Plan Review Details - Permit 16040779
Plan Review Stops For Permit 16040779
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-18 Cont ID  
Sent By jgomez Date 2016-08-18 Time 16:41 Rev Time 0.00
Received By jgomez Date 2016-08-18 Time 15:28 Sent To  
Notes
2016-08-18 17:04:04BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE
 INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS):
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) ARCHED ENTRY DOOR (USE OF EXISTING HISTORIC ENTRY
 DOOR WAS APPROVED BY ROBERT BROWN (BUILDING OFFICIAL).
 THE DOOR STILL NEEDS TO COMPLY WITH THE PRODUCT
 APPROVAL REQUIREMENT. PROVIDE LOCAL PRODUCT APPROVAL
 APPLICATION AND COMPLETE ENGINEERING PACKAGE (2 COPIES)
 FOR BUILDING OFFICIAL APPROVAL.
 B) FLAT ROOF WITH APPROVED ASSEMBLY AS SPECIFIED ON
 PLANS.
 C) PRECAST LINTELS AS SHOWN ON PLANS.
 D) ROOF TILE ADHESIVE. SEE ROOF TILE NOA FOR LISTED
 ADHESIVES.
 2- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS.
 3- NEW GEOTECHNICAL REPORT SUBMITTED (2 COPIES) TO HAVE
 THE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTE.
  
 IMPORTANT:
 (1) ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL AT
 (561)805-6724 AND [email protected] TO AVOID CONFLICTS OR
 DELAYS.
 (2) SPECIAL INSPECTOR IS REQUIRED FOR THE CONSTRUCTION
 OF AUGER CAST PILES. PLEASE COORDINATE WITH KEN CONRAD
 (CHIEF BUILDING INSPECTOR) AT (561)805-6666 AND
 [email protected] FOR APPROVAL OF SPECIAL INSPECTOR TO
 AVOID CONFLICTS OR DELAYS.
 (3) PROVIDE PILES SHOP DRAWINGS APPROVED BY THE
 STRUCTURAL ENGINEER OF RECORD.
 (4) SPECIAL INSPECTOR IS REQUIRED FOR THE CONCRETE
 CONSTRUCTION AS REQUIRED BY SEC. 110.3.9 CITY
 AMENDMENTS. (CONCRETE STRENGTH DESIGN IS MORE THAN 3000
 PSI). PLEASE COORDINATE WITH KEN CONRAD (CHIEF BUILDING
 INSPECTOR) AT (561)805-6666 AND [email protected] FOR
 APPROVAL OF SPECIAL INSPECTOR TO AVOID CONFLICTS OR
 DELAYS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-29 Cont ID  
Sent By jgomez Date 2016-07-27 Time 14:17 Rev Time 0.00
Received By jgomez Date 2016-07-27 Time 14:10 Sent To  
Notes
2016-07-27 14:31:15NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 ****NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH "PROVISO" ONCE THE
 ENERGY CALCULATIONS COMMENTS ARE ADDRESSED. PERMIT MAY
 BE ISSUED AND REQUIRED INFORMATION MAY BE SUBMITTED
 LATER PRIOR TO INSPECTIONS TO AVOID CONFLICTS OR
 DELAYS. FEES MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO
 OPTION IS REQUESTED AT THIS TIME OR IF RE-SUBMITTING
 REQUIRED INFORMATION BEFORE ISSUING THE PERMIT.
  
  
 ORIGINAL COMMENT:
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FESS ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
 RESPONSE:
 PLANS SUBMITED HAVE THE PBC STAMP (MU-2016-16556). BUT
 SUBMITTAL IS MISSING THE COPY OF THE PAID RECEIPT.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO CERTIFY AND DATE THE ENERGY
 CALCULATIONS AT THE BOTTOM OF THE FORM AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). NOTE: BOTH FORMS MAIN HOUSE AND
 GARAGE/APARTMENT.
  
 B) CONTRACTOR TO COMPLETE THE EPL DISPLAY CARD AS
 REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). NOTE: BOTH FORMS MAIN HOUSE AND
 GARAGE/APARTMENT.
  
