Plan Review Details - Permit 16040583
Plan Review Stops For Permit 16040583
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-06-28 Cont ID  
Sent By jwitmer Date 2016-06-28 Time   Rev Time 0.00
Received By jwitmer Date 2016-06-28 Time 15:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-06 Cont ID  
Sent By jwitmer Date 2016-06-06 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2016-06-06 Time 09:33 Sent To  
Notes
2016-06-06 11:00:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040583
 ADD: 915 N DIXIE HWY
 CONT: CONSTRUCTION & REMODELING 1
 TEL: 561-667-9924
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JUNE 06/ 2016
 ACTION: DENIED
  
 1-8) COMPLIED.
  
 9) 1ST REVIEW OF M1 & M2. SHEET M1 SHOWS 3 ROOF TOP
 CONDENSING UNITE ON A STAND. SHEET M2 HEADING A/C
 EQUIPMENT SCHEDULE INDICATES THE REPLACEMENT OF (4)
 UNITS. THERE IS NO INFORMATION IF THERE IS AN EXISITNG
 ROOFTOP STAND, IF IT IS BEING REUSED. NOR IS THERE
 INFORMATION ON THE ANCHORING OF THE A/C CONDENSOR
 UNITS?
 ON THE M1 SHEET I CAN NOT LOCATE WHERE THE (4) TH A/C
 SYSTEM & CONDNSOR IS TO BE LOCATED?
  
 9A) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 9B) 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 9C) 2014 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON
 ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877
 MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT
 APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE
 FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) HIGH OR WALKING ON ROOFS HAVING A SLOPE
 GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE). PERMANENT LADDERS INSTALLED TO
 PROVIDE THE REQUIRED.
  
 9D) 2014 FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE
 PROVIDED WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN
 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A
 WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED
 MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR
 GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN
 DIAMETER.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-11 Cont ID  
Sent By jwitmer Date 2016-05-11 Time 16:26 Rev Time 0.00
Received By jwitmer Date 2016-05-11 Time 14:25 Sent To  
Notes
2016-05-11 16:26:46BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040583
 ADD: 915 N DIXIE HWY
 CONT: CONSTRUCTION & REMODELING 1
 TEL: 561-667-9924
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 11/2014
 ACTION: DENIED
  
 1A) SHEET A1/ COVERSHEETPLEASE CORRECT THE CODE THIS
 PLAN WAS DEVELOPED. THE 2014 FBC-B WAS ADOPTED
 STATEWIDE ON JUNE 30/ 2015. PLEASE REVIEW PLANS AND
 UPDATE THE PLANS TO THE CURRENT CODE.
  
 1B) THIS IS AN EXISITNG BUILDING, PLEASE IDENTIFY FROM
 THE 2014 EXISITNG BLDG. CODE WHAT METHOD THE PLANS WERE
 DEVELOPED?
 2014 EXISTING BLDG. CODE 301.1 THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. APPLICATION OF A METHOD SHALL BE THE
 SOLE BASIS FOR ASSESSING THE COMPLIANCE OF WORK
 PERFORMED UNDER A SINGLE PERMIT UNLESS OTHERWISE
 APPROVED BY THE CODE OFFICIAL.
  
 2) MISSING INFORMATION FOR THE BASIC PLAN REVIEW. 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 OCCUPANCY TYPE
 BLDG TYPE: IIIB/ NON-SPRINKLERED
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
  
 3) SHEET A-1. IT APPEARS THERE IS A BUSINESS OCCUPANCY
 AND A ACCESSORY STORAGE COMPONENT. THE COMMON PATH OF
 TRAVEL IS EXCEEDED. TABLE 1014.3 ALLOWS COMMON PATH OF
 TRAVEL OF 75 FEET WITH AN OCCUPANT LOAD GREATER THAN 30
 IN A NON-SPRINKLERED BUILDING. THE STORAGE COMPONENT OF
 THE OCCUPANCY IS LESS THAN 10% OF THE FLOOR PLATE
 (INCLUDING THE 101 SQ. FT. ON THE MEZZANINE LEVE)
 MAKING THE STORAGE ANCILLARY TO THE MAIN OCCUPANCY AND
 NOT A MIXED OCCUPANCY. THE ISSUE IS SECOND MEANS OF
 EGRESS THROUGH THE STORAGE COMPONENT AND IS NOT
 ALLOWED. FBC-B 1014.2(4) EGRESS SHALL NOT PASS THROUGH
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES. A NEW SECOND EGRESS WILL NEED TO BE PROVIDED
 NOT THROUGH THE WAREHOUSE AREA.
  
