
 FBC-BUILDING CODE- BUILDING CODE. PLEASE CORRECT THE
 CODE REFERENCES TO THE RESIDENTIAL CODE AND TABLES IN
 THE RESIDENTIAL CODE.
 2) 2014 FLORIDA BUILDING CODE- BUILDING, PLEASE PROVIDE
 THE WIND DESIGN CRITERIA UNDER 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
 WIND DESIGN INCLUDES REFERENCES TO THE RESIDENTIAL
 CODE. SEE OTHER COMMENTS. REVISE. PLANS MAY BE SENT TO
 FBPE. HAVE ENGINEER ACKNOWLEDGE IN THE FORM OF A
 RESPONSE LETTER.
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-10-24 Cont ID  
Sent By jwitmer Date 2016-10-24 Time 17:28 Rev Time 0.00
Received By jwitmer Date 2016-10-24 Time 16:40 Sent To  
Notes
2016-10-24 17:16:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041147
 ADD: 914 3RD ST.
 CONT: TREND WEST INC.
 TEL: 561-358-8817
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. OCT. 24 /2016
 ACTION: DENIED
  
 1) SHEET S1:
  
 1A)3RD REQUEST. THIS SHEET AND THE ELECTRICAL SHEETS
 SHOW 5 DWELLING UNITS, BUT THE DESIGNER OF RECORD MAKE
 NUMEROUS MENTION TO THE2014 RESIDENTIAL CODE. PLEASE
 NOTE THE FBC- RESIDENTIAL CODE IS FOR 1 & 2 FAMILY
 ONLY!!!!! PLEASE NOTE THIS 5 UNIT RESIDENTIAL STRUCTURE
 IS COVERED AND TO BE REVIEWED UNDER THE 2014
 FBC-BUILDING CODE- BUILDING CODE. PLEASE CORRECT THE
 CODE REFERENCES TO THE RESIDENTIAL CODE AND TABLES IN
 THE RESIDENTIAL CODE.
  
 2) 2014 FLORIDA BUILDING CODE- BUILDING, PLEASE PROVIDE
 THE WIND DESIGN CRITERIA UNDER 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) THE SUBMITTED PRODUCT APPROVAL (FL 12769 JELD WEN)
 WITHOUT SURFACE BOLTS IS GOOD FOR -50 PSF, THE DESIGNER
 OF RECORD INDICATES THE NEGATIVE PRESSURES FOR THIS
 OPENING ARE -52.7 FOR DOORS LOCATED IN A INTERIOR ZONE
 # 4. THE DESIGNER OF RECORD CAN BE MORE RESTRICTIVE
 THAN THE MINIMUM CODE. PRESSURES GIVEN ARE AT 132 VASD.
  
 4) THE DESIGNER OF RECORD HAS NOT APPLIED THEIR SHOP
 DRAWING STAMP OF APPROVAL ON THE PRODUCT APPROVAL
 SUBMITTED. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-21 Cont ID  
Sent By jwitmer Date 2016-07-21 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2016-07-21 Time 09:44 Sent To  
Notes
2016-07-21 13:50:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041147
 ADD: 914 3RD ST.
 CONT: TREND WEST INC.
 TEL: 561-358-8817
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JULY 21 /16
 ACTION: DENIED
  
 1) SHEET S1:
  
 1A) 2ND REQUEST. THIS SHEET AND THE ELECTRICAL SHEETS
 SHOW 5 DWELLING UNITS, BUT THE DESIGNER OF RECORD MAKE
 NUMEROUS MENTION TO THE2014 RESIDENTIAL CODE. PLEASE
 NOTE THE FBC- RESIDENTIAL CODE IS FOR 1 & 2 FAMILY
 ONLY!!!!! PLEASE NOTE THIS 5 UNIT RESIDENTIAL STRUCTURE
 IS COVERED AND TO BE REVIEWED UNDER THE 2014
 FBC-BUILDING CODE- BUILDING CODE. PLEASE CORRECT THE
 CODE REFERENCES TO THE RESIDENTIAL CODE.
  
 1B) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN MISSING FROM THE 2ND REVIEW.
  
