Plan Review Details - Permit 16040904
Plan Review Stops For Permit 16040904
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-12-22 Cont ID  
Sent By pleduc Date 2016-12-22 Time   Rev Time 0.00
Received By pleduc Date 2016-12-21 Time 11:29 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-12-01 Cont ID  
Sent By pleduc Date 2016-12-01 Time   Rev Time 0.00
Received By pleduc Date 2016-12-01 Time 13:44 Sent To M
Notes
2016-12-01 13:58:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE SUBMITTED PLAN SHEETS ARE NOT BOUND IN PLAN SETS
 AND ARE DISORGAINZED INTO RANDOMED FOLDED SHEETS.
  
 PLEASE ORGANIZE SHEETS IN A LOGICAL ORDER AND HAVE THEM
 BOUND TOGETHER FOR EACH SEPARATE PLAN SET.
  
  
  
 2) THE REVISIONS ARE NOT CLOUDED OR INDICATED IN ANY
 WAY.
  
 PER NFPA 1.14 PLAN REVIEW.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By pleduc Date 2016-04-28 Time   Rev Time 0.00
Received By pleduc Date 2016-04-28 Time 14:08 Sent To M
Notes
2016-04-28 15:54:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PLANS ARE NOT IN AGREEMENT WITH ONES
 SUBMITTED WITH THE ENGINEER OF RECORD. PERMIT #
 15091225.
  
 PROVIDE A NOTE OR REVIEW THAT THE SUBMITTED SHOP
 DRAWINGS ARE IN COMPLIANCE/AGREEMENT WITH THE ABOVE
 PERMIT AND ENGINEER OF RECORD.
  
 I AM REQUESTING/NOT REQUIRING A REVIEW STAMP OR LETTER
 FROM THE ENGINEER OF RECORD TO ENSURE AGREEMENT WITH
 THE ABOVE MASTER PERMIT SET.
  
 2) THE SUBMITTED PLANS ONLY SHOW TWO FLOORS OF
 SPRINKLER DRAWINGS. THE BUILDING IS FOUR FLOORS. THESE
 PLANS ARE INCOMPLETE AND A DETAILED REVIEW WAS NOT
 COMPLETED.
  
 PROVIDE A COMPLETE SET OF DRAWINGS REFLECTING AGREEMENT
 WITH NUMBER 1 ABOVE.
  
 3) BASED ON THE ABOVE, THE HYDRAULIC CALCULATIONS MAY
 NEED ADJUSTMENT/RESUBMITTAL.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON RESUBMITTAL
 OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-27 Cont ID  
Sent By ccole Date 2016-12-27 Time 13:41 Rev Time 0.00
Received By ccole Date 2016-12-16 Time 10:21 Sent To  
Notes
2016-12-19 10:21:14RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-05 Cont ID  
Sent By ccole Date 2016-12-05 Time 12:50 Rev Time 0.00
Received By ccole Date 2016-11-29 Time 10:05 Sent To  
Notes
2016-11-30 10:05:25RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-06 Cont ID  
Sent By ccole Date 2016-05-06 Time 11:10 Rev Time 0.00
Received By ccole Date 2016-04-20 Time 13:12 Sent To  
Notes
2016-04-20 13:12:21ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-01-03 Cont ID  
Sent By ccole Date 2017-01-03 Time 14:11 Rev Time 0.00
Received By ccole Date 2017-01-03 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-12-27 Cont ID  
Sent By ccole Date 2016-12-27 Time 10:49 Rev Time 0.00
Received By ccole Date 2016-12-27 Time 10:48 Sent To  
Notes
2016-12-27 10:59:173RD REVIEW FBC-2014 MECHANICAL
 PERMIT #160409-04
 12/27/16
  
 1) THE PLANS MUST BEAR THE SIGNATURE OF THE PERSON
 RESPONSUIBLE FOR THE DESIGN, OR BEAR THE SHOP DRAWING
 APPROVAL STAMP OF THE ENGINEER OF RECORD- WEST PALM
 BEACH AMENDMENTS TO THE FBC
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND
 DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE
 BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF
 THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR
 THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 107.2.1.1 FIRE PROTECTION SYSTEM SHOP DRAWINGS. SHOP
 DRAWINGS FOR THE FIRE PROTECTION SYSTEM(S)
 SHALL BE SUBMITTED TO INDICATE CONFORMANCE WITH THIS
 CODE AND THE CONSTRUCTION DOCUMENTS AND SHALL
 BE APPROVED PRIOR TO THE START OF SYSTEM INSTALLATION.
 SHOP DRAWINGS SHALL CONTAIN ALL INFORMATION
 AS REQUIRED BY THE REFERENCED INSTALLATION STANDARDS IN
 CHAPTER 9.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-05 Cont ID  
Sent By ccole Date 2016-12-05 Time 12:45 Rev Time 0.00
Received By ccole Date 2016-12-05 Time 12:45 Sent To  
Notes
2016-12-05 12:46:521ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16040904
 12/5/16
  
 1) COMPLY WITH FIRE DEPT. REVIEW COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By ccole Date 2016-05-06 Time 10:42 Rev Time 0.00
Received By ccole Date 2016-05-06 Time 10:42 Sent To  
Notes
2016-05-06 11:14:131ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040904
 5/6/16
  
 1) THE SPRINKER LAYOUT PLANS FOR THE 3RD AND 4TH FLOORS
 WERE NOT SUBMITTED.
 2) PLEASE PROVIDE THE SPECS FOR THE BACKFLOW PREVENTER.
 3) THE PROPOSED FIRE SPRINKLER SYSTEM SHALL BE DESIGNED
 BY A FLORDIA LICENSED ENGINEER IN COMPLIANCE WITH
 SECTION 105.3.1.2 WPB AMENDMENTS TO THE FBC- BUILDING
 CODE. PROVIDE MINIMUM THREE SETS OF SIGNED AND SEALED
 PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  