Plan Review Details - Permit 16040635
Plan Review Stops For Permit 16040635
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-11-07 Cont ID  
Sent By cthroop Date 2016-11-07 Time 09:47 Rev Time 0.00
Received By cthroop Date 2016-11-07 Time 09:47 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-09 Cont ID  
Sent By cthroop Date 2016-08-09 Time 09:24 Rev Time 0.00
Received By cthroop Date 2016-08-09 Time 09:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-20 Cont ID  
Sent By cthroop Date 2016-07-20 Time 11:44 Rev Time 0.00
Received By cthroop Date 2016-07-20 Time 11:44 Sent To  
Notes
2016-07-20 11:46:21PLAN SHEET D1.0 MISSING FROM 2ND SET OF PLANS. OK FOR
 APPLICANT TO SUBMIT SHEET D1.0 UPON RE-SUBMITTAL FOR
 MECH. REVIEW PER SAK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-29 Cont ID  
Sent By cthroop Date 2016-04-29 Time 08:29 Rev Time 0.00
Received By cthroop Date 2016-04-29 Time 08:11 Sent To Z
Notes
2016-04-29 08:36:251ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. PROVIDE FLOOR PLAN WITH DEMENSIONS. CANNOT VERIFY
 EGRESS REQUIREMENTS PER FBC CHPT. 10.
 2. PROVIDE DETAIL FOR BASE PLATE TO FLOOR CONNECTION.
 3. PROVIDE DETAIL FOR TOP PLATE TO CEILING CONNECTION.
 4. PROVIDE DOOR SCHEDULE. CANNOT VERIFY DOORS COMPLY
 WITH EGRESS REQUIREMENTS PER FBC CHPT. 1008.
 5. PROVIDE DETAIL FOR WALL TYPE @ NEW CONFERENCE ROOM.
 6. PROVIDE DESIGN OCCUPANT LOAD.
 7. LICENSED FLORIDA ARCHITECT TO SIGN AND SEAL
 DRAWINGS.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
 FS 481.229 -EXCEPTIONS; EXEMPTIONS FROM LICENSURE.
 (1) NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN
 ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS
 FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR
 ALTERATION OF:
 (A) ANY BUILDING UPON ANY FARM FOR THE USE OF ANY
 FARMER, REGARDLESS OF THE COST OF THE BUILDING;
 (B) ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE BUILDING,
 TOWNHOUSE, OR DOMESTIC OUTBUILDING APPURTENANT TO ANY
 ONE-FAMILY OR TWO-FAMILY RESIDENCE, REGARDLESS OF COST;
 OR
 (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER BUILDING
 INTENDED FOR PUBLIC USE, PROVIDED THAT THE SERVICES OF
 A REGISTERED ARCHITECT SHALL NOT BE REQUIRED FOR MINOR
 SCHOOL PROJECTS PURSUANT TO S. 1013.45.
  
  
 FBC-107.1 GENERAL - FAC 61G1-16.004 - A TITLE BLOCK
 MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT
 ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED.
 (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO
 BE A CORPORATION, LIMITED LIABILITY COMPANY,
 PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME,
 OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN
 HIS OR HER OWN NAME.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-18 Cont ID  
Sent By mvaldes Date 2016-07-18 Time 09:20 Rev Time 0.00
Received By mvaldes Date 2016-07-18 Time 08:34 Sent To B
Notes
2016-07-18 09:24:13REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S :
  