 C) COMPLETE THE INSPECTION COMPONENT CRITERIA TABLE
 402.4.1.1 SUBMITTED. SEC. R405.4.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). NOTE: BOTH FORMS MAIN
 HOUSE AND GARAGE/APARTMENT.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) ARCHED ENTRY DOOR AS SHOWN ON PLANS.
 RESPONSE:
 USE OF EXISTING HISTORIC ENTRY DOOR WAS APPROVED BY
 ROBERT BROWN (BUILDING OFFICIAL). THE DOOR STILL NEEDS
 TO COMPLY WITH THE PRODUCT APPROVAL REQUIREMENT. THIS
 MAY BE ACCOMPLISHED BY APPLYING FOR ONE TIME LOCAL
 PRODUCT APPROVAL. PROVIDE COMPLETE ENGINEERING ANALYSIS
 FOR LOCAL PRODUCT APPROVAL TO BE REVIEWED AND APPROVED
 BY THE BUILDING OFFICIAL. PLEASE CONTACT ROBERT BROWN
 FOR SUBMITTAL PACKAGE REQUIREMENTS. NOTE: IF THERE IS
 GLAZING IN THE DOOR, THEN SUBMITT HURRICANE IMPACT
 PROTECTION INFORMATION AT TIME OF ENTRY DOOR LOCAL
 PRODUCT APPROVAL SUBMITTAL.
  
 B) FLAT ROOF NOA 13-1217.01 SUBMITTED:
 (1) SELECTED ASSEMBLY ON PAGE 30 OF 33 IS FOR AN
 NON-INSULATED ROOF SYSTEM. ARCHITECTURAL PLANS CALL FOR
 R-21 MIN. RIGID INSULATION (SEE KEY NOTE #0703 ON
 ARCHITECTURAL PLANS). NEED TO SELECT ASSEMBLY WITH
 RIGID INSULATION AS SPECIFIED BY THE ARCHITECT. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED BY GENERAL LIMITATION
 #7. ASSEMBLIES WITH GENERAL LIMITATION #9 DON'T ALLOW
 RAS 117 CALCULATIONS.
  
 ORIGINAL COMMENT:
 C) PRECAST LINTELS AS SHOWN ON PLANS.
 RESPONSE:
 NOT SUBMITTED.
  
 ORIGINAL COMMENT:
 D) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF
 RECORD. (NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY ROOF
 TILE FASTENING. SEE ITEM # 5 BELOW).
 RESPONSE:
 (1) NOA 12-0529.01 SUBMITTED EXPIRED ON 01/03/16. NEED
 CURRENT NOA.
 (2) ROOF TILE ADHESIVE RTA-1 IS NOT LISTED ON THE ROOF
 TILE NOA SUBMITTED. THIS ADHESIVE NEEDS TO BE LISTED ON
 THE ROOF TILE OR COMPLETE PROVIDE COMPLETE PRODUCT
 APPROVAL INFORMATION AND APPLY FOR LOCAL PRODUCT
 APPROVAL FOR PROPOSED INSTALLATION. LOCAL PRODUCT
 APPROVAL TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 ORIGINAL COMMENT:
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO VERIFY
 COMPLIANCE WITH THE COMPONENTS AND CLADDING DESIGN
 PRESSURES.
 RESPONSE:
 THE STRUCTURAL ENGINEER OF RECORD IS THE ONE THAT NEEDS
 TO APPROVE THE PRODUCT APPROVALS. PRODUCT APPROVALS ARE
 FOR COMPONENTS AND CLADDING. THAT'S WHY THE STRUCTURAL
 ENGINEER NEEDS TO APPROVE THEM. NOTE: ENGINEER TO
 PROVIDE REVIEW STAMP ON EACH PRODUCT APPROVAL OR TO
 PROVIDE LETTER THAT CLEARLY IDENTIFY EACH PRODUCT
 APPROVAL (NOA OR FLORIDA PRODUCT APPROVAL NUMBER,
 MODEL, ETC,) REVIEW LETTER SUBMITTED BY THE ARCHITECT
 IS NOT ACCEPTABLE BECAUSE IS TOO GENERAL. THERE IS NO
 WAY OF REFERENCING WHICH SPECIFIC PRODUCT APPROVALS
 WERE APPROVED.
  
 ORIGINAL COMMENT:
 5- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN ADHESIVE PRODUCT
 APPROVAL IS REQUIRED. (NOTE: DESIGNER OF RECORD TO
 SPECIFY THE MINIMUM ATTACHMENT RESISTANCE REQUIRED FOR
 THIS BUILDING. SEE NOA 14-0605.03 SUBMITTED FOR
 REFERENCE).
 RESPONSE:
 DESIGNER OF RECORD IS REQUIRED TO SPECIFY SPECIFIC
 FASTENING OPTION. THE PRODUCT APPROVAL IS TO VERIFY
 THAT IT MEETS THE DESIGNER OF RECORD SPECIFICATIONS.
 RESPONSE LETTER STATING "SEE ATTACHED NOA" DOESN'T
 ADDRESS THIS REQUIREMENT.
  
