Plan Review Details - Permit 16040987
Plan Review Stops For Permit 16040987
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-07-05 Cont ID  
Sent By cthroop Date 2016-07-05 Time 13:45 Rev Time 0.00
Received By cthroop Date 2016-07-05 Time 13:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-22 Cont ID  
Sent By cthroop Date 2016-06-22 Time 10:58 Rev Time 0.00
Received By cthroop Date 2016-06-22 Time 10:58 Sent To  
Notes
2016-06-22 11:02:20 
 BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 DATE: 6/22/16
 ACTION: DENIED
  
 1. ALL PROPOSED DOORS ARE TO BE INSTALLED IN RATED
 CORRIDORS. PROVIDE DOCUMENTATION THAT DOORS WILL COMPLY
 WITH THE FOLLOWING REQUIREMENTS:
  
 716.5.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE
 BARRIERS.
 FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE
 PROTECTION RATING OF 20 MINUTES WHERE LOCATED IN
 CORRIDOR WALLS OR SMOKE BARRIER WALLS HAVING A
 FIRE-RESISTANCE RATING IN ACCORDANCE WITH TABLE 716.5
 SHALL BE TESTED IN ACCORDANCE WITH NFPA 252 OR UL 10C
 WITHOUT THE HOSE STREAM TEST.
  
 716.5 FIRE DOOR AND SHUTTER ASSEMBLIES.
 APPROVED FIRE DOOR AND FIRE SHUTTER ASSEMBLIES SHALL BE
 CONSTRUCTED OF ANY MATERIAL OR ASSEMBLY OF COMPONENT
 MATERIALS THAT CONFORMS TO THE TEST REQUIREMENTS OF
 SECTION 716.5.1, 716.5.2 OR 716.5.3 AND THE FIRE
 PROTECTION RATING INDICATED IN TABLE 716.5. FIRE DOOR
 FRAMES WITH TRANSOM LIGHTS, SIDELIGHTS OR BOTH SHALL BE
 PERMITTED IN ACCORDANCE WITH SECTION 716.5.6. FIRE DOOR
 ASSEMBLIES AND SHUTTERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND NFPA
 80.
  
 716.5.7.1 FIRE DOOR LABELING REQUIREMENTS.
 FIRE DOORS SHALL BE LABELED SHOWING THE NAME OF THE
 MANUFACTURER OR OTHER IDENTIFICATION READILY TRACEABLE
 BACK TO THE MANUFACTURER, THE NAME OR TRADEMARK OF THE
 THIRD PARTY INSPECTION AGENCY, THE FIRE PROTECTION
 RATING AND, WHERE REQUIRED FOR FIRE DOORS IN INTERIOR
 EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS BY
 SECTION 716.5.5, THE MAXIMUM TRANSMITTED TEMPERATURE
 END POINT. SMOKE AND DRAFT CONTROL DOORS COMPLYING WITH
 UL 1784 SHALL BE LABELED AS SUCH AND SHALL ALSO COMPLY
 WITH SECTION 716.5.7.3. LABELS SHALL BE APPROVED AND
 PERMANENTLY AFFIXED. THE LABEL SHALL BE APPLIED AT THE
 FACTORY OR LOCATION WHERE FABRICATION AND ASSEMBLY ARE
 PERFORMED.
  
 2. COMPLY WITH FIRE REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By shill Date 2016-05-04 Time 14:31 Rev Time 0.00
Received By shill Date 2016-05-04 Time 14:31 Sent To  
Notes
2016-05-04 14:35:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. NO INFORMATION PROVIDED. PLAN SHOULD INCLUDE
 INFORMATION TO DETERMINE CODE COMPLIANCE. ONLY A
 PRODUCT APPROVAL WAS SUBMITTED FOR A $30,000 DOOR
 REPLACEMENT JOB IN A HIGH RISE.
  
 FBC 107, PROVIDE ENOUGH INFORMATION FOR A REVIEW TO BE
 PERFORMED. AS I HAVE NO INFORMATION REGARDING WHERE THE
 DOORS WILL BE INSTALLED, I CANNOT DETERMINE WHAT
 INFORMATION IS REQUIRED. SOME INFORMATION YOU MAY WANT
 TO CONSIDER PROVIDING:
  
 THRESHOLD INFORMATION (FBC 2014 ACCESSIBILITY)
 PANIC BAR INFO (FBC 2014 1008)
 A PLAN SHOWING LOCATION OF PROPOSED DOOR REPLACEMENT
 (FBC 107)
 BUILDING HEIGHT (ENGINEERING IS REQUIRED FOR BUILDINGS
 OVER 60', FBC 1609)
 IF PANIC BARS ARE NOT PROVIDED, THE PLAN SHOULD SHOW
 WHY IT IS NOT REQUIRED AT THAT LOCATION
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-07-01 Cont ID  
Sent By wjolin Date 2016-07-01 Time 09:17 Rev Time 0.00
Received By wjolin Date 2016-07-01 Time 09:15 Sent To B
Notes
2016-07-01 09:16:581801 NORTH FLAGLER DRIVE
 PERMIT #16040987
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 TRASH ROOMS #113 AND #123 ARE PROTECTED BY FIRE RATED
 WALLS. DOORS WILL REQUIRE A MINIMUM OF A 45-MINUTE FIRE
 RESISTANCE RATING.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-06-08 Cont ID  
Sent By wjolin Date 2016-06-08 Time 10:51 Rev Time 0.00
Received By wjolin Date 2016-06-08 Time 10:42 Sent To B
Notes
2016-06-08 10:51:561801 NORTH FLAGLER DRIVE
 PERMIT #16040987
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 TRASH ROOMS #113 AND #123 ARE PROTECTED BY FIRE RATED
 WALLS; HOWEVER, NO FIRE RATED DOORS/FRAMES HAVE BEEN
 SUBMITTED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By wjolin Date 2016-05-05 Time 13:53 Rev Time 0.00
Received By wjolin Date 2016-05-05 Time 13:51 Sent To  
Notes
2016-05-05 13:53:031801 NORTH FLAGLER DRIVE
 PERMIT #16040987
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INSUFFICIENT INFORMATION PROVIDED TO COMPLETE A PLAN
 REVIEW. NO FLOOR PLANS SUBMITTED, NO QUANTITY OF DOORS
 SUBMITTED, NO FIRE-RATING INFORMATION SUBMITTED, ETC.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-05 Cont ID  
Sent By cthroop Date 2016-07-05 Time 13:45 Rev Time 0.00
Received By cthroop Date 2016-06-29 Time 09:25 Sent To  
Notes
2016-06-30 09:25:50RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-22 Cont ID  
Sent By cthroop Date 2016-06-22 Time 10:57 Rev Time 0.00
Received By cthroop Date 2016-06-03 Time 11:34 Sent To  
Notes
2016-06-03 11:34:45RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-05 Cont ID  
Sent By wjolin Date 2016-05-05 Time 13:53 Rev Time 0.00
Received By wjolin Date 2016-04-21 Time 08:57 Sent To  
Notes
2016-05-04 14:35:575/4 TO FIRE
  
2016-04-22 08:57:47BLDG MISC 1