 107.3.5..11 COMMERCIAL BUILDINGS:
 FLOOR PLAN
  
 PLEASE PROVIDE UNDER THE R2 OCCUPANCY WHICH OF THE USES
 BELOW:
 APARTMENTS
 BOARDING HOUSES (NONTRANSIENT) WITH MORE THAN 16
 OCCUPANTS
 CONGREGATE LIVING FACILITIES (NONTRANSIENT) WITH MORE
 THAN 16 OCCUPANTS
 HOTELS (NONTRANSIENT)
  
 1C) THERE IS A DISCREPANCY IN THE SCOPE OF WORK BETWEEN
 THE PERMIT APPLICATION AND THE SHEET S1. SHEET S1 DOES
 NOT LIST THE REPLACEMENT OF ANY WINDOWS, WHERE AS THE
 PERMIT APPLICATION DOES INDICATE NEW WINDOWS. NO
 PRODUCT APPROVALS FOR WINDOWS HAVE BEEN SUBMITTED TO
 DATE.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. / 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 1D) UNDER COMMENT 1B, THE REQUESTED FLOOR PLAN IS FOR
 THE REPLACEMENT OF WINDOWS, SHOW SIZES OF WINDOWS FOR
 ALL ROOMS, USE OF ROOMS, THE EXISITNG WINDOW AND THE
 TYPE OF PROPOSED WINDOW. PLEASE SHOW COMPLIANCE WITH:
 2014 FBC-B:
  
 1D)(1) 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE
 OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7
 SQUARE FEET (0.53 M2).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADEFLOOR
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5 SQUARE
 FEET (0.46 M2).
  
 1D)(2) 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 1D)(3) 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-13 Cont ID  
Sent By jwitmer Date 2016-05-13 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2016-05-13 Time 06:48 Sent To  
Notes
2016-05-13 07:33:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041147
 ADD: 914 3RD ST.
 CONT: TREND WEST INC.
 TEL: 561-358-8817
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 13/16
 ACTION: DENIED
  
 1) SHEET S1:
  
 1A) THIS SHEET AND THE ELECTRICAL SHEETS SHOW 5
 DWELLING UNITS, BUT THE DESIGNER OF RECORD MAKE
 NUMEROUS MENTION TO THE SINGLE FAMILY CODE. PLEASE NOTE
 THIS 5 UNIT RESIDENTIAL STRUCTURE IS COVERED AND TO BE
 REVIEWED UNDER THE 2014 FBC-BUILDING CODE. PLEASE
 CORRECT THE CODE REFERENCES TO THE RESIDENTIAL CODE.
  