 6- NEW GEOTECHNICAL REPORT SUBMITTED (2 COPIES) NEEDS
 TO HAVE THE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
  
 IMPORTANT FOR YOUR INFORMATION:
 (1) ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL AT
 (561)805-6724 AND [email protected] TO AVOID CONFLICTS OR
 DELAYS.
  
 (2) SPECIAL INSPECTOR IS REQUIRED FOR THE CONSTRUCTION
 OF AUGER CAST PILES. PLEASE COORDINATE WITH KEN CONRAD
 (CHIEF BUILDING INSPECTOR) AT (561)805-6666 AND
 [email protected] FOR APPROVAL OF SPECIAL INSPECTOR TO
 AVOID CONFLICTS OR DELAYS.
  
 (3) PROVIDE PILES SHOP DRAWINGS APPROVED BY THE
 STRUCTURAL ENGINEER OF RECORD.
  
 (4) PLEASE CONTACT/COORDINATE ALL ELEVATIONS
 CERTIFICATES WITH SAMANTHA HILL TO AVOID CONFLICTS OR
 DELAYS AFTER PERMIT IS ISSUED.
 SAMANTHA HILL
 PHONE: 805-6724 EXT: 6724
 E-MAIL: [email protected]
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
 FROM: [email protected] [[email protected]]
 SENT: THURSDAY, JUNE 30, 2016 8:12 PM
 TO: MARTHA BURITICA
 CC: [email protected]; [email protected]; RICK GONZALEZ;
 [email protected]
 SUBJECT: RE: 15040_GREEN RESIDENCE HISTORIC
 RECONSTRUCTION - PERMIT #16040779
  
 MARTHA,
 I HAVE DISCUSSED THE USE OF THE EXISTING DOOR WITH BOTH
 RICK GONZALEZ AND JULIO GOMEZ. I EXPECT THAT YOU GOT
 FEEDBACK FROM THEM. IN CASE YOU DID NOT, PLEASE NOTE
 THAT I TOLD THEM THAT USING THE ORIGINAL DOOR IS OK
 PROVIDED THERE IS AT LEAST ONE OTHER SWING DOOR THAT
 CAN BE USED TO EXIT THE PROPERTY, WITHOUT GOING THROUGH
 A GARAGE. OF COURSE, THAT DOOR MUST MEET THE MINIMUM
 WIDTH REQUIREMENT.
 REGARDS
  
 ROBERT BROWN, CBO
 BUILDING OFFICIAL / BUILDING DIVISION MANAGER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? BUILDING DIVISION
 (561) 805 6652
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-02 Cont ID  
Sent By jgomez Date 2016-05-27 Time 16:59 Rev Time 0.00
Received By jgomez Date 2016-05-27 Time 18:11 Sent To  
Notes
2016-05-25 17:03:07NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FESS ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- A)THIS PROPERTY IS LOCATED IN THE FLOOD ZONE A5. THE
 INFORMATION SHOWN ON THE ELEVATION CERTIFICATE AND
 SURVEY SUBMITTED DON'T MATCH. ELEVATIONS SHOWN ON THE
 ELEVATION CERTIFICATE ARE BASED ON THE NGVD 1929, WHILE
 ELEVATIONS SHOWN ON THE SURVEY ARE BASED ON THE NAVD
 1988. THE FLOOD INSURANCE RATE MAP (FIRM) DATED MARCH
 1, 1979 IS BASED ON NGVD 1929. REVISE ALL THE
 INFORMATION ON THE SURVEY AS REQUIRED USING THE CORRECT
 ELEVATION DATUM. ALSO, COORDINATE INFORMATION WITH THE
 ELEVATION CERTIFICATE PROVIDED.
 CITY ORDINANCE ARTICLE XVII- FLOOD PREVENTION AND
 CONTROL SEC. 94-542.
  
