Plan Review Stops For Permit 16041109 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2016-05-11 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-05-05 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-05-05 |
Time |
08:56 |
Sent To |
E |
|
Notes |
2016-05-05 15:17:36 | 1ST REVIEW: FBC 2014 5TH ED | | CHRISTOPHER S. THROOP, C.B.O. | | BLDG. PLANS EXAMINER ? PX3169 | | (561) 805-7918 | | [email protected] | | | | 1. PROVIDE CONNECTION DETAIL AND FASTENER SCHEDULE FOR | | NEW PARTITION TOP PLATE AND BOTTOM PLATE TO STRUCTURE. | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | SECTION 107.3.5). | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-05-25 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-05-25 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-05-25 |
Time |
11:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-05-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-05-11 |
Time |
08:44 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-05-09 |
Time |
08:48 |
Sent To |
|
|
Notes |
2016-05-09 09:07:49 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - LOW VOLTAGE AND FIRE ALARM SHALL BE UNDER A SEPERATE | | PERMIT WITH SEPERATE DRAWINGS. | | | | - SHEET E02.02, NO EMERGENCY LIGHTING SHOWN ? FBC | | 1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED. THE MEANS | | OF EGRESS, INCLUDING THE EXIT DISCHARGE, SHALL BE | | ILLUMINATED AT ALL TIMES THE BUILDING SPACE SERVED BY | | THE MEANS OF EGRESS ARE OCCUPIED.FBC-B 1006.2. | | EMERGENCY LIGHTING IS REQUIRED | | EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF | | SAME LOCAL AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY | | THE AREA, EM LIGHTS MAY BE ON OWN CIRCUIT. NEC 700.12 | | (F) (4) |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2016-05-20 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-05-20 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-05-20 |
Time |
14:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2016-04-28 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2016-04-28 |
Time |
11:55 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2016-04-28 |
Time |
11:52 |
Sent To |
|
|
Notes |
2016-04-28 11:54:56 | PERMIT #16041109 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 644-7326 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-05-25 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-05-25 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-05-18 |
Time |
15:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-05-09 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-05-09 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-04-26 |
Time |
08:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
N |
Date |
2016-05-25 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-05-25 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-05-25 |
Time |
15:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2016-05-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-05-05 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-05-05 |
Time |
14:03 |
Sent To |
|
|
Notes |
2016-05-05 15:14:56 | 1ST REVIEW: FBC 2014 5TH ED | | CHRISTOPHER S. THROOP, C.B.O. | | BLDG. PLANS EXAMINER ? PX3169 | | (561) 805-7918 | | [email protected] | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND | | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED | | WITH A COPY OF RECEIPT AS APPLICABLE. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2016-05-24 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-05-24 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-05-24 |
Time |
10:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-05-03 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-04-29 |
Time |
06:41 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-04-29 |
Time |
07:07 |
Sent To |
|
|
Notes |
2016-05-03 06:42:24 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16041109 | | 4/29/16 | | | | 1) PROVIDE SHEET M2.2 AS NOTED IN NOTES #4 & 7- SHEET | | M01.02. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|