 1B) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN
 107.3.5..11 COMMERCIAL BUILDINGS:
 FLOOR PLAN
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED. R1, R2 OR R4 USAGE:
 R2:
 BOARDING HOUSES (NONTRANSIENT) WITH MORE THAN 16
 OCCUPANTS
 CONGREGATE LIVING FACILITIES (NONTRANSIENT) WITH MORE
 THAN 16 OCCUPANTS
 HOTELS (NONTRANSIENT)
 R4:
 ALCOHOL AND DRUG CENTERS
 ASSISTED LIVING FACILITIES
 CONGREGATE CARE FACILITIES
 CONVALESCENT FACILITIES
 GROUP HOMES
 HALFWAY HOUSES
 RESIDENTIAL BOARD AND CUSTODIAL CARE FACILITIES
 SOCIAL REHABILITATION FACILITIES
 GROUP R-4 OCCUPANCIES SHALL MEET THE REQUIREMENTS FOR
 CONSTRUCTION AS DEFINED FOR GROUP R-3, EXCEPT AS
 OTHERWISE PROVIDED FOR IN THIS CODE.,
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 DEPENDING ON THE USAGE:
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-02-15 Cont ID  
Sent By vperez Date 2017-02-15 Time 09:49 Rev Time 0.00
Received By vperez Date 2017-02-15 Time 09:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-10-03 Cont ID  
Sent By mvaldes Date 2016-10-03 Time 16:04 Rev Time 0.00
Received By mvaldes Date 2016-10-03 Time 15:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-18 Cont ID  
Sent By mvaldes Date 2016-07-18 Time 15:14 Rev Time 0.00
Received By mvaldes Date 2016-07-18 Time 13:10 Sent To  
Notes
2016-07-18 15:17:44JOB PERMIT NUMBER: 729 PENN ST
 JOB ADDRESS: 471 SPENCER DRIVE
 WEST PALM BEACH FLORIDA
 DATE: JULY 18 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - SHOW LOCATION OF EXISTING SUB PANEL "A" ON THE FLOOR
 PLAN TO VERIFY WORK CLEARANCES, LOAD CALCULATIONS AND
 PANEL SCHEDULE REFLECT A RANGE BUT HOWEVER ON THE
 KITCHEN LAYOUT THERE IS A COOKTOP AND AN OVEN ? MODIFY
 ACCORDINGLY. FBC 107 MINIMUM PLAN REVIEW CRITERIA.
 - KITCHEN ISLAND RECEPTACLE OUTLETS ON BOTH ENDS SHALL
 BE GFCI PROTECTED AND INSTALLED NO MORE THAN 12'' BELOW
 THE COUNTERTOP. FBC R SECTIONS E3902.6 & E3901.4.2
 - A/C DISCONNECT SEEMS TO BE BEHIND THE COMPRESSOR,
 PLEASE REFLECT PROPER WORK CLEARANCE. OUTSIDE GFCI
 RECEPTACLE SHALL ?WR? IN ADDITION OF BEING INSTALLED IN
 A ?WP? ENCLOSURE. FBC R SECTIONS E4002.9 & E3405.1
 - NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE
 DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910
 MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS.
 RELOCATE THE UNITS ACCORDINGLY.
 - ONE AND TWO FAMILY DWELLINGS SHALL HAVE OUTDOOR
 RECEPTACLES IN BOTH BACK & FRONT OF THE HOUSE. FBC R
 E3901.7
 - FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS.
 - PROVIDE AN ATTIC ENTRANCE LIGHT THAT IS SWITCHED AS
 REQUIRED AND ILLUMINATION SHALL BE SUFFICIENT FOR
 SERVICING THE AIR HANDLING UNIT. FBC R SECTION E3903.4
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER'S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By mvaldes Date 2016-04-28 Time 19:09 Rev Time 0.00
Received By mvaldes Date 2016-04-28 Time 19:09 Sent To  
Notes
2016-04-28 19:35:54JOB PERMIT NUMBER: 16041147
 JOB ADDRESS: 914 3RD ST 1
 WEST PALM BEACH FLORIDA
 DATE: APRIL 28 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - ELECTRICAL SERVICE RISER SHOWS 2? CONDUIT WITH 2 SETS
 OF 3/0 AWG IN PARALLEL , HOWEVER TABLE ANNEX C CONDUIT
 FILL STATES ONLY 5 WIRES FIT ASSUMING EITHER IMC OR RMC
 IS BEING INSTALLED. CLARIFY AND CORRECT ACCORDINGLY ?
 - PROVIDE INTERSYSTEM BONDING TERMINAL STRIP ON THE
 GROUNDING DETAIL IN THE RISER DIAGRAM. NEC 250.94
 - ELECTRICAL NOTE OF LIGHTING NEEDING TO BE 50 % HIGH
 EFFICIENT IS INCORRECT FBC-E R 404.1 A MINIMUM 75 %
 LAMPS SHALL BE HIGH EFFICACY , FURTHER MORE CHANGE THE
 CODE REFERENCE OF NEC 2008 TO THE APPLICABLE 2011 IN
 TAMPER RESISTANT RECEPTACLE NOTE.
 - SERVICE EQUIPMENT TO INCLUDE ALL PERMANENT PLAQUES OF
 NEC 225.37 , INTERIOR PANELBOARDS TO HAVE
 IDENTIFICATION OF SOURCE OF SUPPLY IN ACCORDANCE WITH
 NEC 408.4 (B)
 - FOR FINAL INSPECTION ARC-FLASH HAZARD WARNING LABELS
 AND AVAILABLE FAULT CURRENT MARKINGS MUST BE ON
 ELECTRICAL APPARATUS SUITABLE TO WITHSTAND ENVIRONMENT.
 - ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 AND FBC SECTION 714. ANY FIRE RATED
 STRUCTURE THAT IS COMPROMISED SHALL BE RETURNED TO ITS
 ORIGINAL FIRE-RATING WITH APPROVED FIRE SEALING
 MATERIAL.
 - PROVIDE SPECS ON A/C WALL UNITS TO VERIFY IF THEY
 PROVIDE HEAT PER FBC-R 303.9 EVERY DWELLING UNIT
 HABITABLE ROOM SHALL BE CAPABLE OF MAINTAINING 68
 DEGREES FAHRENHEIT AT 3 FT ABOVE FLOOR AND 2 FT FROM
 EXTERIOR WALLS.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2017-02-15 Cont ID  
Sent By ccole Date 2017-02-15 Time 15:09 Rev Time 0.00
Received By ccole Date 2017-02-14 Time 09:37 Sent To  
Notes
2017-02-15 09:38:09RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-01-24 Cont ID  
Sent By ccole Date 2017-01-24 Time 15:28 Rev Time 0.00
Received By ccole Date 2017-01-17 Time 15:16 Sent To  
Notes
2017-01-18 15:16:59RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 16:25 Rev Time 0.00
Received By gjohnson Date 2016-12-22 Time 16:01 Sent To  
Notes
2016-12-22 16:01:52B18