 B) ELEVATION CERTIFICATE SUBMITTED SPECIFIES ATTACHED
 GARAGE. DRAWINGS SUBMITTED SHOW A DETACHED GARAGE.
 REVISE AS REQUIRED TO MATCH PLANS. PROVIDE AN ELEVATION
 CERTIFICATE FOR EACH BUILDING. CITY ORDINANCE ARTICLE
 XVII- FLOOD PREVENTION AND CONTROL SEC. 94-542.
 NOTE: COORDINATE ELEVATION CERTIFICATES WITH SAMANTHA
 HILL AT (561)805-6712 AND [email protected].
  
 3- SHEET S-1:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR THE AUGER CAST
 PILES "P-1", INCLUDING THE REQUIRED LENGTH. SEC. R301.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) TRELLIS DETAIL IS MISSING THE CONNECTION OF 2-2"X8"
 WOOD BEAM TO WOOD POST.. SEC. R301.1 FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 C) COORDINATE CONCRETE SLAB FINISH ELEVATIONS WITH
 PROPOSED FINISH ELEVATIONS SHOWN ON THE ELEVATION
 CERTIFICATE AND REVISED SURVEY. SEE ITEM # 2(A) ABOVE.
 ALSO, COORDINATE FINISH FLOOR ELEVATION WITH ALL THE
 STRUCTURAL AND ARCHITECTURAL PLANS TO AVOID CONFLICT OR
 DELAYS.
 NOTE: THE GARAGE SLAB IS PITCHED DOWN TO THE FRONT OF
 THE GARAGE. THEREFORE, THE LOWEST FINISH FLOOR
 ELEVATION NEED TO BE INDICATED BY THE GARAGE ENTRANCE.
  
 4- SURVEY SHOWS PROPOSED RETENTION WALLS. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL RETENTION WALLS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- SHEET S-5:
 A) CLARIFY WHY THE DESIGN PRESSURES FOR THE PRIMARY
 BUILDING AND THE ACCESSORY BUILDING ARE SO DIFFERENT.
 REVISE AS REQUIRED. PROVIDE THE CORRECT DESIGN
 PRESSURES FOR BOTH BUILDINGS ACCORDING TO THE EXPOSURE
 "D", BUILDING HEIGHT, ROOF ZONE AND WALL ZONE (
 INTERIOR OR END). SEC. R301.1 FBC-RESIDENTIAL.
  
 B) UPDATE NOTES FOR THE PRIMARY BUILDING AND THE
 ACCESSORY BUILDING . NOTES REFERENCE SEC. 1609.1.5 OF
 THE 2010 FBC. SPECIFY CURRENT CODE AND SECTION. CHAPTER
 553 FLORIDA STATUTE.
  
 6- ENTRY DOOR SIZE MAY NOT COMPLY WITH THE EGRESS
 REQUIREMENTS OF SEC. R311.2 FBC-RESIDENTIAL. PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT THE 34" WIDE
 DOOR WILL PROVIDE 32" CLEAR WIDTH OPENING.
  
 7- BEDROOM #2 WINDOWS MAY NOT COMPLY WITH THE EGRESS
 REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL. PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT THE 30"X64"
 SINGLE HUNG WINDOW WILL PROVIDE 5.7 S.F. CLEAR OPENING.
  
 8- SHEET A-1.02:
 A) REVISE EMERGENCY OVERFLOW NOTE ON THE ROOF STORM
 DRAIN SCHEDULE. THE NOTE READS: "EMERGENCY OVERFLOW
 (EO) AT FROM 2" MAX. ABOVE ROOF LOWEST ELEV.".
 ACCORDING TO SEC. R903.4.1 FBC-RESIDENTIAL THE OVERFLOW
 NEED TO BE "NOT LESS THAN 2 INCHES NOR MORE THAN 4
 INCHES ABOVE THE FINISHED ROOF COVERING AND SHALL BE
 LOCATED AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS OR DOWNSPOUTS OR WALL AND PARAPET SCUPPERS".
 REVISE AS REQUIRED.
  
 B) LOCATION OF THE EMERGENCY OVERFLOW SCUPPERS FOR DECK
 1 AND DECK 2 DON'T COMPLY WITH SEC. R903.4.1
 FBC-RESIDENTIAL. LOCATION TO BE AS CLOSE AS POSSIBLE TO
 THE MAIN SCUPPER. REVISE AS REQUIRED.
  
 9- SPECIFY SIZE AND LOCATION OF ATTIC ACCESS AT MASTER
 BEDROOM AND BEDROOM #1 SHOWING COMPLIANCE WITH SEC.
 R807 FBC-RESIDENTIAL.
  