 4) PLEASE PROVIDE A SURVEY FOR THIS BUILDING SINCE BOTH
 THE FRONT DOOR AND REAR DOORS SWING OUT. 2014 FBC-B
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
 ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL
 BE PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS
 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT
 OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
  
 5) SHEET A1 INDICATES A RAMP BUT THE CHANGE IN
 ELEVATION IS NOT GIVEN. PLEASE PROVIDE THE CHANGE OF
 GRADE AS WELL AS THE LENGTH OF THE RAMP. FBC-B 1010.9
 HANDRAILS. RAMPS WITH A RISE GREATER THAN 6 INCHES (152
 MM) SHALL HAVE HANDRAILS ON BOTH SIDES. HANDRAILS SHALL
 COMPLY WITH SECTION 1012.
  
 6) SHEET D-1 SHOWS NEW OPENINGS INTHE EXTERIOR WALL,
 COLUMNS BEING REMOVED FOR THE NEW OVERHEAD DOOR, THERE
 ARE NO STRUCTURAL PLANS INDICATING HOW THE STRUCTURAL
 INTEGRATY OF THE BUILDING IS TO BE MAINTAINED. PART OF
 THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM) IS BEING
 REMOVED?
  
 7) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 8) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) PLEASE NOTE NO MECHANICAL PLANS WERE SUBMITTED.
 ADDTIONAL COMMENTS MAY ARISE IF ADDITIONAL FRESH AIR OR
 ADDTIONAL AIR CONDITIONED AIR IS REQUIRED. 107.2.1.3.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-08 Cont ID  
Sent By mvaldes Date 2016-06-08 Time 13:26 Rev Time 0.00
Received By mvaldes Date 2016-06-08 Time 13:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-18 Cont ID  
Sent By mvaldes Date 2016-04-18 Time 14:38 Rev Time 0.00
Received By mvaldes Date 2016-04-18 Time 11:06 Sent To  
Notes
2016-04-18 14:39:44JOB PERMIT NUMBER: 16040583
 JOB ADDRESS: 915 N DIXIE HIGHWAY
 WEST PALM BEACH FLORIDA 33401
 DATE: APRIL 18 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 - ALL ELECTRICAL BOXES IN DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED
 STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE
 RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE
 SEALING MATERIALS.
 - ADD EMERGENCY LIGHTS AND EXIT SIGNS IN MEZZANINE AREA
 PLUS MEANS OF EGRESS STAIRWAYS ACCORDING TO FBC 1006.2
 & 1011
 - PLEASE CLEARLY STATE THE OCCUPATION OF EACH AREA FOR
 THE PURPOSE IT SERVES ON THE ELECTRICAL FLOOR PLANS.
 WPBA 107
 - NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 - NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY.
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 - REVISE RISER DIAGRAM ARRANGEMENTS SO THAT THE METER
 ENCLOSURE IS BEFORE MAIN DISCONNECT AS PER FPL
 STANDARDS , READJUST ACCORDINGLY AND PROVIDE A FEEDER
 SCHEDULE TO INCLUDE CONDUIT TYPE.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-06-24 Cont ID  
Sent By pleduc Date 2016-06-24 Time   Rev Time 0.00
Received By pleduc Date 2016-06-24 Time 13:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-31 Cont ID  
Sent By pleduc Date 2016-05-31 Time   Rev Time 0.00
Received By pleduc Date 2016-05-31 Time 14:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By pleduc Date 2016-04-13 Time   Rev Time 0.00
Received By pleduc Date 2016-04-13 Time 15:49 Sent To  
Notes
2016-04-13 16:58:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 1 - AN OCCUPANCY TYPE IS NOT INDICATED.
 PLEASE PROVIDE THE PROPOSED OCCUPANY TYPE.
  
 2) SHEET A 1 - AN OCCUPANCY CALCULATION AND LOAD IS NOT
 INDICATED. PLEASE PROVIDE AN OCCUPANCY CALCULATION AND
 LOAD.
  
