Plan Review Details - Permit 16040890
Plan Review Stops For Permit 16040890
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-13 Cont ID  
Sent By cthroop Date 2016-07-13 Time 08:43 Rev Time 0.00
Received By cthroop Date 2016-07-13 Time 08:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-11 Cont ID  
Sent By cthroop Date 2016-05-11 Time 15:10 Rev Time 0.00
Received By cthroop Date 2016-05-11 Time 14:18 Sent To M
Notes
2016-05-11 15:25:471ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-7918
 [email protected]
  
 1. CORRECT GOVERNING CODES ON PLAN SHEET CV.1 TO 2014
 FBC.
 2. PROVIDE ENERGY CALCULATIONS.
 3. PROVIDE WIND LOAD ENGINEERING FOR COMPONENETS
 SUBJECT TO WIND LOADS, (DOORS, WINDOWS & SIDING).
 4. PROVIDE FASTENER SCHEDULE FOR DRYWALL PER FBC CHPT
 1, SECTION 110.3.A.2.2.
 5. PROVIDE SHORING DETAIL FOR LOAD BEARING WALL
 REMOVAL.
 6. PROVIDE LANDINGS AT EXT. DOORS PER FBC R311.3.
 7. BUILDING INSULATION SHALL BE PER TABLE R402.1.1.
 8. PROVIDE PRODUCT APPROVALS AND MANUFACTURERS
 INSTALLATION INSTRUCTIONS FOR HARDI-PLANK.
 9. PROVIDE AIR BARRIER PER TABLE R402.4.1.1.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE SIDING
 SUBMITTALS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By mvaldes Date 2016-07-11 Time 18:55 Rev Time 0.00
Received By mvaldes Date 2016-07-11 Time 18:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-25 Cont ID  
Sent By mvaldes Date 2016-04-25 Time 17:08 Rev Time 0.00
Received By mvaldes Date 2016-04-25 Time 16:12 Sent To  
Notes
2016-04-25 17:08:49REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - AFCI PROTECTION REQUIRED PER NEC 210.12 B
 - TAMPER RESISTANT RECEPTACLES REQUIRED PER NEC 406.11
 - MISSING LIGHTING OUTLET FOR ATTIC ESPECIALLY SINCE
 AHU UNIT WILL BE INSTALLED IN THIS SPACE NEC 210.70 3
 - KITCHEN COUNTER-TOP OUTLET SPACING ALONG THE BREAK OF
 THE SINK IS MISSING ADD A GFCI RECEPTACLE ONTO PLANS.
 NEC 210.52 C 1,4
 - LIGHTING SHALL BE 75 % HIGH EFFICIENT AS WELL AS IC
 RATED AND SEALED TO NOT COMPROMISE BUILDING THERMAL
 ENVELOPE. ( 2 CFM ) FBC- E R 402.4.4 / 404.1.1
 - NEC 250.94 PROVIDE AN INTERSYSTEM BONDING TERMINAL
 STRIP IN THE RISER DIAGRAM.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-13 Cont ID  
Sent By cthroop Date 2016-07-13 Time 08:43 Rev Time 0.00
Received By cthroop Date 2016-06-14 Time 09:49 Sent To  
Notes
2016-06-15 09:49:17R12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-12 Cont ID  
Sent By lmarchan Date 2016-05-12 Time 08:00 Rev Time 0.00
Received By lmarchan Date 2016-04-19 Time 11:21 Sent To  
Notes
2016-04-20 11:21:11R12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-12 Cont ID  
Sent By jvalido Date 2016-07-12 Time 17:45 Rev Time 0.00
Received By jvalido Date 2016-07-12 Time 17:31 Sent To  
Notes
2016-07-12 17:45:01FLORIDA ENERGY CODE FBC 2014
  
 ENERGY CALCULATIONS FORM R405-2014 IS NOT SIGNED BY
 OWNER/AGENT.
 EPL IS NOT SIGNED BY BUILDER.
 PROVIDE AHRI FOR SYSTEM BEING INSTALLED.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-05-11 Cont ID  
Sent By jvalido Date 2016-05-11 Time 18:03 Rev Time 0.00
Received By jvalido Date 2016-05-11 Time 18:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-23 Cont ID  
Sent By gjohnson Date 2016-06-23 Time 10:16 Rev Time 0.00
Received By gjohnson Date 2016-06-23 Time 09:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-05 Cont ID  
Sent By gearl Date 2016-05-05 Time 12:57 Rev Time 0.00
Received By gearl Date 2016-05-05 Time 12:57 Sent To  
Notes
***NONE***