 10- SHEET A-8.01:
 A) THE WINDERS OF THE FIRST FLOOR AND SECOND FLOOR
 STAIR PLANS NEED TO COMPLY WITH THE 6" MIN. TREAD DEPTH
 AS REQUIRED BY SEC. R311.7.5.2.1 FBC-RESIDENTIAL.
  
 B) REVISE THE WOOD STAIR DETAIL "A". SEE SEC.
 R311.7.5.2 TO SEE HOW THE TREAD IS MEASURED. AND, NEED
 TO ADD THE NOSING AS REQUIRED BY SEC. R311.7.5.2.1
 FBC-RESIDENTIAL. ALSO, UPDATE THE FIRESTOPPING CODE
 SECTION R4409.7.2.3. THIS SECTION APPLIES TO HIGH
 VELOCITY HURRICANE ZONES ONLY.
  
 C) UPDATE THE STAIRS GENERAL NOTES. THE CURRENT CODE IS
 FBC-RESIDENTIAL, 5TH EDITION (2014) NOT FBC 2010. ALSO,
 REFER TO CORRECT SECTION REGARDING FIRESTOPPING . SEC.
 R4409.7.2.3 APPLIES TO HIGH VELOCITY HURRICANE ZONES
 ONLY.
  
 11- SPECIFY DRAFTSTOPPING LOCATION AND MATERIALS ON THE
 SECOND FLOOR FLOOR/CEILING ASSEMBLY AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL.
  
 12- ENERGY CALCULATIONS:
 A) PROVIDE ENERGY CALCULATIONS FOR EACH SEPARATE
 BUILDING: MAIN HOUSE AND GARAGE/APARTMENT. SEC. R101.3
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. ADDRESS IS INCORRECT.. PROVIDE OWNER'S NAME,
 BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION NUMBER.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) CEILING INSULATION ON ITEM #10 TO MATCH R-VALUE
 SPECIFIED ON PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 D) CEILING IS NOT VENTED. SEE PLANS. REVIEW ITEM #10 AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 E) FLOOR INFORMATION FOR RAISED FLOOR AND FLOOR OVER
 OTHER SPACE (ABOVE GARAGE) DOESN'T MATCH PLANS. THERE
 IS CONCRETE SLAB ON SECOND FLOOR DECKS (NOT WOOD
 JOISTS) AND THERE IS A CONCRETE SLAB ABOVE THE GARAGE.
 REVISE AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) NEED INSULATION BETWEEN GARAGE AND APARTMENT ABOVE.
 SEC. R402.4.1.1 AND TABLE R402.4.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 13- ARCHITECTURAL PLANS TO PROVIDE DETAIL AND
 SPECIFICATIONS FOR THE INSULATION IN WALLS, CEILINGS,
 FLOOR BETWEEN GARAGE AND APARTMENT ABOVE. COORDINATE
 WITH THE ENERGY CALCULATIONS TO AVOID CONFLICTS. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ARCHED ENTRY DOOR AS SHOWN ON PLANS.
  
 B) DOUBLE HUNG WINDOW THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER (+51/-68). FLORIDA PRODUCT
 APPROVAL FL14477-R2 SUBMITTED IS GOOD FOR +/-65PSF.
  
 C) OVERHEAD GARAGE DOORS THAT MEET THE CALCULATED
 DESIGN PRESSURES SHOWN ON PLANS.
  
 D) PITCHED ROOF UNDERLAYMENT. LIMITATION #2 OF THE
 FLORIDA PRODUCT APPROVAL FL17322-R1 SUBMITTED SPECIFIES
 THAT WIND UPLIFT RESISTANCE IS NOT WITHIN THE SCOPE OF
 THIS EVALUATION. NEED TO PROVIDE INFORMATION SHOWING
 COMPLIANCE WITH THE WIND RESISTANCE BASED ON THE
 PROPOSED INSTALLATION. COORDINATE WITH ITEM # 16 BELOW.
 CLEARLY SPECIFY WHICH UNDERLAYMENT IS GOING TO BE USED.
 ALSO, PROVIDE ROOF TILE PRODUCT APPROVAL THAT LISTS
 THIS UNDERLAYMENT..
  
