Plan Review Stops For Permit 16040952 |
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2016-05-16 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-05-16 |
Time |
07:24 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-05-16 |
Time |
06:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2016-04-29 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-04-29 |
Time |
03:48 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-04-29 |
Time |
03:32 |
Sent To |
|
|
Notes |
2016-04-29 03:38:31 | 1) INDICATE THE TYPE OF "FLEX" PIPE SHOWN ON THE GAS | | DRAWING. IS IT CSST? IF SO, SUBMIT THE CORRESPONDING | | EHD NUMBER FOR THE SIZE OF THE TUBING. COMPLY WITH | | TABLE 402.4 (15) OF THE 2014 FGC. NOTE: THERE IS NO | | SIZING TABLE FOR "FLEX" PIPE IN THE GAS CODE. | | 2) IF THE "FLEX" TUBING IS NOT CSST, SUBMIT | | MANUFACTURER'S SPECIFICATIONS (2 COPIES) FOR THIS | | MATERIAL. THE MATERIAL SHALL BE RATED FOR USE WITH | | NATURAL GAS. 2014 FGC SEC.403.1, 403.3. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-05-16 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-05-16 |
Time |
07:25 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-05-13 |
Time |
13:04 |
Sent To |
|
|
Notes |
2016-05-13 13:04:51 | RESUB ROUTED TO TKLARGE |
|
|
|