Plan Review Details - Permit 16040820
Plan Review Stops For Permit 16040820
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-03 Cont ID  
Sent By cthroop Date 2016-06-03 Time 11:29 Rev Time 0.00
Received By cthroop Date 2016-06-03 Time 11:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-10 Cont ID  
Sent By cthroop Date 2016-05-10 Time 15:24 Rev Time 0.00
Received By cthroop Date 2016-05-10 Time 15:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-03 Cont ID  
Sent By skennedy Date 2016-06-02 Time 11:20 Rev Time 0.00
Received By skennedy Date 2016-06-02 Time 11:19 Sent To  
Notes
2016-06-03 11:21:02REVIEW BY MVALDES

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-09 Cont ID  
Sent By mvaldes Date 2016-05-09 Time 17:57 Rev Time 0.00
Received By mvaldes Date 2016-05-09 Time 17:04 Sent To  
Notes
2016-05-09 17:59:01JOB PERMIT NUMBER: 16040819
 JOB ADDRESS: 314 ALMERIA RD
 WEST PALM BEACH FLORIDA
 DATE: APRIL 20 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - SHOWS OVERHEAD AND UNDERGROUND SERVICE CONDUCTORS ?
 NEC ONLY ALLOWS ONE SERVICE PER BUILDING IN ACCORDANCE
 TO ARTICLE 230.2. IF THE INTENT IS TO METER THE GARAGE
 SEPARATE FROM THE 2ND FLOOR WHY DOES EACH DISCONNECT
 SHOW A RISER ? ELECTRICAL SUB ? PANEL LOCATIONS MUST BE
 SHOWN ON FLOOR PLANS UNLESS THE 100 AMP MAIN BREAKER
 INCLUDES THE BRANCH CIRCUITS TO THEIR PROSPECTIVE
 LOADS. PLEASE CLARIFY SERVICE RISER DIAGRAM LAYOUT?
 - PROVIDE LOAD CALCULATIONS AND A PANEL SCHEDULE
 INDICATING WIRE AND BREAKER SIZES. WPBA 107
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 - FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN
 10 FEET OF EACH SLEEPING ROOM.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By fmittner Date 2016-06-01 Time 11:05 Rev Time 0.00
Received By fmittner Date 2016-06-01 Time 11:05 Sent To E
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-05-05 Cont ID  
Sent By fmittner Date 2016-05-05 Time 14:20 Rev Time 0.00
Received By fmittner Date 2016-05-05 Time 14:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-03 Cont ID  
Sent By cthroop Date 2016-06-03 Time 11:29 Rev Time 0.00
Received By cthroop Date 2016-05-27 Time 14:26 Sent To  
Notes
2016-05-27 14:26:41R05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-10 Cont ID  
Sent By cthroop Date 2016-05-10 Time 15:24 Rev Time 0.00
Received By cthroop Date 2016-04-18 Time 10:40 Sent To  
Notes
2016-04-19 10:40:53R02
 TRAVELLING WITH 16040819

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By gjohnson Date 2016-06-01 Time 16:02 Rev Time 0.00
Received By gjohnson Date 2016-06-01 Time 16:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-06 Cont ID  
Sent By gjohnson Date 2016-05-06 Time 16:45 Rev Time 0.00
Received By gjohnson Date 2016-05-06 Time 16:45 Sent To  
Notes
***NONE***