 E) "FLAT ROOF BASE SHEET" NOA 13-1113.05 SUBMITTED IS
 FOR SLOPED ROOFS ONLY. PROVIDE PRODUCT APPROVAL FOR
 FLAT ROOF ASSEMBLIES. AND, CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF THE DESIGN PRESSURES OF
 THE SELECTED ASSEMBLY DON'T MEET THE DESIGN PRESSURES
 FOR ALL THE ROOF ZONES.
  
 F) "FLAT ROOF WATERPROOFING" NOA 12-0418.02 SUBMITTED
 IS FOR INSULATED WOOD DECK ASSEMBLIES. THERE ARE NO
 INSULATED WOOD DECK ASSEMBLIES IN THIS PROJECT. PROVIDE
 PRODUCT APPROVAL FOR FLAT ROOF ASSEMBLIES. COORDINATE
 WITH ITEM #14(E) ABOVE. ALSO, REMEMBER THAT THERE ARE
 SOME CONCRETE DECKS SHOWN ON PLANS. PROVIDE PRODUCT
 APPROVAL FOR SUCH ASSEMBLIES.
  
 G) PRECAST LINTELS AS SHOWN ON PLANS.
  
 H) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 I) IPE TILE ROOF DECK PEDESTAL SYSTEM. NEED TO SHOW
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 J) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, SECTIONS AND DETAILS. AND, UPDATE FLORIDA
 PRODUCT APPROVALS LISTED ON THE TRUSS CONNECTOR. NEED
 TO SPECIFY CONNECTORS THAT ARE APPROVED UNDER THE 2014
 CODE VERSION. NUMBERS LISTED ARE FOR AN OLDER CODE.
 PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR OR DESIGNER OF RECORD
 TO LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 H) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO VERIFY
 COMPLIANCE WITH THE COMPONENTS AND CLADDING DESIGN
 PRESSURES.
  
 16- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING
 AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN ADHESIVE PRODUCT
 APPROVAL IS REQUIRED.
  
 17- PROVIDE ICC EVALUATION REPORT FOR THE SPRAY
 INSULATION TO BE USED. AND, DESIGNER OF RECORD TO
 REVIEW AND APPROVE IT PRIOR TO SUBMITTAL TO THIS
 OFFICE. SEC. R316 FBC-RESIDENTIAL.
  
 18- CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR IMPACT
 PROTECTION FOR THE ENTRY DOOR. AND, IF USING THIS
 PRODUCT, THEN PROVIDE COMPLETE INSTALLATION SCHEDULE
 SHOWING PROPOSED INSTALLATION BASED ON THE PRODUCT
 APPROVAL SUBMITTED AND SPECIFIC CONDITION OF THE HOUSE.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 19- PROVIDE COMPLETE INFORMATION FOR THE FACTORY BUILT
 FIREPLACE AND CHIMNEY SHOWING THE LISTING AND LABELING
 IN ACCORDANCE WITH UL 127 AS REQUIRED BY SEC. R1004 AND
 R1005 FBC-RESIDENTIAL.
 AND, DESIGNER OF RECORD TO APPROVE PACKAGE PRIOR TO
 SUBMITTAL.
  
 NOTES:
 (1) ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL AT
 (561)805-6724 AND [email protected] TO AVOID CONFLICTS OR
 DELAYS.
  
 (2) SPECIAL INSPECTOR IS REQUIRED FOR THE CONSTRUCTION
 OF AUGER CAST PILES. PLEASE COORDINATE WITH KEN CONRAD
 (CHIEF BUILDING INSPECTOR) AT (561)805-6666 AND
 [email protected] FOR APPROVAL OF SPECIAL INSPECTOR TO
 AVOID CONFLICTS OR DELAYS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-20 Cont ID  
Sent By vperez Date 2016-05-20 Time 11:46 Rev Time 0.00
Received By vperez Date 2016-05-19 Time 17:56 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-05-09 Cont ID  
Sent By gjohnson Date 2016-05-09 Time 14:51 Rev Time 0.00
Received By gjohnson Date 2016-05-09 Time 14:51 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2016-08-12 Cont ID  
Sent By fmittner Date 2016-08-12 Time 17:14 Rev Time 0.00
Received By fmittner Date 2016-08-12 Time 17:14 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2016-07-22 Cont ID  
Sent By fmittner Date 2016-07-22 Time 09:54 Rev Time 0.00
Received By fmittner Date 2016-07-22 Time 09:54 Sent To  
Notes
2016-07-22 10:00:11STRUCTURAL AND ARCHITECTURAL PLANS DO NOT MATCH FOR
 WINDOW CHANGE.
2016-07-22 09:59:22PLANS INDICATE A REPLICATED FRONT ENTRY (0905) ALONG
 WITH OTHER "REPLICATED" ASPECTS. BOARD APPROVED SALVAGE
 AND REINSTALLATION NOT USE OF POLYSTYRENE

