Plan Review Details - Permit 16040819
Plan Review Stops For Permit 16040819
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-09 Cont ID  
Sent By cthroop Date 2016-06-09 Time 10:16 Rev Time 0.00
Received By cthroop Date 2016-06-09 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-10 Cont ID  
Sent By cthroop Date 2016-05-10 Time 15:02 Rev Time 0.00
Received By cthroop Date 2016-05-10 Time 13:30 Sent To  
Notes
2016-05-10 15:09:451ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-7918
 [email protected]
  
 1. STATE GOVERNING CODES ON PLANS.
 2. PROVIDE WINDOW SCHEDULE.
 3. PROVIDE PRODUCT APPROVALS FOR NEW EXT. WINDOWS AND
 DOORS.
 4. PROVIDE WIND LOAD ENGINEERING FOR ALL PRODUCTS
 SUBJECT TO WIND LOADS.
 5. PROVIDE FRAMING DETAIL FOR ALL MODIFIED OPENINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW, AND
 DOOR SUBMITTALS.
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-08 Cont ID  
Sent By mvaldes Date 2016-06-08 Time 16:59 Rev Time 0.00
Received By mvaldes Date 2016-06-08 Time 16:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-09 Cont ID  
Sent By mvaldes Date 2016-05-09 Time 16:59 Rev Time 0.00
Received By mvaldes Date 2016-05-09 Time 15:35 Sent To  
Notes
2016-05-09 17:01:39JOB PERMIT NUMBER: 16040819
 JOB ADDRESS: 314 ALMERIA RD
 WEST PALM BEACH FLORIDA
 DATE: APRIL 20 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - RISER DIAGRAM GROUNDING DETAIL TO INCLUDE INTERSYSTEM
 BONDING TERMINAL. NEC 250.94
 - PANEL SCHEDULE MISSING BATHROOM CIRCUIT WHICH SHALL
 BE 12 AWG WIRE AND 20 AMP OCPD. NEC 210.11(C)(3)
 - ADD THE FOLLOWING GENERAL ELECTRICAL NOTES , TAMPER
 RESISTANT RECEPTACLES NEC 406.11 , AND AFCI PROTECTION
 PER NEC 210.12(B)
 - FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN
 10 FEET OF EACH SLEEPING ROOM.
 - RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT , AS
 WELL AS IC RATED AND SEALED TO NOT COMPROMISE BUILDING
 THERMAL ENVELOPE. ( 2 CFM ) FBC-ER 404.1.1 / 402.4.4
 - SWITCHES SHALL HAVE A GROUNDED CONDUCTOR AT THE
 SWITCH LOCATION IN ACCORDANCE WITH NEC 404.2(C)
 - NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, PANELBOARDS.
 - SHOW A/C HANDLER AND COMPRESSOR UNITS ON FLOOR PLANS
 SHOWING DISCONNECTING MEANS. WPBA 107
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-06-03 Cont ID  
Sent By gjohnson Date 2016-06-03 Time 16:05 Rev Time 0.00
Received By gjohnson Date 2016-06-03 Time 16:05 Sent To  
Notes
2016-06-03 16:07:35GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By fmittner Date 2016-06-01 Time 15:34 Rev Time 0.00
Received By fmittner Date 2016-06-01 Time 15:34 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-05-05 Cont ID  
Sent By fmittner Date 2016-05-05 Time 14:17 Rev Time 0.00
Received By fmittner Date 2016-05-05 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-09 Cont ID  
Sent By cthroop Date 2016-06-09 Time 10:16 Rev Time 0.00
Received By cthroop Date 2016-05-27 Time 15:57 Sent To  
Notes
2016-05-27 15:57:17R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-10 Cont ID  
Sent By cthroop Date 2016-05-10 Time 15:01 Rev Time 0.00
Received By cthroop Date 2016-04-18 Time 10:33 Sent To  
Notes
2016-04-19 10:33:26R02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-07 Cont ID  
Sent By jvalido Date 2016-06-07 Time 17:54 Rev Time 0.00
Received By jvalido Date 2016-06-07 Time 17:54 Sent To  
Notes
2016-06-07 17:56:36R23

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-09 Cont ID  
Sent By jvalido Date 2016-05-09 Time 17:19 Rev Time 0.00
Received By jvalido Date 2016-05-09 Time 17:00 Sent To  
Notes
2016-05-09 17:15:48WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED
  
 FLORIDA ENERGY CODE - SECTION R202 RENOVATED BUILDINGS
 - A RESIDENTIAL OR NONRESIDENTIAL BUILDING UNDERGOING
 ALTERATION THAT VARIES INSULATION, HVAC SYSTEMS, WATER
 HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS,
 PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE.
  
 R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
 PROVIDE ENERGY AND HEAT LOAD CALCULATIONS.
  
 PROVIDE AHRI.
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 PROVIDE CONDENSER TIE DOWN SCHEDULE.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-03 Cont ID  
Sent By gjohnson Date 2016-06-03 Time 16:01 Rev Time 0.00
Received By gjohnson Date 2016-06-03 Time 16:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By gjohnson Date 2016-05-06 Time 16:35 Rev Time 0.00
Received By gjohnson Date 2016-05-06 Time 06:36 Sent To  
Notes
2016-05-06 08:28:421ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE DETAILED SCOPE OF WORK FOR PLUMBING. PER WPB
 AMEND. TO FBC SEC. 107.2.1
  
 2. PROVIDE CODE COMPLIANT RISER DIAGRAM SHOW ALL TRAPS
 ON LAVATORY'S, SHOWERS, TUBS ,WASHING MACHINE , BIDET
 AND SINKS. PER WPB AMEND. TO FBC SEC. 107.3.5.3(11)
  
 3. MASTER BATHROOM SHOW WATER CLOSET AND BIDET
 CONNECTED TO HORIZONTAL DRAIN SEPARATELY. PER FBC RES
 SEC. P3108.1
  
 4. BAR SINK AND COFFE BAR SINK SHOW WASTE ARM ON
 VERTICAL STACK AND SHOW VENT. PER FBC RES SEC. P3101.1
  
 5. SECOND FLOOR SHOW LAVATORY WASTE ARM TIED INTO
 VERTICAL VENT. PER FBC RES SEC. P3101.1
  
 6. SHOW LAUNDRY SINK OFF VERTICAL STACK. PER FBC RES
 SEC. P3101.1
  
 7. SHOW WASHING MACHINE STAND PIPE AND P-TRAP OFF
 VERTICAL STACK. PER FBC RES SEC. P3101.1
  
 8. PROVIDE CLEAN OUTS AT THE BASE OF SOIL AND WASTE
 STACKS PER FBC PL P3005.2.6
  
 9.PROVIDE A WATER RISER DIAGRAM. PER WPB AMEND. TO FBC
 SEC. 107.3.5.3(11)
  
 10. PROVIDE EXISTING FLOOR PLAN. PER WPB AMEND. TO FBC
 SEC. 107.2.1