Plan Review Details - Permit 16040825
Plan Review Stops For Permit 16040825
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-31 Cont ID  
Sent By pleduc Date 2016-05-31 Time   Rev Time 0.00
Received By pleduc Date 2016-05-25 Time 10:30 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-26 Cont ID  
Sent By pleduc Date 2016-04-26 Time   Rev Time 0.00
Received By pleduc Date 2016-04-19 Time 15:02 Sent To PC
Notes
2016-04-20 15:50:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET AA 102 - EXITING THROUGH A GATE DOOR IS
 INDICATED NEAR CLERKS OFFICE 102. NO INFORMATION IS
 PROVIDED FOR THIS EXIT DOOR INCLUDING EXIT HARDWARE.
 PLEASE PROVIDE DETAILS.
  
 2) SHEET AA 102 - AN 1 HOUR WALL LINE IS INDICATED
 ALONG THE CORRIDOR/WORKSHOP WALL. THIS 1 HOUR WALL
 DESIGN INDICATED A "JOG" AT THE BOTTOM OF THE STAIRS.
 THIS IS INCONSISTANT WILL OTHER SHEET DESIGNS SHOWING A
 STRIGHT WALL. PLEASE CORRECT OR CLARIFY.
  
 3) SHEET 102-105 - THE STAIRS FROM THE MEZZANINE SHOWS
 A DOOR ALONG THE CORRIDOR WALL TO EXIT; HOWEVER, SHEET
 EO101-102 SHOW A DIFFERENT DESIGN. PLEASE CORRECT AND
 CLARIFY WHICH ONE IS ACCURATE.
  
 4) SHEET AA 103 - THE DOORS ALONG THE CORRIDOR OF ROOMS
 116 (JAN. CLOST, 128 (TRAINING STORAGE) AND 122 (IT
 ROOM) OPEN INTO THE EXIT CORRIDOR.PER NFPA 101 CHAPTER
 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE CORRECT.
  
 5) SHEET AA 114 - THE DOOR SCHEDULE INDICATES A FUSIBLE
 LINK FOR DOOR 104 C. IN THE EVENT OF AN ACTIVATION AND
 THE DOOR DEPLOYS, HOW DOES A PERSON EXIT FROM THE
 ISOLATED AREA BY THE ELECRTRICAL AND FACITITY STORAGE
 ROOMS AND AREA? PLEASE REVIEW AND CORRECT.
  
 6) SHEET AA 200-301- INCORRECT REFERENCES TO THE FIRE
 CODE ARE NOTED AND ARE INCONSISTENT ON REFERENCED
 PAGES. THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS
 OF THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
  
 FOR CLARIFICATION AND CORRECTION PURPOSES:
  
 THE CURRENT FLORIDA FIRE PREVENTION CODE, THE 5TH
 EDITION, WAS ADOPED BY THE STATE OF FLORIDA ON DECEMBER
 31, 2014; HOWEVER, IT INCLUDES THE 2012 EDITIONS OF
 NFPA 1 & 101. REFERENCES TO THE 5TH EDITION OR THE 2012
 EDITION OF THE FLORIDA FIRE PREVENTION CODE IS
 SUFFICIENT IN THESE AREAS.
  
 7) SHEET AA 301 - A TRAVEL DISTANCE OF 210 FEET AND 126
 FEET ARE INDICATED FROM WITHIN THE SEPARATE PIT AREAS.
 PER NFPA 101, CHAPTER 40, TABLE 40.2.2, A COMMON PATH
 OF TRAVEL CAN NOT EXCEED 100 FEET. PLEASE REVIEW AND
 CORRECT.
  
 8) SHEET EC 101 - EXIT SIGNS SHOULD DIRECT OCCUPANTS TO
 THE NEAREST EXIT. THE EXIT SIGN 2ND FROM THE NORTH WALL
 INDICATES AN ARROW POINTING AWAY FROM THE NEAREST EXIT.
 PLEASE TURN THIS EXIT ARROW IN THE OTHER DIRECTION
 TOWARDS THE NORTH EXIT DOOR.
  
 9) SHEET EC 101 - THERE IS AN EXIT THAT PASSES THROUGH
 A FENCE GATE TYPE DOOR WITH NO EXIT SIGN AT THAT DOOR.
 PLEASE PROVIDE AN EXIT SIGN AT THE FENCE GATE DOOR.
  
 10) SHEET EP 101 - EXIT SIGNS NEED TO BE INSTALLED AT
 THE CENTER ENDS OF EACH PIT CORRIDOR. THE PROPOSED
 INDICATED EXIT SIGNS CAN NOT BE SEEN ALONG THE LONG
 CORRIDOR.
  
 11) SHEET ECA 302 - A NOTE ADDRESSING THE FA SOUND
 LEVEL WITHIN THE PIT AREA IS INDICATED; HOWEVER, THE IS
 NO INDICATION ACCOUNTING OF VISUAL OR STROBE FA
 DEVICES. PLEASE CORRECT.
  
 12) SHEET FP 103 - THE FLOOR LAYOUT OF THE WORKSHOP AND
 MEZZANINE DOES NOT MATCH SHEET AA 106. PLEASE CORRECT
 AND/OR CONFIRM WHICH ONE.
  
 13) SHEET FP 202 - THERE IS A NOTE INDICATING " FIRE
 PUMP CONTROL CONTROLLER W / ATS. WHAT IS ATS? IT IS NOT
 INDICATED IN THE ABBGREVIATIONS TABLE ON SHEET FP 001.
  
 14) ADDITIONAL COMMENTS MAY BE PROVIDED BASED ON THE
 RESUBMITTAL OF THE ABOVE COMMENTS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-26 Cont ID  
Sent By pleduc Date 2016-04-26 Time   Rev Time 0.00
Received By pleduc Date 2016-04-18 Time 15:10 Sent To  
Notes
2016-04-18 15:10:38BOX OF PLANS ROUTED TO FIRE PLAN REVIEW STATION