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By fmittner Date 2016-05-05 Time 14:50 Rev Time 0.00
Received By fmittner Date 2016-05-05 Time 14:50 Sent To  
Notes
2016-05-05 14:51:30ELEVATIONS, SPECIFICALLY WINDOW SIZES AND SHAPES DO NOT
 MATCH WHAT THE HPB APPROVED. EXAMPLE SOUTH FACING
 FRENCH DOORS ON SECOND FLOOR OF PRIMARY STRUCTURE NOW
 ARCHED, ORIGINALLY FLAT. QUESTIONS, CONTACT FRIEDERIKE
 MITTNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-18 Cont ID  
Sent By jgomez Date 2016-08-18 Time 18:59 Rev Time 0.00
Received By jgomez Date 2016-08-12 Time 10:24 Sent To  
Notes
2016-08-12 10:25:01RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-29 Cont ID  
Sent By jgomez Date 2016-07-29 Time 07:37 Rev Time 0.00
Received By jgomez Date 2016-07-08 Time 13:23 Sent To  
Notes
2016-07-11 13:23:30R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-02 Cont ID  
Sent By jgomez Date 2016-06-02 Time 09:02 Rev Time 0.00
Received By jgomez Date 2016-04-15 Time 10:43 Sent To  
Notes
2016-04-18 10:43:41R32

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-07-29 Cont ID  
Sent By jgomez Date 2016-07-27 Time 17:19 Rev Time 0.00
Received By jgomez Date 2016-07-27 Time 17:19 Sent To  
Notes
2016-07-27 17:19:29$120.65 PAID. MU-2016-16556.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-05-25 Cont ID  
Sent By jgomez Date 2016-05-25 Time 17:03 Rev Time 0.00
Received By jgomez Date 2016-05-25 Time 17:03 Sent To  
Notes
2016-05-25 17:04:081- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FESS ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-05-23 Cont ID  
Sent By jvalido Date 2016-05-23 Time 16:26 Rev Time 0.00
Received By jvalido Date 2016-05-23 Time 14:14 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2016-05-25 Cont ID  
Sent By jgomez Date 2016-05-25 Time 15:39 Rev Time 0.00
Received By jgomez Date 2016-05-25 Time 15:39 Sent To  
Notes
2016-05-25 15:40:44SENT E-MAIL TO SAMANTHA HILL WHEN PERMIT IS ISSUED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-09 Cont ID  
Sent By gjohnson Date 2016-05-09 Time 14:51 Rev Time 0.00
Received By gjohnson Date 2016-05-09 Time 13:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2016-08-18 Cont ID  
Sent By jgomez Date 2016-08-18 Time 18:28 Rev Time 0.00
Received By jgomez Date 2016-08-18 Time 18:28 Sent To  
Notes
2016-08-18 18:53:09ROOFING REVIEW APPROVED WITH PROVISO (PROVIDE
 INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS):
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
  
 A) FLAT ROOF ASSEMBLY AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 APPROVED:
 (1) ROOF TILE NOA NO 14-0605.03.
  
 (2) SEALOFLEX ROOF SYSTEM OVER CONCRETE NOA NO
 12-0418.04.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-07-29 Cont ID  
Sent By jgomez Date 2016-07-29 Time 14:37 Rev Time 0.00
Received By jgomez Date 2016-07-29 Time 07:36 Sent To  
Notes
2016-07-29 14:39:421- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
  
 A) FLAT ROOF NOA 13-1217.01 SUBMITTED:
 (1) SELECTED ASSEMBLY ON PAGE 30 OF 33 IS FOR AN
 NON-INSULATED ROOF SYSTEM. ARCHITECTURAL PLANS CALL FOR
 R-21 MIN. RIGID INSULATION (SEE KEY NOTE #0703 ON
 ARCHITECTURAL PLANS). NEED TO SELECT ASSEMBLY WITH
 RIGID INSULATION AS SPECIFIED BY THE ARCHITECT. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED BY GENERAL LIMITATION
 #7. ASSEMBLIES WITH GENERAL LIMITATION #9 DON'T ALLOW
 RAS 117 CALCULATIONS.
  