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-11-30 Cont ID  
Sent By cpuell Date 2016-11-30 Time 14:08 Rev Time 0.00
Received By cpuell Date 2016-11-04 Time 16:21 Sent To  
Notes
2016-11-04 16:21:57B18

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-24 Cont ID  
Sent By jwitmer Date 2016-10-24 Time 17:28 Rev Time 0.00
Received By jwitmer Date 2016-09-29 Time 11:25 Sent To  
Notes
2016-09-30 11:25:51B11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-30 Cont ID  
Sent By tklarge Date 2016-07-30 Time 02:00 Rev Time 0.00
Received By tklarge Date 2016-07-01 Time 12:45 Sent To  
Notes
2016-07-01 12:45:52B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-16 Cont ID  
Sent By ccole Date 2016-05-16 Time 13:50 Rev Time 0.00
Received By ccole Date 2016-04-26 Time 15:00 Sent To  
Notes
2016-04-26 15:00:21B11

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2017-02-15 Cont ID  
Sent By ccole Date 2017-02-15 Time 15:09 Rev Time 0.00
Received By ccole Date 2017-02-15 Time 15:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2017-01-24 Cont ID  
Sent By ccole Date 2017-01-24 Time 15:28 Rev Time 0.00
Received By ccole Date 2017-01-24 Time 15:28 Sent To  
Notes
2017-01-24 15:36:486TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16041147
 1/24/17
  
 1) THE ELECTRICAL PLANS AND THE REVISED AC AND ENERGY
 CALCULATIONS DO NOT MATCH. THE PLANS INDICATE 5 WALL
 SYSTEMS LOCATED IN THE LIVING ROOMS OF UNITS 1-5. THE
 REVISED CALCULATIONS ARE FOR 15 WALL SYSTEMS TO BE
 LOCATED APPARENTLY IN THE LIVING ROOMS AND BEDROOMS OF
 THE UNITS. PLEASE NOTE THAT THE PANEL SCHEDULES ARE
 INDICATING ONLY FIVE WALL SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2016-12-29 Cont ID  
Sent By ccole Date 2016-12-29 Time 08:59 Rev Time 0.00
Received By ccole Date 2016-12-29 Time 08:59 Sent To  
Notes
2016-12-29 09:54:445TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16041147
 12/28/16
  
 1) THE REVISED AC CALCULATIONS BY KO ENERGY DESIGN
 APPEAR TO BE FOR ONE SINGLE 2-BEDROOM RESIDENCE, AND
 INCLUDE TOTAL COOLING AND HEATING LOADS, AND "DUCT
 SIZING". THE PLANS BY BUCHANAN P.E. CONSULTING INC. ARE
 SHOWING 5 "DUCTLESS" THROUGH THE WALL AC UNITS SERVING
 ONLY THE LIVING ROOMS AND KITCHENS AND NO BEDROOMS OF 5
 DIFFERENT APARTMENTS. AS NOTED IN PREVIOUS REVIEWS,
 THESE CONFLICTS NEED TO BE CORRECTED. PLEASE NOTE
 MINIMUM HEATING IS REQUIRED FOR ALL OCCUPIED SPACES PER
 SECTION 309.1.
  
 2) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN TO
 MATCH THE SYSTEM DATA IN THE CALCULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-11-10 Cont ID  
Sent By ccole Date 2016-11-10 Time 10:30 Rev Time 0.00
Received By ccole Date 2016-11-10 Time 10:30 Sent To  
Notes
2016-11-10 11:12:264TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16041147
 11/10/16
  
 1) AS PREVIOUSLY REQUESTED, THE OWNER'S SIGNATURE IS
 REQUIRED TO BE ON THE ENERGY FORMS, AND THE MAKE AND
 MODEL NUMBERS OF THE AC SYSTEMS SHALL BE ON THE PLANS.
  