 3) SHEET A 1 - THE COMMON PATH OF TRAVEL FROM THE
 MEZZANINE IS NOT INDICATED AND SHALL COMPLY WITH THE
 APPROPRIATE OCCUPANCY CHAPTER OF NFPA 101.
  
 4) SHEET A 1 - EXITING THROUGH THE WAREHOUSE AREA IS
 INDICATED. EXITING THROUGH THE WAREHOUSE IS NOT
 PERMITED PER NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 7.5 ARRANGEMENT OF MEANS OF EGRESS.
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS
 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR
 SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO
 LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS
 PERMITTED FOR THE OCCUPANCY BY CHAPTER 18, 19, 22, OR
 23.
  
 5) SHEET A 1 - A RAMP IS INDICATED IS INDICATED IN THE
 MEANS OF EGRESS.
  
 NO RAMP DETAIL IS INDICATED.
  
 NO HANDRAILS OR HANDRAIL DETAILS IS INDICATED.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 7.2.5 RAMPS.
 7.2.5.1 GENERAL. EVERY RAMP USED AS A COMPONENT IN A
 MEANS OF EGRESS SHALL CONFORM TO THE GENERAL
 REQUIREMENTS OF SECTION 7.1 AND TO THE SPECIAL
 REQUIREMENTS OF 7.2.5.
  
 7.2.5.4 GUARDS AND HANDRAILS.
 7.2.5.4.1 GUARDS COMPLYING WITH 7.2.2.4 SHALL BE
 PROVIDED FOR RAMPS, UNLESS OTHERWISE PROVIDED IN
 7.2.5.4.4.
 7.2.5.4.2 HANDRAILS COMPLYING WITH 7.2.2.4 SHALL BE
 PROVIDED ALONG BOTH SIDES OF A RAMP RUN WITH A RISE
 GREATER THAN 6 IN. (150 MM), UNLESS OTHERWISE PROVIDED
 IN 7.2.5.4.4.
  
 PLEASE PROVIDE DETAILS SHOWING COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-07-08 Cont ID  
Sent By ccole Date 2016-07-08 Time 14:10 Rev Time 0.00
Received By ccole Date 2016-07-06 Time 11:04 Sent To  
Notes
2016-07-07 11:04:55RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-28 Cont ID  
Sent By   Date 2016-06-28 Time   Rev Time 0.00
Received By lmarchan Date 2016-06-22 Time 10:37 Sent To  
Notes
2016-06-22 10:37:36C24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-08 Cont ID  
Sent By mvaldes Date 2016-06-08 Time 13:27 Rev Time 0.00
Received By mvaldes Date 2016-05-25 Time 10:25 Sent To  
Notes
2016-05-26 10:25:26C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-11 Cont ID  
Sent By jwitmer Date 2016-05-11 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2016-04-12 Time 11:37 Sent To  
Notes
2016-04-12 11:38:54C12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-05-11 Cont ID  
Sent By jwitmer Date 2016-05-11 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2016-05-11 Time 16:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2016-07-14 Cont ID  
Sent By ccole Date 2016-07-14 Time 16:22 Rev Time 0.00
Received By ccole Date 2016-07-14 Time 16:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-07-08 Cont ID  
Sent By ccole Date 2016-07-08 Time 12:38 Rev Time 0.00
Received By ccole Date 2016-07-08 Time 12:03 Sent To  
Notes
2016-07-08 14:00:574TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040585
 7/8/16
  
 IN AN EFFORT TO HELP EXPEDITE THE APPROVAL OF THE
 MECHANICAL PLANS, PLEASE REVIEW THE COMMENTS BELOW AND
 CONTACT ME AT YOUR EARLIEST CONVENIENCE.
  
 1) REFER TO SECTION 105.3.1.2 WPB AMENDMENTS TO THE
 FBC: THE SUBMITTED AC CALCULATIONS MUST EITHER BEAR THE
 SIGNATURE AND SEAL OF THE MECHANICAL ENGINEER OF
 RECORD, OR BEAR THE SIGNATURE OF THE INSTALLING AC
 CONTRACTOR.
  
 2) DUCT SMOKE DETECTORS WHERE REQUIRED BY SECTION
 606.2.1 SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS.
  