 B) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF
 RECORD. (NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY ROOF
 TILE FASTENING).
 RESPONSE:
 (1) NOA 12-0529.01 SUBMITTED EXPIRED ON 01/03/16. NEED
 CURRENT NOA.
 (2) ROOF TILE ADHESIVE RTA-1 IS NOT LISTED ON THE ROOF
 TILE NOA SUBMITTED. THIS ADHESIVE NEEDS TO BE LISTED ON
 THE ROOF TILE OR COMPLETE PROVIDE COMPLETE PRODUCT
 APPROVAL INFORMATION AND APPLY FOR LOCAL PRODUCT
 APPROVAL FOR PROPOSED INSTALLATION. LOCAL PRODUCT
 APPROVAL TO BE APPROVED BY THE BUILDING OFFICIAL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-06-02 Cont ID  
Sent By jgomez Date 2016-06-02 Time 09:03 Rev Time 0.00
Received By jgomez Date 2016-06-02 Time 09:02 Sent To  
Notes
2016-06-02 09:07:071- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) PITCHED ROOF UNDERLAYMENT. LIMITATION #2 OF THE
 FLORIDA PRODUCT APPROVAL FL17322-R1 SUBMITTED SPECIFIES
 THAT WIND UPLIFT RESISTANCE IS NOT WITHIN THE SCOPE OF
 THIS EVALUATION. NEED TO PROVIDE INFORMATION SHOWING
 COMPLIANCE WITH THE WIND RESISTANCE BASED ON THE
 PROPOSED INSTALLATION. COORDINATE WITH ITEM # 16 BELOW.
 CLEARLY SPECIFY WHICH UNDERLAYMENT IS GOING TO BE USED.
 ALSO, PROVIDE ROOF TILE PRODUCT APPROVAL THAT LISTS
 THIS UNDERLAYMENT..
  
 B) "FLAT ROOF BASE SHEET" NOA 13-1113.05 SUBMITTED IS
 FOR SLOPED ROOFS ONLY. PROVIDE PRODUCT APPROVAL FOR
 FLAT ROOF ASSEMBLIES. AND, CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF THE DESIGN PRESSURES OF
 THE SELECTED ASSEMBLY DON'T MEET THE DESIGN PRESSURES
 FOR ALL THE ROOF ZONES.
  
 C) "FLAT ROOF WATERPROOFING" NOA 12-0418.02 SUBMITTED
 IS FOR INSULATED WOOD DECK ASSEMBLIES. THERE ARE NO
 INSULATED WOOD DECK ASSEMBLIES IN THIS PROJECT. PROVIDE
 PRODUCT APPROVAL FOR FLAT ROOF ASSEMBLIES. COORDINATE
 WITH ITEM #14(E) ABOVE. ALSO, REMEMBER THAT THERE ARE
 SOME CONCRETE DECKS SHOWN ON PLANS. PROVIDE PRODUCT
 APPROVAL FOR SUCH ASSEMBLIES.
  
 D) IPE TILE ROOF DECK PEDESTAL SYSTEM. NEED TO SHOW
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 E) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO VERIFY
 COMPLIANCE WITH THE COMPONENTS AND CLADDING DESIGN
 PRESSURES.
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN ADHESIVE PRODUCT
 APPROVAL IS REQUIRED.
  
  
 APPROVED PRODUCT APPROVALS:
  
 1- ALTUSA "S" CLAY ROOF TILE NOA 14-0605.03

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2016-09-21 Cont ID  
Sent By kconrad Date 2016-09-21 Time 11:16 Rev Time 0.00
Received By kconrad Date 2016-09-21 Time 11:16 Sent To  
Notes
2016-09-21 11:21:55RECEIVED (3) ORIGINAL SETS OF THE RESIDENT INSPECTOR
 AGREEMENT: SCOPE OF WORK IS FOR AUGERCAST PILING
 INSTALLATION ONLY TO BE PERFORMED BY ARDAMAN AND
 ASSOCITES ONLY; ROBERTO BALBIS, PE.

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-22 Cont ID  
Sent By fmittner Date 2016-07-22 Time 09:59 Rev Time 0.00
Received By fmittner Date 2016-07-22 Time 09:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-05 Cont ID  
Sent By fmittner Date 2016-05-05 Time 14:50 Rev Time 0.00
Received By fmittner Date 2016-05-05 Time 14:49 Sent To  
Notes
***NONE***