 2) THE AC CALCULATIONS DO NOT APPEAR TO BE FOR THE
 PROPOSED PROJECT BECAUSE THEY ARE LISTING THE PROJECT
 TITLE AS "MONTOYA RESIDENCE" WITH A STUART ADDRESS, AND
 THE CALCULATIONS ARE FOR ONLY 3 SYSTEMS. THE PROJECT
 UNDER REVIEW HAS 5 SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-10-11 Cont ID  
Sent By ccole Date 2016-10-11 Time 10:27 Rev Time 0.00
Received By ccole Date 2016-10-11 Time 10:27 Sent To  
Notes
2016-10-11 10:40:031ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16041147
 10/11/16
  
 1) THE ENERGY CONSERVATION FORM R402-2014 MUST BE
 SIGNED BY THE PERSON WHO PREPARED THE DOCUMENT AND BY
 THE OWNER/AGENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-20 Cont ID  
Sent By ccole Date 2016-07-20 Time 10:43 Rev Time 0.00
Received By ccole Date 2016-07-20 Time 10:22 Sent To  
Notes
2016-07-20 11:03:452ND REVIEW MECHANICAL
 PERMIT #16041147
 7/20/16
  
 1) THE COMMENTS FROM THE 1ST REVIEW STILL EXIST. I HAVE
 REPRINTED THEM BELOW. PLEASE NOTE THAT MINIMUM HEATING
 IS REQUIRED FOR ALL OCCUPIABLE SPACES PER SECTION
 309.1. THE PLANS DO NOT INDICATE COMPLIANCE.
  
 1ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041147
 4/29/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEMS IN THE LIVING ROOMS- REFER TO SECTION
 C403.2.1 FBC ENERGY CONSERVATION.
 2) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE NEW
 AC SYSTEMS, INSTALLATION DETAILS, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-16 Cont ID  
Sent By ccole Date 2016-04-29 Time 13:50 Rev Time 0.00
Received By ccole Date 2016-04-29 Time 10:46 Sent To  
Notes
2016-04-29 10:48:391ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041147
 4/29/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEMS IN THE LIVING ROOMS- REFER TO SECTION
 C403.2.1 FBC ENERGY CONSERVATION.
 2) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE NEW
 AC SYSTEMS, INSTALLATION DETAILS, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 16:25 Rev Time 0.00
Received By gjohnson Date 2017-01-12 Time 16:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2016-11-28 Cont ID  
Sent By gjohnson Date 2016-11-28 Time 12:15 Rev Time 0.00
Received By gjohnson Date 2016-11-28 Time 12:08 Sent To  
Notes
2016-11-28 12:18:531ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SCOPE OF WORK FOR PLUMBING. PER WPB AMEND TO
 FBC 107.2.1
  
 2. ADDRESS COMMENTS FROM MECHANICAL AND BUILDING. PER
 WPB AMEND TO FBC 107.2.1

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-10-24 Cont ID  
Sent By gjohnson Date 2016-10-24 Time 14:01 Rev Time 0.00
Received By gjohnson Date 2016-10-24 Time 13:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-30 Cont ID  
Sent By tklarge Date 2016-07-30 Time 02:00 Rev Time 0.00
Received By tklarge Date 2016-07-30 Time 01:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-16 Cont ID  
Sent By gjohnson Date 2016-05-16 Time 13:36 Rev Time 0.00
Received By gjohnson Date 2016-05-16 Time 13:36 Sent To  
Notes
2016-05-16 13:43:481ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. E-1 NOTE ON THE PLAN INDICATES WATER HEATERS AS
 NEW PLEASE CLARIFY PROVIDE A DETAILED SCOPE OF ANY
 PLUMBING WORK BEING DONE. PER WPB AMEND. TO FBC
 SEC.107.2.1
  
 DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A
 COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME,
 THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF
 PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  

Review Stop Z ZONING
Rev No 4 Status P Date 2016-11-29 Cont ID  
Sent By   Date 2016-11-29 Time   Rev Time 0.00
Received By kmartin Date 2016-11-29 Time 16:53 Sent To  
Notes
2016-11-28 14:29:53ROUTED TO KEVIN MARTIN

Review Stop Z ZONING
Rev No 3 Status P Date 2016-10-20 Cont ID  
Sent By   Date 2016-10-20 Time   Rev Time 0.00
Received By kmartin Date 2016-10-20 Time 16:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2016-07-29 Time   Rev Time 0.00
Received By kmartin Date 2016-07-29 Time 08:30 Sent To  
Notes
2016-07-29 08:32:551. AC SCREENING DETAILS NEEDED.
  
 FOR MORE INFORMATION PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT (561) 822-1426 OR [email protected].

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By kmartin Date 2016-05-16 Time   Rev Time 0.00
Received By kmartin Date 2016-05-16 Time 08:25 Sent To  
Notes
***NONE***