 - ADD EXIT/EMERGENCY COMBOS AS RED LINED IN BY FIRE
 REVIEWER FBC 1011 & 1006.2
  
 - OCCUPANCY SENSORS SHALL BE INSTALLED IN BATHROOMS AS
 WELL AS OFFICES PER FBC E SECTION C405.2.2.2
  
 - ALL BATHROOMS RECEPTACLE SHALL BE GFCI PROTECTED IN
 ACCORDANCE WITH NEC 210.8(B)(1)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-29 Cont ID  
Sent By mvaldes Date 2016-04-18 Time 09:55 Rev Time 0.00
Received By mvaldes Date 2016-04-18 Time 09:18 Sent To  
Notes
2016-04-18 09:57:28JOB PERMIT NUMBER: 16040635
 JOB ADDRESS: 4807 GEORGIA AVENUE
 WEST PALM BEACH FLORIDA
 DATE: APRIL 18 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 410.36 B LUMINAIRES SHALL BE SECURELY FASTENED TO
 THE FRAMING MEMBER BY MECHANICAL MEANS. SUSPENDED
 CEILING SHALL HAVE ADEQUATE STRENGTH TO ATTACH LIGHTING
 OR THE LUMINAIRES SHALL BE INDEPENDENTLY SECURED.
 - ADD A NOTE TO COMPLY WITH FLORIDA BUILDING ENERGY
 CODE SECTION C 405 MANDATORY LIGHTING CONTROLS.
 - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 - ALL ELECTRICAL BOXES IN DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED
 STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE
 RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE
 SEALING MATERIALS.
 - IMPORTANT NOTICE ALL RE ? USED CIRCUITS FOR DIFFERENT
 APPLICATIONS SHALL BE RE ? IDENTIFIED IN THE PANEL
 BOARD DIRECTORY. NEC 408.4 A
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-08-04 Cont ID  
Sent By lmarchan Date 2016-11-04 Time 10:41 Rev Time 0.00
Received By pleduc Date 2016-08-04 Time 15:44 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-07 Cont ID  
Sent By pleduc Date 2016-07-07 Time   Rev Time 0.00
Received By pleduc Date 2016-07-07 Time 09:41 Sent To  
Notes
2016-07-07 09:56:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) AS PREVIOUSLY NOTED AS A PROVISO COMMENT, PROVIDE
 EXITS SIGNS WHERE INDICATED PER NFPA 101, CHAPTER 7
 MEANS OF EGRESS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-14 Cont ID  
Sent By pleduc Date 2016-04-14 Time   Rev Time 0.00
Received By pleduc Date 2016-04-14 Time 15:22 Sent To  
Notes
2016-04-14 15:41:02THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PROVIDE AN EXIT SIGN AT THE NEWLY CREATED ACCESS TO
 THE FRONT EXIT PER NFPA 101, CHAPTER 39 EXISTING
 BUSINESS OCCUPANCIES AND
  
 39.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 39.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS,
 SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 10:15 Rev Time 0.00
Received By ccole Date 2016-11-04 Time 10:41 Sent To  
Notes
2016-11-04 10:41:40RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-04 Cont ID  
Sent By lmarchan Date 2016-11-04 Time 10:41 Rev Time 0.00
Received By lmarchan Date 2016-07-26 Time 16:04 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-20 Cont ID  
Sent By cthroop Date 2016-07-20 Time 11:44 Rev Time 0.00
Received By cthroop Date 2016-06-30 Time 14:14 Sent To  
Notes
2016-06-30 14:14:19B08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-04 Cont ID  
Sent By cpuell Date 2016-05-04 Time 14:24 Rev Time 0.00
Received By cpuell Date 2016-04-12 Time 10:39 Sent To  
Notes
2016-04-13 10:39:22B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-08-09 Cont ID  
Sent By cthroop Date 2016-08-09 Time 09:24 Rev Time 0.00
Received By cthroop Date 2016-08-09 Time 09:24 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-04-29 Cont ID  
Sent By cthroop Date 2016-04-29 Time 09:46 Rev Time 0.00
Received By cthroop Date 2016-04-29 Time 09:46 Sent To  
Notes
2016-04-29 09:48:331ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 11:10 Rev Time 0.00
Received By ccole Date 2016-11-07 Time 10:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-08-09 Cont ID  
Sent By ccole Date 2016-08-09 Time 11:34 Rev Time 0.00
Received By ccole Date 2016-08-09 Time 11:34 Sent To  
Notes
2016-08-09 11:41:463RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16040635
 8/9/16
  
 1) SHEET A1.1: THE AC PLAN IS INCOMPLETE: A) SHOW THE
 RELOCATED DUCT RUNS AND INCLUDE DUCT SIZES. B) INDICATE
 THE SUPPLY AND RETURN CFMS AT EACH NEW OR RELOCATED
 DIFFUSER OR GRILL.
  
 2) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS. I HAVE
 RE-PRINTED IT BELOW- PLEASE COMPLY.
  
 REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-05 Cont ID  
Sent By ccole Date 2016-07-05 Time 12:21 Rev Time 0.00
Received By ccole Date 2016-07-05 Time 12:21 Sent To  
Notes
2016-07-05 12:28:462ND REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16040635
 7/5/16
  
 1) AS PREVIOUSLY REQUESTED, PROVIDE MECHANICAL PLANS.
 THE SUBMITTED RESPONSE NARRATIVE FROM BUTLER
 CONSTRUCTION STATES THAT MECHANICAL PLANS HAVE BEEN
 ATTACHED, AND THERE IS A REFERENCE TO THEM ON SHEET
 A1.0, HOWEVER NO PLANS HAVE BEEN SUBMITTED.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-29 Cont ID  
Sent By ccole Date 2016-04-18 Time 11:40 Rev Time 0.00
Received By ccole Date 2016-04-18 Time 11:40 Sent To  
Notes
2016-04-18 11:45:401ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040635
 4/18/16
  
 1) PROVIDE MECHANICAL PLANS- SECTION 107.3.5.1.4 WPB
 AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-03 Cont ID  
Sent By ajones Date 2016-05-03 Time 10:54 Rev Time 0.00
Received By ajones Date 2016-05-03 Time 10:54 Sent To  
Notes
***NONE***