Plan Review Details - Permit 16040726
Plan Review Stops For Permit 16040726
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-02 Cont ID  
Sent By pleduc Date 2016-05-02 Time   Rev Time 0.00
Received By pleduc Date 2016-05-02 Time 16:26 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-18 Cont ID  
Sent By pleduc Date 2016-04-18 Time   Rev Time 0.00
Received By pleduc Date 2016-04-18 Time 10:17 Sent To M
Notes
2016-04-18 10:46:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PLAN INDICATES A PROPOSED WATER
 CURTAIN ON GLASS WALLS. EACH SECTION OF GLASS WALL HAS
 DOOR THAT OPEN. A WATER CURTAIN IN THIS INSTALLTION IS
 A MISAPPLICATION OF THE CODE AS A WATER CURTAIN CAN NOT
 PROTECT AN OPENING. IT CAN PROTECT FIXED GLASS.
  
 WHAT IS THE INTENT OF THE WATER CURTAIN. IS THE WALL
 REQUIRED TO BE RATED?
  
 PLEASE REVIEW WITH THE ENGINEER OF RECORD.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-26 Cont ID  
Sent By lmarchan Date 2016-04-26 Time 08:15 Rev Time 0.00
Received By lmarchan Date 2016-04-14 Time 16:12 Sent To  
Notes
2016-04-14 16:12:13ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-04-25 Cont ID  
Sent By jvalido Date 2016-04-25 Time 17:06 Rev Time 0.00
Received By jvalido Date 2016-04-25 Time 17:06 Sent To  
Notes
***NONE***