Plan Review Details - Permit 16041109
Plan Review Stops For Permit 16041109
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-11 Cont ID  
Sent By ccole Date 2016-05-05 Time 15:15 Rev Time 0.00
Received By cthroop Date 2016-05-05 Time 08:56 Sent To E
Notes
2016-05-05 15:17:361ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-7918
 [email protected]
  
 1. PROVIDE CONNECTION DETAIL AND FASTENER SCHEDULE FOR
 NEW PARTITION TOP PLATE AND BOTTOM PLATE TO STRUCTURE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-25 Cont ID  
Sent By mvaldes Date 2016-05-25 Time 12:06 Rev Time 0.00
Received By mvaldes Date 2016-05-25 Time 11:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-09 Cont ID  
Sent By cthroop Date 2016-05-11 Time 08:44 Rev Time 0.00
Received By mvaldes Date 2016-05-09 Time 08:48 Sent To  
Notes
2016-05-09 09:07:49REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - LOW VOLTAGE AND FIRE ALARM SHALL BE UNDER A SEPERATE
 PERMIT WITH SEPERATE DRAWINGS.
  
 - SHEET E02.02, NO EMERGENCY LIGHTING SHOWN ? FBC
 1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED. THE MEANS
 OF EGRESS, INCLUDING THE EXIT DISCHARGE, SHALL BE
 ILLUMINATED AT ALL TIMES THE BUILDING SPACE SERVED BY
 THE MEANS OF EGRESS ARE OCCUPIED.FBC-B 1006.2.
 EMERGENCY LIGHTING IS REQUIRED
 EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF
 SAME LOCAL AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY
 THE AREA, EM LIGHTS MAY BE ON OWN CIRCUIT. NEC 700.12
 (F) (4)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-20 Cont ID  
Sent By pleduc Date 2016-05-20 Time   Rev Time 0.00
Received By pleduc Date 2016-05-20 Time 14:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-28 Cont ID  
Sent By scaldero Date 2016-04-28 Time 11:55 Rev Time 0.00
Received By scaldero Date 2016-04-28 Time 11:52 Sent To  
Notes
2016-04-28 11:54:56PERMIT #16041109
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-25 Cont ID  
Sent By mvaldes Date 2016-05-25 Time 12:06 Rev Time 0.00
Received By mvaldes Date 2016-05-18 Time 15:08 Sent To  
Notes
2016-05-19 15:08:51B34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-09 Cont ID  
Sent By mvaldes Date 2016-05-09 Time 09:26 Rev Time 0.00
Received By mvaldes Date 2016-04-26 Time 08:38 Sent To  
Notes
2016-04-27 08:38:58B34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-05-25 Cont ID  
Sent By cthroop Date 2016-05-25 Time 15:00 Rev Time 0.00
Received By cthroop Date 2016-05-25 Time 15:00 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By cthroop Date 2016-05-05 Time 15:13 Rev Time 0.00
Received By cthroop Date 2016-05-05 Time 14:03 Sent To  
Notes
2016-05-05 15:14:561ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-7918
 [email protected]
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-24 Cont ID  
Sent By ccole Date 2016-05-24 Time 10:05 Rev Time 0.00
Received By ccole Date 2016-05-24 Time 10:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-03 Cont ID  
Sent By ccole Date 2016-04-29 Time 06:41 Rev Time 0.00
Received By ccole Date 2016-04-29 Time 07:07 Sent To  
Notes
2016-05-03 06:42:241ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041109
 4/29/16
  
 1) PROVIDE SHEET M2.2 AS NOTED IN NOTES #4 & 7- SHEET
 M01.02.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  