 3) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 INSTALLATION OF THE ROOFTOP CONDENSERS, THE CONDENSER
 STANDS, AND EXHAUST FANS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-06-27 Cont ID  
Sent By ccole Date 2016-06-27 Time 15:33 Rev Time 0.00
Received By ccole Date 2016-06-27 Time 15:33 Sent To  
Notes
2016-06-27 16:01:023RD REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CODES
 PERMIT 16040583
 6/27/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 PROPOSED AC SYSTEMS- SECTION C403.2.1 CALCULATION OF
 HEATING AND COOLING LOADS FBC-14 ENERGY CONSERVATION.
  
 2) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTION C101.4.3.
  
 3) M-1: PROVIDE THE CORRECT RETURN AIR SYMBOL FOR AHU-1
 AT THE HVAC ROOM, AND AT THE OFFICE 101 RISER.
  
 4) M-1: NO RETURN AIR DUCT IS SHOWN FOR AHU-3 AT THE
 HVAC ROOM.
  
 5) M-1: THE OAI-1 APPEARS TO BE MISLABELED AS EAO-2
  
 6) CLARIFY IF THERE IS A DOOR FOR THE HVAC ROOM AND
 INDICATE THE TYPE AND SIZE.
  
 7) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF ALL
 ROOF TOP EQUIPMENT AND CLEARANCE DISTANCES FOR AIR
 INTAKES TO EXHAUST AND VENT OUTLETS- SEE SECTION 401.4
 FBC-14 MECHANICAL
  
 8) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE O/A INAKES
 AND RELIEF EXHAUSTS THAT WILL AUTOMATICALY SHUT WHEN
 THE SYSTEMS OR SPACES ARE NOT IN USE- SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-06-02 Cont ID  
Sent By ccole Date 2016-06-02 Time 11:47 Rev Time 0.00
Received By ccole Date 2016-06-02 Time 11:47 Sent To  
Notes
2016-06-02 12:21:322ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040583
 6/2/16
  
 1) SUBMIT AC CHANGEOUT FORMS AND AHRI CERTIFICATES FOR
 THE SYSTEMS BEING REPLACED AS INDICATED ON SHEET M-2.
  
 2) THE SCOPE OF WORK FOR MECHANICAL IS NOT CLEAR: THE
 1ST FLOOR AND MEZZANINE DUCT LAYOUT PLANS ON M-1 ARE
 LABELED AS "EXISTING", HOWEVER THE HVAC NOTES ON M-2
 APPEAR TO INDICATE ALL NEW DUCT WORK, EXHAUST FANS, AND
 OTHER COMPONENTS. PLEASE CLARIFY AND USE LETTERED
 SYMBOLS SUCH AS "E" FOR EXISTING, "N" FOR NEW, "R" FOR
 RELOCATED AT DIFFUSER AND GRILL LOCATIONS, USE DOTTED
 LINES TO INDICATE REMOVED OR RELOCATED DUCTS AND SOLID
 LINES TO INDICATE NEW, REPLACED, OR RELOCATED DUCTS. IN
 REGARD TO THE EXISTING PLANS PLEASE REVIEW THESE
 COMMENTS:
  
 A) LABEL THE 8X6 DUCT IN THE OFFICE 108 AND THE CFMS.
 B) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 OPEN AREA SHOWN ON THE 1ST FLOOR, CLARIFY WHY EXHAUST
 IS NEEDED (WHAT PROCESSES OR WORK IS BEING CONDUCTED IN
 THE ROOM?), AND LABEL THE EXHAUST DUCT TERMINATION
 LOCATION.
 C) PROVIDE WIND LOAD DEIGN CRITERIA AND ENGINEERED
 DETAILS FOR INSTALLATION OF THE NEW ROOF TOP CONDENSER
 AND CONDENSER STANDS, AND EXHAUST TERMINATION CAPS-
 SECTION 301.15.
 D) THE TOILET ROOM EXHAUST FANS SHALL HAVE CAPACITIES
 OF 70 CFMS EACH PER TABLE 403.3 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-14 Cont ID  
Sent By ccole Date 2016-04-14 Time 14:25 Rev Time 0.00
Received By ccole Date 2016-04-14 Time 14:25 Sent To  
Notes
2016-04-14 14:48:261ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 16040583
 4/14/16
  
 1) THE APPLICATION AND ELECTRICAL PLANS EACH INDICATE
 AC SYSTEMS HOWEVER NO MECHANICAL PLANS, DOCUMENTS, AND
 SPECIFICATIONS WERE SUBMITTED FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  